952 SUTTER ST

Nob Hill · San Francisco, CA · Parcel 0280011 · Last violation Nov 26, 2025 · Last complaint Sep 30, 2026

NeighborhoodNob Hill
Above-average violations for the neighborhood
More violations than 72% of buildings and more complaints than 82% of buildings in Nob Hill. Size-normalized against residential buildings in the neighborhood.
ViolationsComplaints
Activity TrendsLast 5 years
A steady level of activity over time
Last 2 yrs: 5 violations · 11 complaints
'23'26ViolationsComplaints
Severityⓘopen violations
5 open DBI violations
Active Notices of Violation issued by the Department of Building Inspection.
Severe0
Serious4
Minor1

What to watch forⓘ

  1. Fire safety problems have been reported here.
    Worth checkingⓘ
    Walk the exit route from the unit to the street and check the stairs and hallways are clear of stored items, and that fire doors close properly.
    details ▸

    California law requires safe fire or emergency exits leading to a street or hallway, and requires stairs, hallways and exits to be kept litter free. Storage areas, garages and basements must be kept free of combustible materials. San Francisco's Housing Code separately treats inadequate exits and inadequate fire protection equipment as conditions that make a building substandard, which is the finding behind a notice of violation.

    • California Tenant Guide
    • San Francisco Housing Code §1001(m), (n)
  2. Tenants here have reported no heat or no hot water.
    details ▸

    California law requires heating facilities in good working order, and plumbing facilities in good working order including hot and cold running water. A rental unit that substantially lacks either may be legally uninhabitable, which is the standard the implied warranty of habitability sets for every residential tenancy in the state.

311 Housing Complaints
Total complaints since 2010
18
1 per year avg.↑ Up 450% in the last 2 years (11 vs 2 prior 2 yrs)
Complaint severity
Last 5 years
13
Severeⓘ6
Seriousⓘ3
Minorⓘ4
Dept. of Building Inspection Violations
Total violations since 1999
43
2 per year avg.↑ Up 25% in the last 2 years (5 vs 4 prior 2 yrs)
Open violations
5
Severeⓘ0
Seriousⓘ4
Minorⓘ1

Top violation categories

5 yrsAll time
General disrepairⓘ1 violations
Heat / hot waterⓘ1 violations
Heating equipmentⓘ1 violations
Pestsⓘ1 violations
Cleanliness & refuseⓘ1 violations
No specific condition stated4 violations
2 still open. See violation log below.

Top complaint types

5 yrsAll time
Fire Alarm System2 complaints
Heat Lack Of Heat2 complaints
Elevators No Working Elevator 7 Or More Stories2 complaints
Inadequately Maintained Building Exterior1 complaints
Infestation Rodent Insect1 complaints
Paint Peeling1 complaints
Elevators Everthing Else1 complaints
Plumbing Broken Leaking1 complaints
Garbage Receptacles1 complaints
General Maintenance Not In List Above1 complaints
Hide violations (43) ↑See complaints (18) →

Violation log

43 DBI violations

AllOpenClosed
StatusFiledCategoryItemNOV Item Description
OpenNov 26, 2025building sectionthis notice includes violations for the areas noted.952 sutter street and all common area
See something wrong? File a complaint with SF 311

Ask how heat and hot water are supplied and who pays for them. If either fails once you live here, put the request to the landlord in writing and keep a copy.

  • California Tenant Guide
  • San Francisco Housing Code §701
  • Tenants here have reported pests.
    Worth checkingⓘ
    Look along baseboards and inside low cabinets for droppings, greasy rub marks or tracks, and check whether the bins outside overflow and whether gaps around exterior doors are sealed.
    details ▸

    California law requires buildings and grounds to be kept clean and sanitary and free from debris, filth, rubbish, garbage, rodents and vermin. San Francisco requires property owners to keep their property free of vermin, and requires an owner or manager to respond to a tenant's bed bug complaint by hiring a licensed pest control operator.

    • California Tenant Guide
    • SF.gov, Keeping your building free of vermin
  • OpenNov 26, 2025sanitation sectioneliminate rodent infestation (1001b, 1306 hc)evidence of rodents exist in this building. have licensed pest control contractor treat building in approved manner to eliminate rodents. provide written documentation of treatment from pest control company at time of reinspection.
    OpenNov 26, 2025sanitation sectionremove rubbish or trash at garbage area (1304,1306,1001b hc)at time of inspection, overflowing trash was observed in the garbage area. remove all overflowing trash.
    OpenNov 26, 2025plumbing and electrical sectiongeneral dilapidation or improper maintenance (1001 (b)(13))at time of inspection, washing and drying machines in building basement laundry room did not work. repair or replace washing and drying machines in an approved manner.
    OpenNov 26, 2025other sectioninspector commentsit is the property owner's responsibility to be present or direct his/her representative to attend the re-inspection as scheduled on this notice of violation for the purpose of providing entry to the inspector of those areas not accessed during the initial inspection as specified, and/or to provide access to all areas cited within this notice. if the property owner cannot attend the scheduled reinspection (as specified on this notice) it is his/her responsibility to secure a different inspection date and time with the inspector. provide all tenants with notification as required by california civil code section 1954 (san francisco housing code section 303(b), if any dwellings, apartment units or guest rooms are to be accessed during the re-inspection. you can reach inspector lee @ 415-793-7947 or by email at joy.lee@sfgov.org.
    not activeDec 7, 2023building sectionthis notice includes violations for the areas noted.925 sutter street unit#9
    not activeDec 7, 2023other sectionprovide heat to each occupied habitable room capable of maintaining a min. room temp. of 70 degrees f. (21 degrees c.). (701(a) hc)at the time of inspection heating wall unit did not work. repair or replace heating unit to provide adequate heat to habitable rooms in unit. work for this must begin within 3 working days of receiving this notice. if new heating source is installed, please attain all necessary permits, including plumbing, mechanical, electric and building permits. all permits must be finalized prior to housing inspector reinspection, in order to abate this item.
    not activeDec 7, 2023other sectioninspector commentsit is the property owner's responsibility to be present or direct his/her representative to attend the re-inspection as scheduled on this notice of violation for the purpose of providing entry to the inspector of those areas not accessed during the initial inspection as specified, and/or to provide access to all areas cited within this notice. if the property owner cannot attend the scheduled reinspection (as specified on this notice) it is his/her responsibility to secure a different inspection date and time with the inspector. provide all tenants with notification as required by california civil code section 1954 (san francisco housing code section 303(b), if any dwellings, apartment units or guest rooms are to be accessed during the re-inspection. you can reach inspector lee @ 415-793-7947 or by email at joy.lee@sfgov.org.
    not activeSep 1, 2023Heating equipment—No permit to operate the boiler. serial no C18290019, CMC 1022. Monthly monitoring fee applies. Code Sec: SFBC 110A, Table 1A-K
    not activeNov 28, 2018building sectionthis notice includes violations for the areas noted.this notice includes violations of the san francisco housing code. unless noted otherwise, all violations were observed on the date of inspection at 952 sutter street. this was a complaint generated routine inspection initiated by complaint number 201807991.
    not activeNov 28, 2018building sectionprovide a caretaker 1311, 1001d sfhcthe directory does not display a resident in responsible charge. the san francisco housing code requires that any apartment house with 16 or more units requires a live in janitor, housekeeper, owner or manager. provide a resident manager or person in responsible charge. this person shall be clearly identified with contact information on the entry system directory.
    not activeNov 28, 2018other sectioninspector commentsimportant note: due to the nature of this violation, this property has been defined as a nuisance per section 1001-d of the san francisco housing code. it is the property owner's responsibility to be present or direct his/her representative to attend the re-inspection as scheduled on this notice of violation for the purpose of providing entry to the inspector of those areas not accessed during the initial inspection as specified, and/or to provide access to all areas cited within this notice. if the property owner cannot attend the scheduled re-inspection (as specified on this notice) it is his/her responsibility to secure a different inspection date and time with the inspector, and provide all tenants with notification as required by california civil code section 1954 (san francisco housing code section 303(b), if any dwellings, apartment units or guest rooms are to be accessed during the re-inspection.
    not activeApr 17, 2017building sectionthis notice includes violations for the areas noted.this notice includes violations of the san francisco housing code. unless noted otherwise, all violations were observed on the date of inspection at 952 sutter street. this was a complaint generated routine inspection initiated by complaint number 201771281.
    not activeApr 17, 2017building sectionprovide 604 affidavit for all exterior appendages 604, 908 sfhcyour property has been researched and is not listed on the department of building inspection's 604 compliance log. provide a signed and completed 604 affidavit from a licensed professional to certify the functionality of your fire escapes and all other exterior appendages. provide completed form at inspection or return by mail to: department of building inspection housing division, c. grady 1660 mission street, 6th floor san francisco, ca 94103
    not activeApr 17, 2017building sectionprovide carbon monoxide detectors 420 cbc provide smoke detectors 908, 911 sfhc, 907.2.11 sfbcprovide carbon monoxide detectors laid out per the san francisco building code section 420. there shall be one unit in each guest room within the immediate floor and each adjacent floor, above and below a gas burning appliance to include stoves, dryers, furnaces, water heaters and boilers. most of the smoke detectors in the common areas are chirping. replace the batteries or the smoke detectoring units as required by the san francisco building code to stop the chirping and demonstrate that the units are working properly. a self-certification form has been included for your convenience. provide completed form at inspection or return by mail to: department of building inspection housing division, c. grady 1660 mission street, 6th floor san francisco, ca 94103
    not activeApr 17, 2017building sectionreplace broken glass window pane (1001(h),708 hc)the window in the door at the back stairs on the first floor is broken. replace the pane of glass.
    not activeApr 17, 2017building sectionprovide junction box cover 1001e sfhc, 314.25 necthere is a wiremold box at the rear stairs on the first floor hanging from the conductors of the light switch at this location. the conductors are exposed and connections are open to the user. openings must be effectively closed and provide protection substantially equivalent to the wall of the equipment unless covered by a fixture canopy or lamp holder. repair the connection to prevent accidental contact with the live conductors.
    not activeApr 17, 2017plumbing and electrical sectionroot the clogged area drain 1001f sfhc, 1101.1 upcthere is standing water in the east side courtyard/lightwell. the area drain in this court is clogged. provide the services of a rooting company to clear the standing water.
    not activeApr 17, 2017plumbing and electrical sectionprovide roof drainage 1001f sfhc, 1101.11.2.1 upcthe roof scupper on the center of the west wall is clogged creating standing water on the roof. clear the roof scuppers of trash and debris and insure proper drainage.
    not activeApr 17, 2017other sectioninspector commentsimportant note: due to the nature of this violation, this property has been defined as a nuisance per section 1001-d of the san francisco housing code. it is the property owner's responsibility to be present or direct his/her representative to attend the re-inspection as scheduled on this notice of violation for the purpose of providing entry to the inspector of those areas not accessed during the initial inspection as specified, and/or to provide access to all areas cited within this notice. if the property owner cannot attend the scheduled re-inspection (as specified on this notice) it is his/her responsibility to secure a different inspection date and time with the inspector, and provide all tenants with notification as required by california civil code section 1954 (san francisco housing code section 303(b), if any dwellings, apartment units or guest rooms are to be accessed during the re-inspection.
    not activeApr 17, 2017fire sectionreplace smoke enclosure door closer (807,707 hc)the self closing mechanism on the roof access door is broken. replace the self closing mechanism to provide automatic closure of the smoke enclosure door.
    not activeApr 3, 2017building sectionthis notice includes violations for the areas noted.this notice includes violations of the san francisco housing code. unless noted otherwise, all violations were observed on the date of inspection at 952 sutter street.
    not activeApr 3, 2017building sectionstop all work immediately, 1001d, k sfhcyou are in violation of san francisco's lead abatement regulations. the san francisco building code section 3426 governs the requirements of work that disturbs or removes lead-based paint. you are hereby warned in this notice of violation referenced with complaint number 201771281 to adhere to these standards. violations were observed and cited outside of your building. clean up, containment barrier systems and measures implemented to restrict access to work areas must be approved by the housing inspector before work resumes.
    not activeApr 3, 2017building sectionviolation of work practices 1001d, k sfhc , 3426.3 sfbcthe common areas of this building are under construction generating work debris. this structure is a pre-1979 structure and so this debris is presumed to contain lead. to continue work as currently conducted, provide certification from a qualified lead testing laboratory to show the debris has no lead base. without this clearance report you shall comply with the balance of this notice of violation.
    not activeApr 3, 2017building sectionprovide notification 1001d, k sfhc , 3426.5.6 sfbcyou are required to give 3 business days' notification to the occupants of this and the immediately adjacent buildings subject to the work debris and dust. review section 3426.5.1 of the san francisco building code for the specific requirements of notification.
    not activeApr 3, 2017building sectionprovide signage 1001d, k sfhc , 3426.5.4 sfbcat the time of inspection there were no lead hazard signs posted: post the required signage.
    not activeApr 3, 2017building sectionrestrict access 1001d, k sfhc , 3426.4.1 sfbcestablish a regulated work area that restricts access to only those qualified to handle or disturb lead paint. containment must be established in a way that allows safe passage in and out of the building for building occupants without exposing them to lead based paint chips, debris and dust.
    not activeApr 3, 2017building sectionprovide containment and barrier systems 1001d, k sfhc , 3426.4.2 sfbcthe containment system in place at the time of inspection was inadequate to contain all paint chips, debris and dust. the neighboring building to the east is experiencing contamination in their adjacent court from the open windows on the east side of your building. establish and maintain the required containment and barrier systems.
    not activeApr 3, 2017building sectionprotect the ground 1001d, k sfhc , 3426.4.2.1 sfbcany person performing exterior work shall protect the ground from contamination by work debris by laying 6 mil visquene on all horizontal surfaces extending 10 feet beyond the work area.
    not activeApr 3, 2017building sectionprevent migration 1001d, k sfhc , 3425.4.3 sfbconce containment barriers and ground protection are in place, establish a restricted work area using 6 mil visquene providing full containment to prevent the migration of work debris outside the work area. all windows, doors and vents within 10 feet of work area must be covered and sealed.
    not activeApr 3, 2017building sectionexterior clean up standards 1001d, k sfhc , 3425.4.4.2 sfbcat the completion of work each day, remove all visible work debris from the regulated area. initial clean up should be done with an epa certified hepa vacuum cleaner. do not sweep, this causes the particulate to become air borne. once all dry dust has been removed, a wet dusting should be conducted in all work areas until the wet rag is relatively clean. debris shall be double bagged and duct taped and disposed of in an approved manner. lead debris is a toxic hazard and must be disposed of as such.
    not activeApr 3, 2017other sectioninspector commentsnote: in addition to the regulation established by the city and county of san francisco, work that disturbs lead based paint is also regulated by the epa, the state of california health department, calosha, and the contractors state license board. please be advised to comply with all regulations governing the disturbance of lead based paint. work should be conducted following the regulatory requirements of epa rrp, cdph title 17 and dosh 1532.1. use only approved methods and lead abatement certified contractors for the balance of this work handling lead based paint, dust and debris. important note: due to the nature of this violation, this property has been defined as a nuisance per section 1001-d of the san francisco housing code. it is the property owner's responsibility to be present or direct his/her representative to attend the re-inspection as scheduled on this notice of violation for the purpose of providing entry to the inspector of those areas not accessed during the initial inspection as specified, and/or to provide access to all areas cited within this notice. if the property owner cannot attend the scheduled re-inspection (as specified on this notice) it is his/her responsibility to secure a different inspection date and time with the inspector, and provide all tenants with notification as required by california civil code section 1954 (san francisco housing code section 303(b), if any dwellings, apartment units or guest rooms are to be accessed during the re-inspection.
    not activeJun 1, 2016Heating equipment—No permit to operate the boiler. serial no 9405114932, CMC 1022
    not activeFeb 28, 2014building sectionthis notice includes violations for the areas noted.common area of subject property.
    not activeFeb 28, 2014building sectionprovide grab bars (505,j, hc)provide grab bars in common bathroom on ground floor level. common bathrooms, including water-closets, lavatory, and bathing facilities require grab bars. building permit is required for installation.
    not activeFeb 28, 2014building sectionbuilding permit required (301 hc)provide building permit for above installation.
    not activeFeb 28, 2014other sectioninspector commentsit is the property owner's responsibility to be present or direct his/her representative to attend, the reinspection as scheduled on this notice of violation for the purpose of providing entry to the inspector of those areas not accessed during the initial inspection as specified, and/or to provide access to all areas cited within this notice. if the property owner cannot attend the scheduled reinspection (as specified on this notice) it is his/her responsibility to secure a different inspection date and time with the inspector, and provide all tenants with notification as required by california civil code section 1954 (san francisco housing code section 303(b), if any dwellings, apartment units or guest rooms are to be accessed during the reinspection
    not activeJan 11, 2013Plumbing—A complaint has been filed with the Plumbing Inspection Division regarding the lack of cross connection control on the main water service.
    not activeOct 13, 2006building sectionrecharge expired, leaking fire extinguisher in the basement area.sec.905 h.c.leaking basement fire extinguisher in need to be recharged,pressure tested or replaced with an approved type. (2a 10bc or 5 lb abc.)
    not activeOct 13, 2006building sectionremove flamables from the boiler room.1001hc.remove furnishing,storage from boiler room constituting a potential fire hazard.1001hc.
    not activeOct 13, 2006building sectionreplace damaged screen over boiler room window.1001hc.damaged wire mash extending over the bottom portion of boiler room window is in need to be replaced.
    not activeOct 13, 2006building sectionprovide preventive pest and rodent control measures in the basement, laundry, storage room and boiler areas.1001hc.—
    not activeOct 21, 1999fire sectionprovide automatic fire sprinklers over garbage receptacles (904,906(4) hc)plumbing permit required.
    OpenNov 26, 2025
    building section · this notice includes violations for the areas noted.
    952 sutter street and all common area
    OpenNov 26, 2025
    sanitation section · eliminate rodent infestation (1001b, 1306 hc)
    evidence of rodents exist in this building. have licensed pest control contractor treat building in approved manner to eliminate rodents. provide written documentation of treatment from pest control company at time of reinspection.
    OpenNov 26, 2025
    sanitation section · remove rubbish or trash at garbage area (1304,1306,1001b hc)
    at time of inspection, overflowing trash was observed in the garbage area. remove all overflowing trash.
    OpenNov 26, 2025
    plumbing and electrical section · general dilapidation or improper maintenance (1001 (b)(13))
    at time of inspection, washing and drying machines in building basement laundry room did not work. repair or replace washing and drying machines in an approved manner.
    OpenNov 26, 2025
    other section · inspector comments
    it is the property owner's responsibility to be present or direct his/her representative to attend the re-inspection as scheduled on this notice of violation for the purpose of providing entry to the inspector of those areas not accessed during the initial inspection as specified, and/or to provide access to all areas cited within this notice. if the property owner cannot attend the scheduled reinspection (as specified on this notice) it is his/her responsibility to secure a different inspection date and time with the inspector. provide all tenants with notification as required by california civil code section 1954 (san francisco housing code section 303(b), if any dwellings, apartment units or guest rooms are to be accessed during the re-inspection. you can reach inspector lee @ 415-793-7947 or by email at joy.lee@sfgov.org.
    not activeDec 7, 2023
    building section · this notice includes violations for the areas noted.
    925 sutter street unit#9
    not activeDec 7, 2023
    other section · provide heat to each occupied habitable room capable of maintaining a min. room temp. of 70 degrees f. (21 degrees c.). (701(a) hc)
    at the time of inspection heating wall unit did not work. repair or replace heating unit to provide adequate heat to habitable rooms in unit. work for this must begin within 3 working days of receiving this notice. if new heating source is installed, please attain all necessary permits, including plumbing, mechanical, electric and building permits. all permits must be finalized prior to housing inspector reinspection, in order to abate this item.
    not activeDec 7, 2023
    other section · inspector comments
    it is the property owner's responsibility to be present or direct his/her representative to attend the re-inspection as scheduled on this notice of violation for the purpose of providing entry to the inspector of those areas not accessed during the initial inspection as specified, and/or to provide access to all areas cited within this notice. if the property owner cannot attend the scheduled reinspection (as specified on this notice) it is his/her responsibility to secure a different inspection date and time with the inspector. provide all tenants with notification as required by california civil code section 1954 (san francisco housing code section 303(b), if any dwellings, apartment units or guest rooms are to be accessed during the re-inspection. you can reach inspector lee @ 415-793-7947 or by email at joy.lee@sfgov.org.
    not activeSep 1, 2023
    Heating equipment
    No permit to operate the boiler. serial no C18290019, CMC 1022. Monthly monitoring fee applies. Code Sec: SFBC 110A, Table 1A-K
    not activeNov 28, 2018
    building section · this notice includes violations for the areas noted.
    this notice includes violations of the san francisco housing code. unless noted otherwise, all violations were observed on the date of inspection at 952 sutter street. this was a complaint generated routine inspection initiated by complaint number 201807991.
    not activeNov 28, 2018
    building section · provide a caretaker 1311, 1001d sfhc
    the directory does not display a resident in responsible charge. the san francisco housing code requires that any apartment house with 16 or more units requires a live in janitor, housekeeper, owner or manager. provide a resident manager or person in responsible charge. this person shall be clearly identified with contact information on the entry system directory.
    not activeNov 28, 2018
    other section · inspector comments
    important note: due to the nature of this violation, this property has been defined as a nuisance per section 1001-d of the san francisco housing code. it is the property owner's responsibility to be present or direct his/her representative to attend the re-inspection as scheduled on this notice of violation for the purpose of providing entry to the inspector of those areas not accessed during the initial inspection as specified, and/or to provide access to all areas cited within this notice. if the property owner cannot attend the scheduled re-inspection (as specified on this notice) it is his/her responsibility to secure a different inspection date and time with the inspector, and provide all tenants with notification as required by california civil code section 1954 (san francisco housing code section 303(b), if any dwellings, apartment units or guest rooms are to be accessed during the re-inspection.
    not activeApr 17, 2017
    building section · this notice includes violations for the areas noted.
    this notice includes violations of the san francisco housing code. unless noted otherwise, all violations were observed on the date of inspection at 952 sutter street. this was a complaint generated routine inspection initiated by complaint number 201771281.
    not activeApr 17, 2017
    building section · provide 604 affidavit for all exterior appendages 604, 908 sfhc
    your property has been researched and is not listed on the department of building inspection's 604 compliance log. provide a signed and completed 604 affidavit from a licensed professional to certify the functionality of your fire escapes and all other exterior appendages. provide completed form at inspection or return by mail to: department of building inspection housing division, c. grady 1660 mission street, 6th floor san francisco, ca 94103
    not activeApr 17, 2017
    building section · provide carbon monoxide detectors 420 cbc provide smoke detectors 908, 911 sfhc, 907.2.11 sfbc
    provide carbon monoxide detectors laid out per the san francisco building code section 420. there shall be one unit in each guest room within the immediate floor and each adjacent floor, above and below a gas burning appliance to include stoves, dryers, furnaces, water heaters and boilers. most of the smoke detectors in the common areas are chirping. replace the batteries or the smoke detectoring units as required by the san francisco building code to stop the chirping and demonstrate that the units are working properly. a self-certification form has been included for your convenience. provide completed form at inspection or return by mail to: department of building inspection housing division, c. grady 1660 mission street, 6th floor san francisco, ca 94103
    not activeApr 17, 2017
    building section · replace broken glass window pane (1001(h),708 hc)
    the window in the door at the back stairs on the first floor is broken. replace the pane of glass.
    not activeApr 17, 2017
    building section · provide junction box cover 1001e sfhc, 314.25 nec
    there is a wiremold box at the rear stairs on the first floor hanging from the conductors of the light switch at this location. the conductors are exposed and connections are open to the user. openings must be effectively closed and provide protection substantially equivalent to the wall of the equipment unless covered by a fixture canopy or lamp holder. repair the connection to prevent accidental contact with the live conductors.
    not activeApr 17, 2017
    plumbing and electrical section · root the clogged area drain 1001f sfhc, 1101.1 upc
    there is standing water in the east side courtyard/lightwell. the area drain in this court is clogged. provide the services of a rooting company to clear the standing water.
    not activeApr 17, 2017
    plumbing and electrical section · provide roof drainage 1001f sfhc, 1101.11.2.1 upc
    the roof scupper on the center of the west wall is clogged creating standing water on the roof. clear the roof scuppers of trash and debris and insure proper drainage.
    not activeApr 17, 2017
    other section · inspector comments
    important note: due to the nature of this violation, this property has been defined as a nuisance per section 1001-d of the san francisco housing code. it is the property owner's responsibility to be present or direct his/her representative to attend the re-inspection as scheduled on this notice of violation for the purpose of providing entry to the inspector of those areas not accessed during the initial inspection as specified, and/or to provide access to all areas cited within this notice. if the property owner cannot attend the scheduled re-inspection (as specified on this notice) it is his/her responsibility to secure a different inspection date and time with the inspector, and provide all tenants with notification as required by california civil code section 1954 (san francisco housing code section 303(b), if any dwellings, apartment units or guest rooms are to be accessed during the re-inspection.
    not activeApr 17, 2017
    fire section · replace smoke enclosure door closer (807,707 hc)
    the self closing mechanism on the roof access door is broken. replace the self closing mechanism to provide automatic closure of the smoke enclosure door.
    not activeApr 3, 2017
    building section · this notice includes violations for the areas noted.
    this notice includes violations of the san francisco housing code. unless noted otherwise, all violations were observed on the date of inspection at 952 sutter street.
    not activeApr 3, 2017
    building section · stop all work immediately, 1001d, k sfhc
    you are in violation of san francisco's lead abatement regulations. the san francisco building code section 3426 governs the requirements of work that disturbs or removes lead-based paint. you are hereby warned in this notice of violation referenced with complaint number 201771281 to adhere to these standards. violations were observed and cited outside of your building. clean up, containment barrier systems and measures implemented to restrict access to work areas must be approved by the housing inspector before work resumes.
    not activeApr 3, 2017
    building section · violation of work practices 1001d, k sfhc , 3426.3 sfbc
    the common areas of this building are under construction generating work debris. this structure is a pre-1979 structure and so this debris is presumed to contain lead. to continue work as currently conducted, provide certification from a qualified lead testing laboratory to show the debris has no lead base. without this clearance report you shall comply with the balance of this notice of violation.
    not activeApr 3, 2017
    building section · provide notification 1001d, k sfhc , 3426.5.6 sfbc
    you are required to give 3 business days' notification to the occupants of this and the immediately adjacent buildings subject to the work debris and dust. review section 3426.5.1 of the san francisco building code for the specific requirements of notification.
    not activeApr 3, 2017
    building section · provide signage 1001d, k sfhc , 3426.5.4 sfbc
    at the time of inspection there were no lead hazard signs posted: post the required signage.
    not activeApr 3, 2017
    building section · restrict access 1001d, k sfhc , 3426.4.1 sfbc
    establish a regulated work area that restricts access to only those qualified to handle or disturb lead paint. containment must be established in a way that allows safe passage in and out of the building for building occupants without exposing them to lead based paint chips, debris and dust.
    not activeApr 3, 2017
    building section · provide containment and barrier systems 1001d, k sfhc , 3426.4.2 sfbc
    the containment system in place at the time of inspection was inadequate to contain all paint chips, debris and dust. the neighboring building to the east is experiencing contamination in their adjacent court from the open windows on the east side of your building. establish and maintain the required containment and barrier systems.
    not activeApr 3, 2017
    building section · protect the ground 1001d, k sfhc , 3426.4.2.1 sfbc
    any person performing exterior work shall protect the ground from contamination by work debris by laying 6 mil visquene on all horizontal surfaces extending 10 feet beyond the work area.
    not activeApr 3, 2017
    building section · prevent migration 1001d, k sfhc , 3425.4.3 sfbc
    once containment barriers and ground protection are in place, establish a restricted work area using 6 mil visquene providing full containment to prevent the migration of work debris outside the work area. all windows, doors and vents within 10 feet of work area must be covered and sealed.
    not activeApr 3, 2017
    building section · exterior clean up standards 1001d, k sfhc , 3425.4.4.2 sfbc
    at the completion of work each day, remove all visible work debris from the regulated area. initial clean up should be done with an epa certified hepa vacuum cleaner. do not sweep, this causes the particulate to become air borne. once all dry dust has been removed, a wet dusting should be conducted in all work areas until the wet rag is relatively clean. debris shall be double bagged and duct taped and disposed of in an approved manner. lead debris is a toxic hazard and must be disposed of as such.
    not activeApr 3, 2017
    other section · inspector comments
    note: in addition to the regulation established by the city and county of san francisco, work that disturbs lead based paint is also regulated by the epa, the state of california health department, calosha, and the contractors state license board. please be advised to comply with all regulations governing the disturbance of lead based paint. work should be conducted following the regulatory requirements of epa rrp, cdph title 17 and dosh 1532.1. use only approved methods and lead abatement certified contractors for the balance of this work handling lead based paint, dust and debris. important note: due to the nature of this violation, this property has been defined as a nuisance per section 1001-d of the san francisco housing code. it is the property owner's responsibility to be present or direct his/her representative to attend the re-inspection as scheduled on this notice of violation for the purpose of providing entry to the inspector of those areas not accessed during the initial inspection as specified, and/or to provide access to all areas cited within this notice. if the property owner cannot attend the scheduled re-inspection (as specified on this notice) it is his/her responsibility to secure a different inspection date and time with the inspector, and provide all tenants with notification as required by california civil code section 1954 (san francisco housing code section 303(b), if any dwellings, apartment units or guest rooms are to be accessed during the re-inspection.
    not activeJun 1, 2016
    Heating equipment
    No permit to operate the boiler. serial no 9405114932, CMC 1022
    not activeFeb 28, 2014
    building section · this notice includes violations for the areas noted.
    common area of subject property.
    not activeFeb 28, 2014
    building section · provide grab bars (505,j, hc)
    provide grab bars in common bathroom on ground floor level. common bathrooms, including water-closets, lavatory, and bathing facilities require grab bars. building permit is required for installation.
    not activeFeb 28, 2014
    building section · building permit required (301 hc)
    provide building permit for above installation.
    not activeFeb 28, 2014
    other section · inspector comments
    it is the property owner's responsibility to be present or direct his/her representative to attend, the reinspection as scheduled on this notice of violation for the purpose of providing entry to the inspector of those areas not accessed during the initial inspection as specified, and/or to provide access to all areas cited within this notice. if the property owner cannot attend the scheduled reinspection (as specified on this notice) it is his/her responsibility to secure a different inspection date and time with the inspector, and provide all tenants with notification as required by california civil code section 1954 (san francisco housing code section 303(b), if any dwellings, apartment units or guest rooms are to be accessed during the reinspection
    not activeJan 11, 2013
    Plumbing
    A complaint has been filed with the Plumbing Inspection Division regarding the lack of cross connection control on the main water service.
    not activeOct 13, 2006
    building section · recharge expired, leaking fire extinguisher in the basement area.sec.905 h.c.
    leaking basement fire extinguisher in need to be recharged,pressure tested or replaced with an approved type. (2a 10bc or 5 lb abc.)
    not activeOct 13, 2006
    building section · remove flamables from the boiler room.1001hc.
    remove furnishing,storage from boiler room constituting a potential fire hazard.1001hc.
    not activeOct 13, 2006
    building section · replace damaged screen over boiler room window.1001hc.
    damaged wire mash extending over the bottom portion of boiler room window is in need to be replaced.
    not activeOct 13, 2006
    building section · provide preventive pest and rodent control measures in the basement, laundry, storage room and boiler areas.1001hc.
    not activeOct 21, 1999
    fire section · provide automatic fire sprinklers over garbage receptacles (904,906(4) hc)
    plumbing permit required.