not activeApr 1, 2026
Heating equipment
No permit to operate the boiler. serial no GY402343449, CMC 1022. Monthly monitoring fee applies. Code Sec: SFBC 110A, Table 1A-K
not activeNov 25, 2025
building section · this notice includes violations for the areas noted.
440 davis court unit#403 and all common area
not activeNov 25, 2025
plumbing and electrical section · make necessary repairs to tub/shower/sink (1001 hc)
at time of inspection, slowly/clogged drainage sinks/bathtub were observed in unit#403 bathroom and kitchen. make necessary repair to sinks/bathtub drain.
not activeNov 25, 2025
plumbing and electrical section · general dilapidation or improper maintenance (1001 (b)(13))
at time of inspection, leak was observed around unit#403 dishwasher area. locate and repair the source of leak.
not activeNov 25, 2025
other section · inspector comments
it is the property owner's responsibility to be present or direct his/her representative to attend the re-inspection as scheduled on this notice of violation for the purpose of providing entry to the inspector of those areas not accessed during the initial inspection as specified, and/or to provide access to all areas cited within this notice. if the property owner cannot attend the scheduled reinspection (as specified on this notice) it is his/her responsibility to secure a different inspection date and time with the inspector. provide all tenants with notification as required by california civil code section 1954 (san francisco housing code section 303(b), if any dwellings, apartment units or guest rooms are to be accessed during the re-inspection. you can reach inspector lee @ 415-793-7947 or by email at joy.lee@sfgov.org.
not activeNov 3, 2025
Heating equipment
No permit to operate the boiler. serial no GY36-12-36515, CMC 1022. Monthly monitoring fee applies. Code Sec: SFBC 110A, Table 1A-K
not activeOct 16, 2025
Heating equipment
No permit to operate the boiler. serial no FY23-23-43271, CMC 1022. Monthly monitoring fee applies. Code Sec: SFBC 110A, Table 1A-K
not activeOct 16, 2025
Heating equipment
No permit to operate the boiler. serial no FY23-23-43263, CMC 1022. Monthly monitoring fee applies. Code Sec: SFBC 110A, Table 1A-K
not activeOct 16, 2025
Heating equipment
No permit to operate the boiler. serial no FY01-23-43012, CMC 1022. Monthly monitoring fee applies. Code Sec: SFBC 110A, Table 1A-K
not activeOct 16, 2025
Heating equipment
No permit to operate the boiler. serial no FY01-23-43013, CMC 1022. Monthly monitoring fee applies. Code Sec: SFBC 110A, Table 1A-K
not activeApr 22, 2025
building section · this notice includes violations for the areas noted.
subject property located at 440 davis ct. unit #403.
not activeApr 22, 2025
other section · inspector comments
it is the property owner's responsibility to be present or direct his/her representative to attend the re-inspection as scheduled on this notice of violation for the purpose of providing entry to the inspector of those areas not accessed during the initial inspection as specified, and/or to access to all areas cited within this notice. if the property owner cannot attend the scheduled re-inspection (as specified on this notice) it is his/her responsibility to secure a different inspection date and time with the inspector, and provide all tenants with notification as required by california civil code section 1954 (san francisco housing code section 303(b), if any dwellings, apartment units or guest rooms are to be accessed during the re-inspection. ***correction of violations cited in this notice may require building, plumbing and/or electrical permits. it is the responsibility of the owner to obtain (or have others obtain) any required permits before beginning work that requires permit(s). when applying for a permit, reference the complaint number from this notice of violation. you must have the proper permit signed-off and finalized before the housing insp. returns in order for this violation to be abated.***
not activeApr 22, 2025
plumbing and electrical section · make necessary repairs to tub/ shower (1001 hc)
unclog drain so tub/ shower could drain properly; at time of inspection, standing water observed in bathtub. location: bathroom ----------
not activeFeb 3, 2025
Heating equipment
No permit to operate the boiler. serial no GY402343449, CMC 1022. Monthly monitoring fee applies. Code Sec: SFBC 110A, Table 1A-K
not activeJul 15, 2024
Heating equipment
No permit to operate the boiler. serial no FY01-23-43012, CMC 1022. Monthly monitoring fee applies. Code Sec: SFBC 110A, Table 1A-K
not activeJul 15, 2024
Heating equipment
No permit to operate the boiler. serial no FY01-23-43013, CMC 1022. Monthly monitoring fee applies. Code Sec: SFBC 110A, Table 1A-K
not activeOct 16, 2023
Heating equipment
No permit to operate the boiler. serial no FY01-09-33140, CMC 1022. Monthly monitoring fee applies. Code Sec: SFBC 110A, Table 1A-K
not activeOct 16, 2023
Heating equipment
No permit to operate the boiler. serial no FY01-09-33138, CMC 1022. Monthly monitoring fee applies. Code Sec: SFBC 110A, Table 1A-K
not activeOct 16, 2023
Heating equipment
No permit to operate the boiler. serial no FY01-09-33139, CMC 1022. Monthly monitoring fee applies. Code Sec: SFBC 110A, Table 1A-K
not activeOct 16, 2023
Heating equipment
No permit to operate the boiler. serial no FY01-09-33137, CMC 1022. Monthly monitoring fee applies. Code Sec: SFBC 110A, Table 1A-K
not activeNov 20, 2020
DBI code violation
At the time of inspection the fire dept had not released the scene of the fire. Code/Section: SFBC 102A Monthly monitoring fee applies. Code/Section: SFBC 110A, Table 1A-K
not activeSep 16, 2020
Heating equipment
No permit to operate the boiler. serial no FY01-09-33138, CMC 1022. Monthly monitoring fee applies. Code Sec: SFBC 110A, Table 1A-K
not activeSep 16, 2020
Heating equipment
No permit to operate the boiler. serial no GY36-12-36476, CMC 1022. Monthly monitoring fee applies. Code Sec: SFBC 110A, Table 1A-K
not activeSep 16, 2020
Heating equipment
No permit to operate the boiler. serial no GY32-12-36416, CMC 1022. Monthly monitoring fee applies. Code Sec: SFBC 110A, Table 1A-K
not activeSep 16, 2020
Heating equipment
No permit to operate the boiler. serial no FY01-09-33137, CMC 1022. Monthly monitoring fee applies. Code Sec: SFBC 110A, Table 1A-K
not activeSep 16, 2020
Heating equipment
No permit to operate the boiler. serial no FY01-09-33140, CMC 1022. Monthly monitoring fee applies. Code Sec: SFBC 110A, Table 1A-K
not activeSep 16, 2020
Heating equipment
No permit to operate the boiler. serial no GY36-12-36475, CMC 1022. Monthly monitoring fee applies. Code Sec: SFBC 110A, Table 1A-K
not activeSep 16, 2020
Heating equipment
No permit to operate the boiler. serial no GY36-12-36477, CMC 1022. Monthly monitoring fee applies. Code Sec: SFBC 110A, Table 1A-K
not activeSep 16, 2020
Heating equipment
No permit to operate the boiler. serial no FY01-09-33139, CMC 1022. Monthly monitoring fee applies. Code Sec: SFBC 110A, Table 1A-K
not activeSep 16, 2020
Heating equipment
No permit to operate the boiler. serial no GY36-12-36478, CMC 1022. Monthly monitoring fee applies. Code Sec: SFBC 110A, Table 1A-K
not activeSep 16, 2020
Heating equipment
No permit to operate the boiler. serial no GY33-12-36429, CMC 1022. Monthly monitoring fee applies. Code Sec: SFBC 110A, Table 1A-K
not activeSep 16, 2020
Heating equipment
No permit to operate the boiler. serial no GY36-12-36516, CMC 1022. Monthly monitoring fee applies. Code Sec: SFBC 110A, Table 1A-K
not activeFeb 2, 2017
other section · repair defective or non-working elevator (1001(l), 713 hc)
at the time of inspection one of three elevators was out of service while a second was making loud scraping noises when in operation. complete the repairs in progress and return the elevators to full service.
not activeFeb 2, 2017
other section · inspector comments
it is the property owner's responsibility to be present or direct his/her representative to attend the re-inspection as scheduled on this notice of violation for the purpose of providing entry to the inspector of those areas not accessed during the initial inspection as specified, and/or to provide access to all areas cited within this notice. if the property owner cannot attend the scheduled re-inspection (as specified on this notice) it is his/her responsibility to secure a different inspection date and time with the inspector, and provide all tenants with notification as required by california civil code section 1954 (san francisco housing code section 303(b), if any dwellings, apartment units or guest rooms are to be accessed during the re-inspection. important note: due to the violations noted, this property is defined as a nuisance per sec. 1001-d of the sfhc. please review the attached "notice of violation warnings" for information regarding failure to comply with this notice.
not activeSep 22, 2015
Heating equipment
No permit to operate the boiler. serial no FY01-09-33138, CMC 1022
not activeSep 22, 2015
Heating equipment
No permit to operate the boiler. serial no FY01-09-33137, CMC 1022
not activeSep 22, 2015
Heating equipment
No permit to operate the boiler. serial no FY01-09-33140, CMC 1022
not activeSep 22, 2015
Heating equipment
No permit to operate the boiler. serial no FY01-09-33139, CMC 1022
not activeNov 4, 2014
DBI code violation
Kitchen remodel at Apt #1214 with no permits on file. Codes: 103A. 102A.3, table 1A-K -Monthly monitoring violation fee $52
not activeMar 26, 2013
Heating equipment
No permit to operate the boiler. serial no FY01 09 33139, CMC 1022
not activeMar 26, 2013
Heating equipment
No permit to operate the boiler. serial no FY01 09 33140, CMC 1022
not activeMar 26, 2013
Heating equipment
No permit to operate the boiler. serial no FY01 09 33138, CMC 1022
not activeMar 26, 2013
Heating equipment
No permit to operate the boiler. serial no FY01 09 33137, CMC 1022
not activeNov 2, 2011
DBI code violation
Stairways leading from 2nd floor common area deck to the public sidewalk at the center of the block facing Jackson Street and South end of the block facing Drumm Street are creating an overhanging obstruction hazard. 2010 CBC Section 1133B.8.2
not activeNov 2, 2011
DBI code violation
Failure to comply with 1st NOV issued on 11/1/11 Stairway creating an overhanging distruction hazard 2010 CBC Section 1133B.8.s
not activeAug 25, 2010
Heating equipment
No permit to operate the boiler. CMC 1023
not activeAug 25, 2010
Heating equipment
No permit to operate the boiler. CMC 1023
not activeAug 14, 2008
Plumbing
Plumbing work in lobby without permit. Examples: 4" copper victolic elbow, 2" vent, 1" indirect drain. SFPC 103.1 & 103.5.
not activeAug 11, 2006
building section · repair window latches or hardware (1001(b)hc)
make the following repairs in #2222: -replace the missing window crank to the left window in the bedroom; -repair/replace the non-functioning window cranks in the kitchen and bedroom.
not activeAug 11, 2006
other section · inspector comments
it is the property owner's responsibility to be present or direct his/her representative to attend, the reinspection as scheduled on this notice of violation for the purpose of providing entry to the inspector of those areas not accessed during the initial inspection as specified, and/or to provide access to all areas cited within this notice. if the property owner cannot attend the scheduled reinspection (as specified on this notice) it is his/her responsibility to secure a different inspection date and time with the inspector, and provide all tenants with notification as required by california civil code section 1954 (san francisco housing code section 303(b), if any dwellings, apartment units or guest rooms are to be accessed during the reinspection.