OpenNov 4, 2026
building section · this notice includes violations for the areas noted.
861 post street unit#206 and all common area
OpenNov 4, 2026
other section · provide apt. house or hotel water heated to min. 105 degrees f. (41 degrees c.) and max. of 120 degrees f. (49 degrees c.) at hot water taps. (505d(3))
at time of inspection, water from hot water tap in unit#206 was measured at lower than 105 degrees f. (41 degrees c.). make necessary repair to ensure hot water measured at min. of 105 degrees f. (41 degrees c.) and max. of 120 degrees f. (49 degrees c.) at hot water taps.
OpenNov 4, 2026
other section · inspector comments
it is the property owner's responsibility to be present or direct his/her representative to attend the re-inspection as scheduled on this notice of violation for the purpose of providing entry to the inspector of those areas not accessed during the initial inspection as specified, and/or to provide access to all areas cited within this notice. if the property owner cannot attend the scheduled reinspection (as specified on this notice) it is his/her responsibility to secure a different inspection date and time with the inspector. provide all tenants with notification as required by california civil code section 1954 (san francisco housing code section 303(b), if any dwellings, apartment units or guest rooms are to be accessed during the re-inspection. you can reach inspector lee @ 415-793-7947 or by email at joy.lee@sfgov.org.
OpenNov 2, 2026
Heating equipment
No permit to operate the boiler. serial no C13247912, CMC 1022. Monthly monitoring fee applies. Code Sec: SFBC 110A, Table 1A-K
OpenNov 2, 2026
Heating equipment
No permit to operate the boiler. serial no 709240-201409, CMC 1022. Monthly monitoring fee applies. Code Sec: SFBC 110A, Table 1A-K
OpenOct 29, 2026
building section · this notice includes violations for the areas noted.
891 post street unit#211 and all common area
OpenOct 29, 2026
building section · provide designated missing unit/apartment identification numbers to all units (706 hc)
at time of inspection, damage was observed on unit#211 identification numbers. repair or replace the unit identification numbers.
OpenOct 29, 2026
building section · general dilapidation or improper maintenance (1001 (b)(13))
at time of inspection, damage was observed on the entrance door frame of unit#211. repair or replace the door frame in an approved manner.
OpenOct 29, 2026
building section · repairs cited in this notice may require building, plumbing and / or electrical permits. it is the responsibility of the owner to obtain (or have others obtain) any required permits before beginning work that requires permit(s).this case can not be abated until the housing inspector makes a final inspection to verify that all violations have been corrected and all required permits have been obtained and finalized. on reinspection day, present to the housing inspector the job card, permit application and permits indicating that all required work under permit is complete. prior to reinspection by housing inspector, call building, electrical and/or plumbing inspector(s) for required inspection(s).
OpenOct 29, 2026
other section · inspector comments
it is the property owner's responsibility to be present or direct his/her representative to attend the re-inspection as scheduled on this notice of violation for the purpose of providing entry to the inspector of those areas not accessed during the initial inspection as specified, and/or to provide access to all areas cited within this notice. if the property owner cannot attend the scheduled reinspection (as specified on this notice) it is his/her responsibility to secure a different inspection date and time with the inspector. provide all tenants with notification as required by california civil code section 1954 (san francisco housing code section 303(b), if any dwellings, apartment units or guest rooms are to be accessed during the re-inspection. you can reach inspector lee @ 415-793-7947 or by email at joy.lee@sfgov.org.
OpenOct 22, 2026
building section · this notice includes violations for the areas noted.
891 post street unit#107 and all common area
OpenOct 22, 2026
interior surfaces section · repair damaged ceilings (1001b,h,o hc)
at time of inspection, leak damage/peeling paint was observed in the following areas: 1) unit#107 ceiling 2) first floor lobby ceiling 3) second floor hallway ceiling in front of the elevator. repair and repaint all damaged areas in an approved manner. at time of inspection, no active leak was observed. however, there were signs of possible leak in the past. locate and repair source of leak if necessary.
OpenOct 22, 2026
interior surfaces section · disturbing lead based paint can be extremely dangerous to dwelling occupants and visitors, particularly to young children, pregnant women, pets, and to people performing work on the premises. for interior or exterior paint removal : always wet the surface, contain and properly dispose of leaded paint. if you are unsure whether the paint is leaded, you should test it prior to performing any work. if the paint is found to contain lead, you should consult with an expert about appropriate procedures. proper containment and 3-day notification is required for exterior jobs of more than 10 sq.ft. (sec.3423, sfbc) informational packets are available at (415) 558-6088. you can contact the san francisco childhood lead poisoning prevention program at: (415) 252-3800 for free advice. if you cause lead dust to be created, you could be liable for any illness caused by the dust. ordinance #446-97.
OpenOct 22, 2026
interior surfaces section · repair floor covering (1001b,j,o hc)
at time of inspection, carpet on the stairway leading from first to second floor was not secured. repair or replace all loose carpet in an approved manner.
OpenOct 22, 2026
fire section · service central alarm system (908, 909 hc)
at time of inspection, trouble light was on on the fire alarm panel in the lobby. have licensed fire alarm company service / certify fire alarm system - required each year.
OpenOct 22, 2026
other section · repair defective or non-working elevator (1001(l), 713 hc)
at time of inspection, building elevator was out of service. restore non-working elevator to proper working condition and provide documentation showing that the state permit to operate is current.
OpenOct 22, 2026
other section · inspector comments
it is the property owner's responsibility to be present or direct his/her representative to attend the re-inspection as scheduled on this notice of violation for the purpose of providing entry to the inspector of those areas not accessed during the initial inspection as specified, and/or to provide access to all areas cited within this notice. if the property owner cannot attend the scheduled reinspection (as specified on this notice) it is his/her responsibility to secure a different inspection date and time with the inspector. provide all tenants with notification as required by california civil code section 1954 (san francisco housing code section 303(b), if any dwellings, apartment units or guest rooms are to be accessed during the re-inspection. you can reach inspector lee @ 415-793-7947 or by email at joy.lee@sfgov.org.
OpenAug 6, 2026
DBI code violation
Based on the department's vacant storefront renewal list, the property meets the definition of a Vacant or Abandoned Commercial Storefront (103A.5.1) and is not registered as required by 103A.5.2. Failure to register and maintain the storefront has resulted in blight and unsafe conditions under SFBC 102A and Chapter 80. Violations include: 1. Failure to Register Vacant Storefront - 103A.5.2 2. Failure to Pay Registration Fee - Table 1A-J 3. Failure to Submit Required Information / Contact Details 4. Failure to Maintain Storefront - 103A.4.5.1 / 103A.4.5.2 5. Failure to Secure Storefront - 103A.4.5.3 6. Failure to Post Required Signage - 103A.5.6 / 103A.4.4 7. Public Nuisance - 103A.5.7 & 102A MONTHLY MONITORING FEE Section 110A TABLE 1A-k
not activeMar 4, 2026
building section · this notice includes violations for the areas noted.
891 post street unit#410 and all common areas
not activeMar 4, 2026
interior surfaces section · repair damaged ceilings (1001b,h,o hc)
at time of inspection, peeling paint/damaged ceiling was observed in unit#410. repair and repaint the damaged areas in an approved manner.
not activeMar 4, 2026
other section · inspector comments
it is the property owner's responsibility to be present or direct his/her representative to attend the re-inspection as scheduled on this notice of violation for the purpose of providing entry to the inspector of those areas not accessed during the initial inspection as specified, and/or to provide access to all areas cited within this notice. if the property owner cannot attend the scheduled reinspection (as specified on this notice) it is his/her responsibility to secure a different inspection date and time with the inspector. provide all tenants with notification as required by california civil code section 1954 (san francisco housing code section 303(b), if any dwellings, apartment units or guest rooms are to be accessed during the re-inspection. you can reach inspector lee @ 415-793-7947 or by email at joy.lee@sfgov.org.
not activeMay 23, 2025
DBI code violation
FAILURE TO COMPLY WITH THE VACANT OR ABANDONED COMMERCIAL STOREFRONT ORDINANCE 52-19 and S.F.B.C 103A.5, MONTHLY MONITORING FEE Section 110A Table 1A-K
not activeDec 30, 2024
DBI code violation
FAILURE TO COMPLY WITH THE VACANT OR ABANDONED COMMERCIAL STOREFRONT ORDINANCE 52-19 and S.F.B.C 103A.5, MONTHLY MONITORING FEE Section 110A Table 1A-K
not activeJul 1, 2024
Heating equipment
No permit to operate the boiler. serial no 709240-201409, CMC 1022. Monthly monitoring fee applies. Code Sec: SFBC 110A, Table 1A-K
not activeJul 1, 2024
Heating equipment
No permit to operate the boiler. serial no C13247912, CMC 1022. Monthly monitoring fee applies. Code Sec: SFBC 110A, Table 1A-K
not activeFeb 6, 2023
DBI code violation
FAILURE TO COMPLY WITH THE VACANT OR ABANDONED COMMERCIAL STOREFRONT ORDINANCE 52-19 and 103A.5 MONTHLY MONITORING FEE Section 110A Table 1A-K
not activeAug 27, 2018
DBI code violation
Amendment to 1st NOV: Site visit complaint #201888451 revealed demolition of entire interior of ground floor unit (pictures attached) removed all interior of B unit, removed rated assembly at demising walls and ceilings at occupancy separation, unsafe gas lines and electric, see filed PA 201808177671. Code/Section: SFBC 102, 103A Monthly monitoring fee to apply. Code/Section: SFBC 102A.3 Table 1A-K, 3405 B.6.1
not activeAug 27, 2018
DBI code violation
Site visit for complaint #201888451 revealed demo of entire ground floor unit (picture attached). Removed all interior unsafe gas lines. Demo @ lower portion of unit. See filed permit #201808177671.
not activeOct 14, 2015
building section · this notice includes violations for the areas noted.
this notice includes violations of the san francisco housing code. unless noted otherwise, all violations were observed on the date of inspection at 891 post street, in the common areas.
not activeOct 14, 2015
building section · provide elevator service, nuisance 401.2, 713, 1001d, 1002b sfhc
at the time of inspection the elevator was not in service. repair/restore/replace the elevator as necessary within the specified time frame listed below.
not activeOct 14, 2015
other section · inspector comments
it is the property owner's responsibility to be present or direct his/her representative to attend the re-inspection as scheduled on this notice of violation for the purpose of providing entry to the inspector of those areas not accessed during the initial inspection as specified, and/or to provide access to all areas cited within this notice. if the property owner cannot attend the scheduled re-inspection (as specified on this notice) it is his/her responsibility to secure a different inspection date and time with the inspector, and provide all tenants with notification as required by california civil code section 1954 (san francisco housing code section 303(b), if any dwellings, apartment units or guest rooms are to be accessed during the re-inspection.
not activeMar 31, 2015
Heating equipment
No current permit to operate the boiler. serial no 780J D87 70415, CMC 1022 Monthly violation monitoring fee: $52
not activeMar 31, 2015
Heating equipment
No current permit to operate the boiler, serial no 780J D87 70415, CMC 1022
not activeOct 20, 2014
building section · this notice includes violations for the areas noted.
this notice includes violations of the san francisco housing code. unless noted otherwise, all violations were observed on the date of inspection at 891 post street, in the common areas.
not activeOct 20, 2014
building section · provide elevator service, nuisance 401(2), 713, 1001(d), 1002(b) sfhc
at the time of inspection the elevator was not in service. repair/restore/replace the elevator as necessary within the specified time frame listed below.
not activeOct 20, 2014
other section · inspector comments
it is the property owner's responsibility to be present or direct his/her representative to attend the re-inspection as scheduled on this notice of violation for the purpose of providing entry to the inspector of those areas not accessed during the initial inspection as specified, and/or to provide access to all areas cited within this notice. if the property owner cannot attend the scheduled re-inspection (as specified on this notice) it is his/her responsibility to secure a different inspection date and time with the inspector, and provide all tenants with notification as required by california civil code section 1954 (san francisco housing code section 303(b), if any dwellings, apartment units or guest rooms are to be accessed during the re-inspection.
not activeOct 17, 2014
DBI code violation
1.) A building you owned on September 15, 2013 was noticed as part of the mandatory Soft Story Retrofit Program. This completed form must be submitted to the Department of Building Inspection By September 15, 2014. You have not returned the form. This building is in violation of the requirements of the San Francisco Building Code regarding earthquake safety. The owner of this building has not complied with the mandatory Soft Story Retrofit Program as required by S.F.B.C. Chapter 34B (SFBC 3405B.6.1). 2.) Monthly Violation Monitoring Fee (SFBC 102A.2.4, Table 1A-K). 3.) Do not remove the posted "Earthquake Warning" Placard.
not activeAug 8, 2012
DBI code violation
Store front window has been damage by car accident approx area 8'X8' ((SF Coin Laundry Co.)
not activeAug 8, 2012
DBI code violation
You have failed to comply with Notice of Violation dated 8/8/12 therefore this department has intiated abatement proceedings against the property.
not activeSep 15, 2008
building section · this notice includes violations for the areas noted.
891 post street apartment# 214.
not activeSep 15, 2008
interior surfaces section · repair damaged walls (1001b,h,o hc)
around bathtub in apartment# 214.
not activeSep 15, 2008
interior surfaces section · repair source of water damage (703,1001f hc)
from ceiling in bathroom in apartment# 214.
not activeSep 15, 2008
interior surfaces section · repair damaged ceilings (1001b,h,o hc)
in bathroom in apartment# 214.
not activeSep 15, 2008
interior surfaces section · repair damaged walls (1001b,h,o hc)
in closet in apartment# 214.
not activeSep 15, 2008
interior surfaces section · paint ceilings and walls (1001b,1301 hc)
in bathroom,hallway, closet, livingroom and kitchen.
not activeSep 15, 2008
interior surfaces section · comments regarding possible lead based paint "disturbing lead based paint can be extremely dangerous to dwelling occupants and visitors, particularly to young children, pregnant women, pets, and to people performing work on the premises. for interior or exterior paint removal : always wet the surface, contain and properly dispose of leaded paint. if you are unsure whether the paint is leaded, you should test it prior to performing any work. if the paint is found to contain lead, you should consult with an expert about appropriate procedures. proper containment and 3-day notification is required for exterior jobs of more than 10 square feet. (sec.3604, sfbc) informational packets are available at (415) 558-6088. you can contact the san francisco childhood lead poisoning prevention program at: (415) 554-8930 for free advice. if you cause lead dust to be created, you could be liable for any illness caused by the dust. ordinance #446-97."
not activeSep 15, 2008
interior surfaces section · repair floor covering (1001b,j,o hc)
in bathroom and kitchen in apartment# 214.
not activeSep 15, 2008
other section · inspector comments
i have scheduled a reinspection of your building on monday, 20-october-2008 at 2:00 pm. reinspection of premise to include all areas referenced above. it is the property owner¿s responsibility to be present or direct his/her representative to attend, the reinspection as scheduled on this notice of violation for the purpose of providing entry to the inspector of those areas cited within this notice. if the property owner cannot attend the scheduled reinspection (as specified on this notice) it is his/her responsibility to secure a different inspection date and time with the inspector. on scheduled reinspection day, provide the inspector with a full access to all common and public areas per attached checklist. your cooperation is appreciated.
not activeJan 12, 2005
building section · this notice includes violations for the areas noted.
891 post street #311 and common areas.
not activeJan 12, 2005
other section · provide heat to each occupied habitable room for 13 hrs between 5:00 a.m. and 11:00 a.m. and between 3:00 p.m. and 10:00 p.m. capable to maintaining a min. room temp. of 68 degrees f. (20 degrees c.). (701c hc)
including #311. please open boiler room for inspection at time of reinspection.