OpenSep 22, 2026
building section · this notice includes violations for the areas noted.
242 turk st. in unit #307 unless otherwise noted.
OpenSep 22, 2026
building section · eliminate cockroach infestation (1001-b, 1306 sfhc)
at the time of inspection, an extensive cockroach infestation was observed throughout unit #307, with live cockroach activity present in all areas of the unit inspected. have a licensed pest control company treat all areas of the unit and building as necessary to eliminate the cockroach infestation. provide all pest control reports to the housing inspector at the time of reinspection.
OpenSep 22, 2026
building section · repair bathroom lighting (1001(b)(10) sfhc)
at the time of inspection, the bathroom light fixtures were inoperable and did not provide illumination. lighting in other areas of the unit was operable at the time of inspection. repair or replace the bathroom light fixtures and restore proper illumination.
OpenSep 22, 2026
building section · repair leak under kitchen sink (1001 sfhc)
at the time of inspection, water was observed pooling and being collected beneath the kitchen sink. locate the source of the leak and repair or replace the affected plumbing components in an approved manner to eliminate the leak.
OpenSep 22, 2026
building section · repair kitchen faucet (1306 sfhc)
at the time of inspection, the kitchen faucet fixture was observed detaching from the sink at its base. repair or replace the kitchen faucet fixture as necessary so that it is properly secured and maintained in a sanitary condition.
OpenSep 22, 2026
building section · repair electrical outlets/cover plates (1001(e) sfhc)
at the time of inspection, multiple electrical outlet covers throughout the unit were damaged. repair or replace all damaged outlet covers throughout the unit. if repair work requires alteration of the existing electrical wiring or other work requiring an electrical permit, obtain all required permits.
OpenSep 22, 2026
building section · repair smoke alarm (911(c) sfhc)
at the time of inspection, a smoke alarm was observed hanging from the ceiling by its electrical wires. properly install, test, and maintain the smoke alarm in accordance with the manufacturer¿s recommendations.
OpenSep 22, 2026
building section · repair bathroom ventilation (504(c), 1001(b)(7),(8) sfhc)
at the time of inspection, the bathroom exhaust fan was inoperable. repair or replace the exhaust fan and maintain the mechanical ventilation system in good order and repair.
OpenSep 22, 2026
building section · damaged bathroom door / door off hinges (103, 1001(b)(13) sfhc
at the time of inspection, the bathroom door was observed detached from its hinges and in damaged condition. repair or replace the bathroom door and all damaged or defective hinges, hardware, and associated components as necessary. properly reinstall the door and maintain it securely attached and in good working condition.
OpenSep 22, 2026
building section · inspector comments
it is the property owner's responsibility to be present or direct his/her representative to attend, the reinspection as scheduled on this notice of violation for the purpose of providing entry to the inspector to all areas cited within this notice. it is the responsibility of the property owner to provide tenants with notification, as required by california civil code section 1954 (san francisco housing code section 303(b)), if any dwellings, apartment units or guest rooms are to be accessed during reinspection(s). repairs cited in this notice may require building, plumbing, and/or electrical permits. the owner is responsible for obtaining all required permits before starting any work that requires permits. this case cannot be abated until all violations are corrected and required permits are finalized. at reinspection, present job card(s), plans, and permit(s) showing completed work. call the appropriate inspectors for required inspections before housing reinspection.
not activeDec 8, 2023
Ventilation & light
Corridor lighting repairs not being completed. Code/Section: S.F.E.C 89.116, 89.120 Monthly monitoring fee applies. Code/Section: SFBC 110A, Table 1A-K
not activeNov 17, 2023
building section · this notice includes violations for the areas noted.
subject property located at 242 turk st. common areas.
not activeNov 17, 2023
other section · inspector comments
it is the property owner's responsibility to be present or direct his/her representative to attend the re-inspection as scheduled on this notice of violation for the purpose of providing entry to the inspector of those areas not accessed during the initial inspection as specified, and/or to access to all areas cited within this notice. if the property owner cannot attend the scheduled re-inspection (as specified on this notice) it is his/her responsibility to secure a different inspection date and time with the inspector, and provide all tenants with notification as required by california civil code section 1954 (san francisco housing code section 303(b), if any dwellings, apartment units or guest rooms are to be accessed during the re-inspection.
not activeNov 17, 2023
security requirements section · lighting (504(g), 1001(b)(10) hc)
repair/ replace light fixture above door so it is properly illuminated. location: 8th fl. (above units #818, #820 & #821) ----------
not activeJul 5, 2022
building section · this notice includes violations for the areas noted.
subject property located at 242 turk st. common areas.
not activeJul 5, 2022
fire section · service central alarm system (908, 909 hc)
at time of inspection, central fire alarm system indicating "trouble"; have central alarm system serviced and tagged by a licensed professional. ----------
not activeJul 5, 2022
other section · inspector comments
it is the property owner's responsibility to be present or direct his/her representative to attend the re-inspection as scheduled on this notice of violation for the purpose of providing entry to the inspector of those areas not accessed during the initial inspection as specified, and/or to access to all areas cited within this notice. if the property owner cannot attend the scheduled re-inspection (as specified on this notice) it is his/her responsibility to secure a different inspection date and time with the inspector, and provide all tenants with notification as required by california civil code section 1954 (san francisco housing code section 303(b), if any dwellings, apartment units or guest rooms are to be accessed during the re-inspection.
not activeMar 21, 2022
building section · this notice includes violations for the areas noted.
subject property located at 242 turk st. common areas.
not activeMar 21, 2022
other section · inspector comments
it is the property owner's responsibility to be present or direct his/her representative to attend the re-inspection as scheduled on this notice of violation for the purpose of providing entry to the inspector of those areas not accessed during the initial inspection as specified, and/or to access to all areas cited within this notice. if the property owner cannot attend the scheduled re-inspection (as specified on this notice) it is his/her responsibility to secure a different inspection date and time with the inspector, and provide all tenants with notification as required by california civil code section 1954 (san francisco housing code section 303(b), if any dwellings, apartment units or guest rooms are to be accessed during the re-inspection.
not activeMar 21, 2022
building section · replace broken glass window pane (1001(h),708 hc)
replace shattered/ broken glass for exterior front door entry. location: exterior front door ----------
not activeApr 15, 2020
Heating equipment
No permit to operate the boiler. serial no C07187103, CMC 1022. Monthly monitoring fee applies. Code Sec: SFBC 110A, Table 1A-K
not activeJan 2, 2020
Heating equipment
No permit to operate the boiler. serial no C07187104, CMC 1022. Monthly monitoring fee applies. Code Sec: SFBC 110A, Table 1A-K
not activeJan 2, 2020
Heating equipment
No permit to operate the boiler. serial no C07187400, CMC 1022. Monthly monitoring fee applies. Code Sec: SFBC 110A, Table 1A-K
not activeJan 2, 2020
Heating equipment
No permit to operate the boiler. serial no C07187236, CMC 1022. Monthly monitoring fee applies. Code Sec: SFBC 110A, Table 1A-K
not activeApr 26, 2019
building section · this notice includes violations for the areas noted.
this notice of violation describes violations found at the common areas of the subject property at 242 turk street.
not activeApr 26, 2019
other section · provide for compliance affidavit (sfhc 604 )
complete the 604 affidavit provided for self-certification of structural maintenance. provide to inspector at the time of reinspection, send to inspector lawrie at 1660 mission st, san francisco, ca 94103, fax to (415) 558-6249, or email the forms to james.lawrie@sfgov.org .
not activeApr 26, 2019
other section · provide for compliance affidavit (sfbc 420.4, 907.2.11 and 3401.6.1 )
complete the affidavit provided for self certification of smoke detectors and carbon monoxide alarms. provide to inspector at the time of reinspection, send to inspector lawrie at 1660 mission st, san francisco, ca 94103, fax to (415) 558-6249, or email the forms to james.lawrie@sfgov.org .
not activeApr 26, 2019
other section · inspector comments
it is the property owner's responsibility to be present or direct his/her representative to attend the reinspection as scheduled on this notice of violation for the purpose of providing entry to the inspector of those areas not accessed during the initial inspection as specified, and/or to provide access to all areas cited within this notice. if the property owner cannot attend the scheduled reinspection (as specified on this notice) it is his/her responsibility to secure a different inspection time/date with the inspector, and provide all tenants with notification as required by california civil code section 1954 (san francisco housing code section 303(b)), if any dwellings, apartment units or guest rooms are to be accessed during the reinspection.
not activeFeb 20, 2018
Heating equipment
No permit to operate the boiler. serial no D13H00056736, CMC 1022
not activeFeb 20, 2018
Heating equipment
No permit to operate the boiler. serial no C07187104, CMC 1022
not activeJan 25, 2016
Heating equipment
No permit to operate the boiler, serial no D13H00056736, CMC 1022
not activeJan 25, 2016
Heating equipment
No permit to operate the boiler. serial no D13H00056736, CMC 1022
not activeApr 27, 2015
Heating equipment
No permit to operate the boiler. serial no C07187104, CMC 1022
not activeApr 27, 2015
Heating equipment
No current permit to operate the boiler. serial no C07187104, CMC 1022
not activeApr 27, 2015
Heating equipment
No permit to operate the boiler. serial no C07187236, CMC 1022
not activeApr 27, 2015
Heating equipment
No current permit to operate the boiler. serial no C07187236, CMC 1022
not activeApr 27, 2015
Heating equipment
No permit to operate the boiler. serial no C07187400, CMC 1022
not activeApr 27, 2015
Heating equipment
No current permit to operate the boiler. serial no C07187400, CMC 1022
not activeApr 27, 2015
Heating equipment
No current permit to operate the boiler. serial no C07187103, CMC 1022
not activeApr 27, 2015
Heating equipment
No permit to operate the boiler. serial no C07187103, CMC 1022
not activeApr 24, 2015
Heating equipment
No current permit to operate the boiler. serial no C07H00196031, CMC 1022 Monthly violation monitoring fee: $52