2500 ARELIOUS WALKER DR

Bayview Hunters Point · San Francisco, CA · Parcel 8803001 · Last violation Aug 17, 2026 · Last complaint Aug 17, 2026

NeighborhoodBayview Hunters Point
More violations than 99% of nearby buildings
More violations than 99% of buildings and more complaints than 100% of buildings in Bayview Hunters Point. Size-normalized against residential buildings in the neighborhood.
ViolationsComplaints
Activity TrendsLast 5 years
More activity recently than in past years
Last 2 yrs: 58 violations · 35 complaints
'21'26ViolationsComplaints
Severityⓘopen violations
9 open DBI violations
Active Notices of Violation issued by the Department of Building Inspection.
Severe0
Serious6
Minor3

What to watch forⓘ

  1. Fire safety problems have been reported here.
    Worth checkingⓘ
    Walk the exit route from the unit to the street and check the stairs and hallways are clear of stored items, and that fire doors close properly.
    details ▸

    California law requires safe fire or emergency exits leading to a street or hallway, and requires stairs, hallways and exits to be kept litter free. Storage areas, garages and basements must be kept free of combustible materials. San Francisco's Housing Code separately treats inadequate exits and inadequate fire protection equipment as conditions that make a building substandard, which is the finding behind a notice of violation.

    • California Tenant Guide
    • San Francisco Housing Code §1001(m), (n)
  2. Tenants here have reported no heat or no hot water.
    details ▸

    California law requires heating facilities in good working order, and plumbing facilities in good working order including hot and cold running water. A rental unit that substantially lacks either may be legally uninhabitable, which is the standard the implied warranty of habitability sets for every residential tenancy in the state.

311 Housing Complaints
Total complaints since 2020
52
7 per year avg.↑ Up 150% in the last 2 years (35 vs 14 prior 2 yrs)
Complaint severity
Last 5 years
50
Severeⓘ9
Seriousⓘ25
Minorⓘ16
Dept. of Building Inspection Violations
Total violations since 2019
168
21 per year avg.↓ Down 28% in the last 2 years (58 vs 81 prior 2 yrs)
Open violations
9
Severeⓘ0
Seriousⓘ6
Minorⓘ3

Top violation categories

5 yrsAll time
Fire safetyⓘ19 violations
Plumbingⓘ9 violations
Electricalⓘ8 violations
Floors & stairsⓘ7 violations
Peeling paintⓘ5 violations
Walls, ceilings & cabinetsⓘ5 violations
Smoke detectorsⓘ4 violations
Exterior & windowsⓘ4 violations
Cleanliness & refuseⓘ3 violations
Permits & unpermitted workⓘ2 violations
Heating equipmentⓘ2 violations
Moldⓘ1 violations
Pestsⓘ1 violations
General disrepairⓘ1 violations
Locks & securityⓘ1 violations
Heat / hot waterⓘ1 violations
No specific condition stated84 violations
5 still open. See violation log below.

Top complaint types

5 yrs
Hide violations (168) ↑See complaints (52) →

Violation log

159 DBI violations · Closed

AllOpenClosed
StatusFiledCategoryItemNOV Item Description
not activeApr 28, 2023security requirements sectionprovide primary locking devices at unit door (706 hc)repair the broken entry lock at unit 433, using approved materials and methods.
See something wrong? File a complaint with SF 311

Ask how heat and hot water are supplied and who pays for them. If either fails once you live here, put the request to the landlord in writing and keep a copy.

  • California Tenant Guide
  • San Francisco Housing Code §701
  • Smoke detector problems have been reported here.
    Worth checkingⓘ
    Look for a smoke detector in each bedroom and in the common stairwell, and for a carbon monoxide detector if the unit has a gas stove, a gas heater or an attached garage.
    details ▸

    California law requires working smoke detectors in all bedrooms and other designated areas of a rental unit, and apartment complexes must also have them in common stairwells. Any unit with appliances that burn fossil fuels such as natural gas, propane or fuel oil, or with an attached garage, must also have working carbon monoxide detectors.

    • California Tenant Guide
  • All time
    Infestation Rodent Insect10 complaints
    General Maintenance Not In List Above7 complaints
    Garbage Receptacles5 complaints
    Hot Water Lack Of Hot Water4 complaints
    Elevators Everthing Else4 complaints
    Bathroom3 complaints
    Doors Windows Broken Defective3 complaints
    Plumbing Broken Leaking3 complaints
    Mail Service Delivery Problem2 complaints
    Electrical Non Hazard2 complaints
    Fire Extinguishers Missing Expired2 complaints
    Mold And Mildew2 complaints
    Fire Hazard1 complaints
    Blocked Exit Common Areas1 complaints
    Smoke Detectors Missing Broken Unit Interior1 complaints
    not activeApr 28, 2023other sectioninspector commentsimportant note: due to the nature of this violation, this property has been defined as a nuisance per section 1001-d of the san francisco housing code. it is the property owner's responsibility to be present or direct his/her representative to attend the re-inspection as scheduled on this notice of violation for the purpose of providing entry to the inspector of those areas not accessed during the initial inspection as specified, and/or to provide access to all areas cited within this notice. if the property owner cannot attend the scheduled re-inspection (as specified on this notice) it is his/her responsibility to secure a different inspection date and time with the inspector. provide all tenants with notification as required by california civil code section 1954 (san francisco housing code section 303(b), if any dwellings, apartment units or guest rooms are to be accessed during the re-inspection. you can reach inspector chierici @ 628.652.3439 or by email at paul.chierici@sfgov.org.
    not activeMar 31, 2023building sectionthis notice includes violations for the areas noted.this notice includes violations of the san francisco housing code. unless noted otherwise, all violations were observed on the date of inspection at 2500 arelious walker dr., main front door.
    not activeMar 31, 2023security requirements sectionrepair self-closing devices at exterior doors (706 hc)at the time of inspection, main front entrance door failed to close fully and latch on its own. adjust closer and remove binding obstructions at sill/jamb so the door can freely close and latch on its own per industry standards.
    not activeMar 31, 2023other sectioninspector commentsimportant note: due to the nature of this violation, this property has been defined as a nuisance per section 1001-d of the san francisco housing code. it is the property owner's responsibility to be present or direct his/her representative to attend the re-inspection as scheduled on this notice of violation for the purpose of providing entry to the inspector of those areas not accessed during the initial inspection as specified, and/or to provide access to all areas cited within this notice. if the property owner cannot attend the scheduled re-inspection (as specified on this notice) it is his/her responsibility to secure a different inspection date and time with the inspector. provide all tenants with notification as required by california civil code section 1954 (san francisco housing code section 303(b), if any dwellings, apartment units or guest rooms are to be accessed during the re-inspection. you can reach inspector chierici @ 628.652.3439 or by email at paul.chierici@sfgov.org.
    not activeMar 20, 2023building sectionthis notice includes violations for the areas noted.this notice includes violations of the san francisco housing code. unless noted otherwise, all violations were observed on the date of inspection at 2500 arelious walker dr., common areas.
    not activeMar 20, 2023fire sectionmalfunctioning appliance - repair exit lighting sign 504g, 1001e, l, m sfhc, 1011.6.3 sfbcreplace exit lighting sign using approved materials and methods at 2nd floor exit corridor near unit 213, exit sign missing, wires dangling.
    not activeMar 20, 2023other sectioninspector commentsimportant note: due to the nature of this violation, this property has been defined as a nuisance per section 1001-d of the san francisco housing code. it is the property owner's responsibility to be present or direct his/her representative to attend the re-inspection as scheduled on this notice of violation for the purpose of providing entry to the inspector of those areas not accessed during the initial inspection as specified, and/or to provide access to all areas cited within this notice. if the property owner cannot attend the scheduled re-inspection (as specified on this notice) it is his/her responsibility to secure a different inspection date and time with the inspector. provide all tenants with notification as required by california civil code section 1954 (san francisco housing code section 303(b), if any dwellings, apartment units or guest rooms are to be accessed during the re-inspection. you can reach inspector chierici @ 628.652.3439 or by email at paul.chierici@sfgov.org.
    not activeMar 10, 2023building sectionthis notice includes violations for the areas noted.this notice includes violations of the san francisco housing code. unless noted otherwise, all violations were observed on the date of inspection at 2500 arelious walker dr., unit 246
    not activeMar 10, 2023building sectionprovide heat to each occupied habitable room capable to maintaining a min. room temp. of 70 degrees f. (701c hc)heater was inoperable at time of inspection. repair or replace heater as required. note: if the heater requires replacement, obtain an electrical, plumbing and/or mechanical permits as required.
    not activeMar 10, 2023other sectioninspector commentsimportant note: due to the nature of this violation, this property has been defined as a nuisance per section 1001-d of the san francisco housing code. it is the property owner's responsibility to be present or direct his/her representative to attend the re-inspection as scheduled on this notice of violation for the purpose of providing entry to the inspector of those areas not accessed during the initial inspection as specified, and/or to provide access to all areas cited within this notice.
    not activeMar 8, 2023building sectionthis notice includes violations for the areas noted.this notice includes violations of the san francisco housing code. unless noted otherwise, all violations were observed on the date of inspection at 2500 arelious walker dr., unit 246
    not activeMar 8, 2023building sectionlocate and repair source of water damage 703 & 1001(f) sfhcat time of inspection the damaged ceiling was reported to be the result of leaking water from the upstairs bathroom. locate source of damage and make necessary repairs. provide proof that the damage source has been located and repaired upon reinspection. provide dehumidifiers and drying equipment for remediation of any moisture left residing in the unit. replace drywall, tape, top, prime and paint all affected areas, using approved materials and methods. if more than 32 sq. ft of drywall is replaced a building permit is required. see attached lead hazard warning.
    not activeMar 8, 2023interior surfaces sectionreplace/repair floor covering (1001b,j,o hc)replace removed flooring and baseboards at upstairs hall, laundry closet and bathroom. kitchen and dining area flooring should be checked for moisture content and damage, replaced as necessary, using approved materials and methods. replace missing front nosings of stair treads leading from first floor to second floor, using approved materials and methods.
    not activeMar 8, 2023security requirements sectionprovide weather tight seal at front door (1001 hc)adjust strike at front door so that it pulls the door closed tightly when dead bolt is engaged. re-apply weatherstripping and door bottom around entire perimeter of door to stop water and air filtration.
    not activeMar 8, 2023other sectionlead hazard warning: disturbing lead based paint can be extremely dangerous to dwelling occupants and visitors, particularly to young children, pregnant women, pets, and to people performing work on the premises. for interior or exterior paint removal : always wet the surface, contain and properly dispose of leaded paint. if you are unsure whether the paint is leaded, you should test it prior to performing any work. if the paint is found to contain lead, you should consult with an expert about appropriate procedures. proper containment and 3-day notification is required for exterior jobs of more than 10 sq.ft. (sec.327, sfebc) informational packets are available at (415) 558-6088. you can contact the san francisco childhood lead poisoning prevention program at: (415) 252-3800 for free advice. if you cause lead dust to be created, you could be liable for any illness caused by the dust. ordinance #446-97.—
    not activeMar 8, 2023other sectioninspector commentsimportant note: due to the nature of this violation, this property has been defined as a nuisance per section 1001-d of the san francisco housing code. repairs cited in this notice may require building, plumbing and/or electrical permits. when you apply for a permit, reference the complaint number from this notice of violation. it is the responsibility of the owner to obtain (or have others obtain) any required permits before beginning work that requires permit(s). this case can not be abated until the housing inspector makes a final inspection to verify that all violations have been corrected and all required permits have been obtained and finalized. on reinspection day, present to the housing inspector the job card, permit application and permits indicating that all required work under permit is complete. prior to reinspection by housing inspector, call building, electrical and/or plumbing inspector(s) for required inspection(s). it is the property owner's responsibility to be present or direct his/her representative to attend the re-inspection as scheduled on this notice of violation for the purpose of providing entry to the inspector of those areas not accessed during the initial inspection as specified, and/or to provide access to all areas cited within this notice. if the property owner cannot attend the scheduled re-inspection (as specified on this notice) it is his/her responsibility to secure a different inspection date and time with the inspector. provide all tenants with notification as required by california civil code section 1954 (san francisco housing code section 303(b), if any dwellings, apartment units or guest rooms are to be accessed during the re-inspection. you can reach inspector chierici @ 628.652.3439 or by email at paul.chierici@sfgov.org.
    not activeFeb 24, 2023fire sectionremove egress obstruction at (801,1001(l) hc)remove book shelf cabinet in front of unit # 427. all storage items and matter shall be removed to create a permanent clear path of travel.
    not activeFeb 24, 2023building sectionthis notice includes violations for the areas noted.this notice includes violations of the san francisco housing code. unless noted otherwise, all violations were observed on the date of inspection at 2500 arelious walker dr., 4th floor common hallway.
    not activeFeb 24, 2023other sectioninspector commentsimportant note: due to the nature of this violation, this property has been defined as a nuisance per section 1001-d of the san francisco housing code. it is the property owner's responsibility to be present or direct his/her representative to attend the re-inspection as scheduled on this notice of violation for the purpose of providing entry to the inspector of those areas not accessed during the initial inspection as specified, and/or to provide access to all areas cited within this notice. if the property owner cannot attend the scheduled re-inspection (as specified on this notice) it is his/her responsibility to secure a different inspection date and time with the inspector. provide all tenants with notification as required by california civil code section 1954 (san francisco housing code section 303(b), if any dwellings, apartment units or guest rooms are to be accessed during the re-inspection. you can reach inspector chierici @ 628.652.3439 or by email at paul.chierici@sfgov.org.
    not activeFeb 21, 2023building sectionthis notice includes violations for the areas noted.this notice includes violations of the san francisco housing code. unless noted otherwise, all violations were observed on the date of inspection at 2500 arelious walker dr., unit 431.
    not activeFeb 21, 2023building sectionrepair window glazing seal (1001(h),(j),& 708 hc)it was noted at the time of inspection, the master bedroom window, lower left fixed insulated window panel seal has failed, causing fogging between the two glass panes. remove and replace failed insulated glass panel with an approved material and methods.
    not activeFeb 21, 2023other sectioninspector commentsimportant note: due to the nature of this violation, this property has been defined as a nuisance per section 1001-d of the san francisco housing code. it is the property owner's responsibility to be present or direct his/her representative to attend the re-inspection as scheduled on this notice of violation for the purpose of providing entry to the inspector of those areas not accessed during the initial inspection as specified, and/or to provide access to all areas cited within this notice. if the property owner cannot attend the scheduled re-inspection (as specified on this notice) it is his/her responsibility to secure a different inspection date and time with the inspector. provide all tenants with notification as required by california civil code section 1954 (san francisco housing code section 303(b), if any dwellings, apartment units or guest rooms are to be accessed during the re-inspection. you can reach inspector chierici @ 628.652.3439 or by email at paul.chierici@sfgov.org.
    not activeFeb 9, 2023building sectionthis notice includes violations for the areas noted.this notice includes violations of the san francisco housing code. unless noted otherwise, all violations were observed on the date of inspection at 2500 arelious walker dr., common areas.
    not activeFeb 9, 2023fire sectionrepair central alarm system (908, 909 hc)ceiling mounted illuminating exit signs were damaged and hanging by their wires in (2) locations in front of unit # 323. replace and test exit signage using approved materials and methods.
    not activeFeb 9, 2023fire sectionprovide fire extinguisher type 2a 10bc or equivalent.(905, 1001(n)hc)the fire extinguiser was missing from its hall wall cabinet adajacent to unit 1101 carrol ave. replace fire extinguisher with an approved product.
    not activeFeb 9, 2023other sectioninspector commentsimportant note: due to the nature of this violation, this property has been defined as a nuisance per section 1001-d of the san francisco housing code. it is the property owner's responsibility to be present or direct his/her representative to attend the re-inspection as scheduled on this notice of violation for the purpose of providing entry to the inspector of those areas not accessed during the initial inspection as specified, and/or to provide access to all areas cited within this notice. if the property owner cannot attend the scheduled re-inspection (as specified on this notice) it is his/her responsibility to secure a different inspection date and time with the inspector. provide all tenants with notification as required by california civil code section 1954 (san francisco housing code section 303(b), if any dwellings, apartment units or guest rooms are to be accessed during the re-inspection. you can reach inspector chierici @ 628.652.3439 or by email at paul.chierici@sfgov.org.
    not activeDec 16, 2022building sectionthis notice includes violations for the areas noted.this notice includes violations of the san francisco housing code. unless noted otherwise, all violations were observed on the date of inspection at 2500 arelious walker dr., 4th floor common areas.
    not activeDec 16, 2022fire sectionprovide fire extinguisher type 2a 10bc or equivalent.(905, 1001(n)hc)at the time of inspection, the fire extinguisher was missing from its cabinet at the fourth floor hall way, across from unit 426. provide a fire extinguisher type 2a 10bc or equivalent with current date tag.
    not activeDec 16, 2022interior surfaces sectionrepair damaged walls (1001b,h,o hc)at the time of inspection, the wall at the 4th floor stairwell 3, was damaged from the door handle opening into it. patch wall with approved materials and methods, provide door stop to prevent future damage.
    not activeDec 16, 2022other sectioninspector commentsimportant note: due to the nature of this violation, this property has been defined as a nuisance per section 1001-d of the san francisco housing code. it is the property owner's responsibility to be present or direct his/her representative to attend the re-inspection as scheduled on this notice of violation for the purpose of providing entry to the inspector of those areas not accessed during the initial inspection as specified, and/or to provide access to all areas cited within this notice. if the property owner cannot attend the scheduled re-inspection (as specified on this notice) it is his/her responsibility to secure a different inspection date and time with the inspector. provide all tenants with notification as required by california civil code section 1954 (san francisco housing code section 303(b), if any dwellings, apartment units or guest rooms are to be accessed during the re-inspection. you can reach inspector chierici @ 628.652.3439 or by email at paul.chierici@sfgov.org.
    not activeDec 13, 2022building sectionthis notice includes violations for the areas noted.this notice includes violations of the san francisco housing code. unless noted otherwise, all violations were observed on the date of inspection at 2500 arelious walker dr., common areas.
    not activeDec 13, 2022interior surfaces sectionclean and sanitize (1306 hc)at the time of inspection, clean and sanitize what appears to be blood traces noted in the follow areas: a)front lobby, signage between elevator doors b)4th floor wall above rubber base, across from unit 423 c)4th floor unit 433 door
    not activeDec 13, 2022other sectioninspector commentsimportant note: due to the nature of this violation, this property has been defined as a nuisance per section 1001-d of the san francisco housing code. it is the property owner's responsibility to be present or direct his/her representative to attend the re-inspection as scheduled on this notice of violation for the purpose of providing entry to the inspector of those areas not accessed during the initial inspection as specified, and/or to provide access to all areas cited within this notice. if the property owner cannot attend the scheduled re-inspection (as specified on this notice) it is his/her responsibility to secure a different inspection date and time with the inspector. provide all tenants with notification as required by california civil code section 1954 (san francisco housing code section 303(b), if any dwellings, apartment units or guest rooms are to be accessed during the re-inspection. you can reach inspector chierici @ 628.652.3439 or by email at paul.chierici@sfgov.org.
    not activeJul 1, 2022building sectionthis notice includes violations for the areas noted.this notice includes violations of the san francisco housing code. unless noted otherwise, all violations were observed on the date of inspection at 2500 arelious walker dr., unit 432
    not activeJul 1, 2022building sectionlocate and repair source of water damage 703 & 1001(f) sfhcat time of inspection there was removed drywall from ceiling and walls at the tub surround and linen closet as reported to be the result of leaking water from unit above. locate source of damage and make necessary repairs. provide proof that the damage source has been located and repaired upon reinspection. if plumbing piping is replaced/added, a plumbing permit and corresponding inspection are required.
    not activeJul 1, 2022interior surfaces sectionrepair damaged ceilings and walls (1001b,h,o hc)replace all removed drywall at shower surround ceiling, walls and linen closet ceiling and walls. tape, top and finish as necessary. areas should be cleaned, sanitized and repainted with a mold resistant paint. due to the amount of drywall to be replaced a building permit is required. **you are required to obtain a building permit to correct this violation. when all work is complete the building inspector must inspect and sign the final inspection job card before the housing inspector can abate this violation. please present the signed job card indicating that work is complete to the housing inspector at reinspection day.**
    not activeJul 1, 2022other sectionnuisance (1001(d))important note: due to the nature of this violation, this property has been defined as a nuisance per section 1001-d of the san francisco housing code.
    not activeJul 1, 2022other sectioninspector commentsrepairs cited in this notice may require building, plumbing and/or electrical permits. when you apply for a permit, reference the complaint number from this notice of violation. it is the responsibility of the owner to obtain (or have others obtain) any required permits before beginning work that requires permit(s). this case can not be abated until the housing inspector makes a final inspection to verify that all violations have been corrected and all required permits have been obtained and finalized. on reinspection day, present to the housing inspector the job card, permit application and permits indicating that all required work under permit is complete. prior to reinspection by housing inspector, call building, electrical and/or plumbing inspector(s) for required inspection(s). it is the property owner's responsibility to be present or direct his/her representative to attend the re-inspection as scheduled on this notice of violation for the purpose of providing entry to the inspector of those areas not accessed during the initial inspection as specified, and/or to provide access to all areas cited within this notice. if the property owner cannot attend the scheduled re-inspection (as specified on this notice) it is his/her responsibility to secure a different inspection date and time with the inspector. provide all tenants with notification as required by california civil code section 1954 (san francisco housing code section 303(b), if any dwellings, apartment units or guest rooms are to be accessed during the re-inspection. you can reach inspector chierici @ 628.652.3439 or by email at paul.chierici@sfgov.org.
    not activeMay 12, 2022building sectionthis notice includes violations for the areas noted.this notice includes violations of the san francisco housing code. unless noted otherwise, all violations were observed on the date of inspection at 2500 arelios walker dr, common area door adjacent to 1107 carrol st.
    not activeMay 12, 2022building sectionrepair exterior door glazing 1001(b) sfhcat the time of inspection, the common area exterior glass door adjacent to 1107 carrol st. was shattered. replace glazing using an approved material and methods.
    not activeMay 12, 2022other sectionnuisance (1001(d))important note: due to the nature of this violation, this property has been defined as a nuisance per section 1001-d of the san francisco housing code.
    not activeMay 12, 2022other sectioninspector commentsit is the property owner's responsibility to be present or direct his/her representative to attend the re-inspection as scheduled on this notice of violation for the purpose of providing entry to the inspector of those areas not accessed during the initial inspection as specified, and/or to provide access to all areas cited within this notice. if the property owner cannot attend the scheduled re-inspection (as specified on this notice) it is his/her responsibility to secure a different inspection date and time with the inspector. provide all tenants with notification as required by california civil code section 1954 (san francisco housing code section 303(b), if any dwellings, apartment units or guest rooms are to be accessed during the re-inspection. you can reach inspector chierici @ 628.652.3439 or by email at paul.chierici@sfgov.org.
    not activeFeb 14, 2022building sectionthis notice includes violations for the areas noted.this notice includes violations of the san francisco housing code. unless noted otherwise, all violations were observed on the date of inspection at 2500 arelious walker dr., unit 309.
    not activeFeb 14, 2022interior surfaces sectionlocate and repair source of water damage. 703 & 1001(f) sfhcat the time of inspection, water intrusian was noted at ceilings throughout the unit. locate and repair source of water damage. provide written documentation identifying the source of the damage and the steps taken to prevent future damage at re-inspection.
    not activeFeb 14, 2022interior surfaces sectionrepair damaged ceilings and walls (1001b,h,o hc)provide dehumidifiers and drying equipment for remediation of any moisture left residing in the unit. provide moisture monitoring logs along with a report and certificate of water mitigation service. replace drywall, tape, top prime and paint all affected areas. if more than 10 sq. ft of drywall is replaced a building permit is required.
    not activeFeb 14, 2022other sectionnuisance (1001(d))important note: due to the nature of this violation, this property has been defined as a nuisance per section 1001-d of the san francisco housing code.
    not activeFeb 14, 2022other sectioninspector commentsit is the property owner's responsibility to be present or direct his/her representative to attend the re-inspection as scheduled on this notice of violation for the purpose of providing entry to the inspector of those areas not accessed during the initial inspection as specified, and/or to provide access to all areas cited within this notice. if the property owner cannot attend the scheduled re-inspection (as specified on this notice) it is his/her responsibility to secure a different inspection date and time with the inspector. provide all tenants with notification as required by california civil code section 1954 (san francisco housing code section 303(b), if any dwellings, apartment units or guest rooms are to be accessed during the re-inspection. you can reach inspector chierici @ 628.652.3439 or by email at paul.chierici@sfgov.org.
    not activeAug 17, 2021Heating equipment—No permit to operate the boiler. serial no G17391337, CMC 1022. Monthly monitoring fee applies. Code Sec: SFBC 110A, Table 1A-K
    not activeAug 17, 2021Heating equipment—No permit to operate the boiler. serial no G17391335, CMC 1022. Monthly monitoring fee applies. Code Sec: SFBC 110A, Table 1A-K
    not activeApr 28, 2023
    security requirements section · provide primary locking devices at unit door (706 hc)
    repair the broken entry lock at unit 433, using approved materials and methods.
    not activeApr 28, 2023
    other section · inspector comments
    important note: due to the nature of this violation, this property has been defined as a nuisance per section 1001-d of the san francisco housing code. it is the property owner's responsibility to be present or direct his/her representative to attend the re-inspection as scheduled on this notice of violation for the purpose of providing entry to the inspector of those areas not accessed during the initial inspection as specified, and/or to provide access to all areas cited within this notice. if the property owner cannot attend the scheduled re-inspection (as specified on this notice) it is his/her responsibility to secure a different inspection date and time with the inspector. provide all tenants with notification as required by california civil code section 1954 (san francisco housing code section 303(b), if any dwellings, apartment units or guest rooms are to be accessed during the re-inspection. you can reach inspector chierici @ 628.652.3439 or by email at paul.chierici@sfgov.org.
    not activeMar 31, 2023
    building section · this notice includes violations for the areas noted.
    this notice includes violations of the san francisco housing code. unless noted otherwise, all violations were observed on the date of inspection at 2500 arelious walker dr., main front door.
    not activeMar 31, 2023
    security requirements section · repair self-closing devices at exterior doors (706 hc)
    at the time of inspection, main front entrance door failed to close fully and latch on its own. adjust closer and remove binding obstructions at sill/jamb so the door can freely close and latch on its own per industry standards.
    not activeMar 31, 2023
    other section · inspector comments
    important note: due to the nature of this violation, this property has been defined as a nuisance per section 1001-d of the san francisco housing code. it is the property owner's responsibility to be present or direct his/her representative to attend the re-inspection as scheduled on this notice of violation for the purpose of providing entry to the inspector of those areas not accessed during the initial inspection as specified, and/or to provide access to all areas cited within this notice. if the property owner cannot attend the scheduled re-inspection (as specified on this notice) it is his/her responsibility to secure a different inspection date and time with the inspector. provide all tenants with notification as required by california civil code section 1954 (san francisco housing code section 303(b), if any dwellings, apartment units or guest rooms are to be accessed during the re-inspection. you can reach inspector chierici @ 628.652.3439 or by email at paul.chierici@sfgov.org.
    not activeMar 20, 2023
    building section · this notice includes violations for the areas noted.
    this notice includes violations of the san francisco housing code. unless noted otherwise, all violations were observed on the date of inspection at 2500 arelious walker dr., common areas.
    not activeMar 20, 2023
    fire section · malfunctioning appliance - repair exit lighting sign 504g, 1001e, l, m sfhc, 1011.6.3 sfbc
    replace exit lighting sign using approved materials and methods at 2nd floor exit corridor near unit 213, exit sign missing, wires dangling.
    not activeMar 20, 2023
    other section · inspector comments
    important note: due to the nature of this violation, this property has been defined as a nuisance per section 1001-d of the san francisco housing code. it is the property owner's responsibility to be present or direct his/her representative to attend the re-inspection as scheduled on this notice of violation for the purpose of providing entry to the inspector of those areas not accessed during the initial inspection as specified, and/or to provide access to all areas cited within this notice. if the property owner cannot attend the scheduled re-inspection (as specified on this notice) it is his/her responsibility to secure a different inspection date and time with the inspector. provide all tenants with notification as required by california civil code section 1954 (san francisco housing code section 303(b), if any dwellings, apartment units or guest rooms are to be accessed during the re-inspection. you can reach inspector chierici @ 628.652.3439 or by email at paul.chierici@sfgov.org.
    not activeMar 10, 2023
    building section · this notice includes violations for the areas noted.
    this notice includes violations of the san francisco housing code. unless noted otherwise, all violations were observed on the date of inspection at 2500 arelious walker dr., unit 246
    not activeMar 10, 2023
    building section · provide heat to each occupied habitable room capable to maintaining a min. room temp. of 70 degrees f. (701c hc)
    heater was inoperable at time of inspection. repair or replace heater as required. note: if the heater requires replacement, obtain an electrical, plumbing and/or mechanical permits as required.
    not activeMar 10, 2023
    other section · inspector comments
    important note: due to the nature of this violation, this property has been defined as a nuisance per section 1001-d of the san francisco housing code. it is the property owner's responsibility to be present or direct his/her representative to attend the re-inspection as scheduled on this notice of violation for the purpose of providing entry to the inspector of those areas not accessed during the initial inspection as specified, and/or to provide access to all areas cited within this notice.
    not activeMar 8, 2023
    building section · this notice includes violations for the areas noted.
    this notice includes violations of the san francisco housing code. unless noted otherwise, all violations were observed on the date of inspection at 2500 arelious walker dr., unit 246
    not activeMar 8, 2023
    building section · locate and repair source of water damage 703 & 1001(f) sfhc
    at time of inspection the damaged ceiling was reported to be the result of leaking water from the upstairs bathroom. locate source of damage and make necessary repairs. provide proof that the damage source has been located and repaired upon reinspection. provide dehumidifiers and drying equipment for remediation of any moisture left residing in the unit. replace drywall, tape, top, prime and paint all affected areas, using approved materials and methods. if more than 32 sq. ft of drywall is replaced a building permit is required. see attached lead hazard warning.
    not activeMar 8, 2023
    interior surfaces section · replace/repair floor covering (1001b,j,o hc)
    replace removed flooring and baseboards at upstairs hall, laundry closet and bathroom. kitchen and dining area flooring should be checked for moisture content and damage, replaced as necessary, using approved materials and methods. replace missing front nosings of stair treads leading from first floor to second floor, using approved materials and methods.
    not activeMar 8, 2023
    security requirements section · provide weather tight seal at front door (1001 hc)
    adjust strike at front door so that it pulls the door closed tightly when dead bolt is engaged. re-apply weatherstripping and door bottom around entire perimeter of door to stop water and air filtration.
    not activeMar 8, 2023
    other section · lead hazard warning: disturbing lead based paint can be extremely dangerous to dwelling occupants and visitors, particularly to young children, pregnant women, pets, and to people performing work on the premises. for interior or exterior paint removal : always wet the surface, contain and properly dispose of leaded paint. if you are unsure whether the paint is leaded, you should test it prior to performing any work. if the paint is found to contain lead, you should consult with an expert about appropriate procedures. proper containment and 3-day notification is required for exterior jobs of more than 10 sq.ft. (sec.327, sfebc) informational packets are available at (415) 558-6088. you can contact the san francisco childhood lead poisoning prevention program at: (415) 252-3800 for free advice. if you cause lead dust to be created, you could be liable for any illness caused by the dust. ordinance #446-97.
    not activeMar 8, 2023
    other section · inspector comments
    important note: due to the nature of this violation, this property has been defined as a nuisance per section 1001-d of the san francisco housing code. repairs cited in this notice may require building, plumbing and/or electrical permits. when you apply for a permit, reference the complaint number from this notice of violation. it is the responsibility of the owner to obtain (or have others obtain) any required permits before beginning work that requires permit(s). this case can not be abated until the housing inspector makes a final inspection to verify that all violations have been corrected and all required permits have been obtained and finalized. on reinspection day, present to the housing inspector the job card, permit application and permits indicating that all required work under permit is complete. prior to reinspection by housing inspector, call building, electrical and/or plumbing inspector(s) for required inspection(s). it is the property owner's responsibility to be present or direct his/her representative to attend the re-inspection as scheduled on this notice of violation for the purpose of providing entry to the inspector of those areas not accessed during the initial inspection as specified, and/or to provide access to all areas cited within this notice. if the property owner cannot attend the scheduled re-inspection (as specified on this notice) it is his/her responsibility to secure a different inspection date and time with the inspector. provide all tenants with notification as required by california civil code section 1954 (san francisco housing code section 303(b), if any dwellings, apartment units or guest rooms are to be accessed during the re-inspection. you can reach inspector chierici @ 628.652.3439 or by email at paul.chierici@sfgov.org.
    not activeFeb 24, 2023
    fire section · remove egress obstruction at (801,1001(l) hc)
    remove book shelf cabinet in front of unit # 427. all storage items and matter shall be removed to create a permanent clear path of travel.
    not activeFeb 24, 2023
    building section · this notice includes violations for the areas noted.
    this notice includes violations of the san francisco housing code. unless noted otherwise, all violations were observed on the date of inspection at 2500 arelious walker dr., 4th floor common hallway.
    not activeFeb 24, 2023
    other section · inspector comments
    important note: due to the nature of this violation, this property has been defined as a nuisance per section 1001-d of the san francisco housing code. it is the property owner's responsibility to be present or direct his/her representative to attend the re-inspection as scheduled on this notice of violation for the purpose of providing entry to the inspector of those areas not accessed during the initial inspection as specified, and/or to provide access to all areas cited within this notice. if the property owner cannot attend the scheduled re-inspection (as specified on this notice) it is his/her responsibility to secure a different inspection date and time with the inspector. provide all tenants with notification as required by california civil code section 1954 (san francisco housing code section 303(b), if any dwellings, apartment units or guest rooms are to be accessed during the re-inspection. you can reach inspector chierici @ 628.652.3439 or by email at paul.chierici@sfgov.org.
    not activeFeb 21, 2023
    building section · this notice includes violations for the areas noted.
    this notice includes violations of the san francisco housing code. unless noted otherwise, all violations were observed on the date of inspection at 2500 arelious walker dr., unit 431.
    not activeFeb 21, 2023
    building section · repair window glazing seal (1001(h),(j),& 708 hc)
    it was noted at the time of inspection, the master bedroom window, lower left fixed insulated window panel seal has failed, causing fogging between the two glass panes. remove and replace failed insulated glass panel with an approved material and methods.
    not activeFeb 21, 2023
    other section · inspector comments
    important note: due to the nature of this violation, this property has been defined as a nuisance per section 1001-d of the san francisco housing code. it is the property owner's responsibility to be present or direct his/her representative to attend the re-inspection as scheduled on this notice of violation for the purpose of providing entry to the inspector of those areas not accessed during the initial inspection as specified, and/or to provide access to all areas cited within this notice. if the property owner cannot attend the scheduled re-inspection (as specified on this notice) it is his/her responsibility to secure a different inspection date and time with the inspector. provide all tenants with notification as required by california civil code section 1954 (san francisco housing code section 303(b), if any dwellings, apartment units or guest rooms are to be accessed during the re-inspection. you can reach inspector chierici @ 628.652.3439 or by email at paul.chierici@sfgov.org.
    not activeFeb 9, 2023
    building section · this notice includes violations for the areas noted.
    this notice includes violations of the san francisco housing code. unless noted otherwise, all violations were observed on the date of inspection at 2500 arelious walker dr., common areas.
    not activeFeb 9, 2023
    fire section · repair central alarm system (908, 909 hc)
    ceiling mounted illuminating exit signs were damaged and hanging by their wires in (2) locations in front of unit # 323. replace and test exit signage using approved materials and methods.
    not activeFeb 9, 2023
    fire section · provide fire extinguisher type 2a 10bc or equivalent.(905, 1001(n)hc)
    the fire extinguiser was missing from its hall wall cabinet adajacent to unit 1101 carrol ave. replace fire extinguisher with an approved product.
    not activeFeb 9, 2023
    other section · inspector comments
    important note: due to the nature of this violation, this property has been defined as a nuisance per section 1001-d of the san francisco housing code. it is the property owner's responsibility to be present or direct his/her representative to attend the re-inspection as scheduled on this notice of violation for the purpose of providing entry to the inspector of those areas not accessed during the initial inspection as specified, and/or to provide access to all areas cited within this notice. if the property owner cannot attend the scheduled re-inspection (as specified on this notice) it is his/her responsibility to secure a different inspection date and time with the inspector. provide all tenants with notification as required by california civil code section 1954 (san francisco housing code section 303(b), if any dwellings, apartment units or guest rooms are to be accessed during the re-inspection. you can reach inspector chierici @ 628.652.3439 or by email at paul.chierici@sfgov.org.
    not activeDec 16, 2022
    building section · this notice includes violations for the areas noted.
    this notice includes violations of the san francisco housing code. unless noted otherwise, all violations were observed on the date of inspection at 2500 arelious walker dr., 4th floor common areas.
    not activeDec 16, 2022
    fire section · provide fire extinguisher type 2a 10bc or equivalent.(905, 1001(n)hc)
    at the time of inspection, the fire extinguisher was missing from its cabinet at the fourth floor hall way, across from unit 426. provide a fire extinguisher type 2a 10bc or equivalent with current date tag.
    not activeDec 16, 2022
    interior surfaces section · repair damaged walls (1001b,h,o hc)
    at the time of inspection, the wall at the 4th floor stairwell 3, was damaged from the door handle opening into it. patch wall with approved materials and methods, provide door stop to prevent future damage.
    not activeDec 16, 2022
    other section · inspector comments
    important note: due to the nature of this violation, this property has been defined as a nuisance per section 1001-d of the san francisco housing code. it is the property owner's responsibility to be present or direct his/her representative to attend the re-inspection as scheduled on this notice of violation for the purpose of providing entry to the inspector of those areas not accessed during the initial inspection as specified, and/or to provide access to all areas cited within this notice. if the property owner cannot attend the scheduled re-inspection (as specified on this notice) it is his/her responsibility to secure a different inspection date and time with the inspector. provide all tenants with notification as required by california civil code section 1954 (san francisco housing code section 303(b), if any dwellings, apartment units or guest rooms are to be accessed during the re-inspection. you can reach inspector chierici @ 628.652.3439 or by email at paul.chierici@sfgov.org.
    not activeDec 13, 2022
    building section · this notice includes violations for the areas noted.
    this notice includes violations of the san francisco housing code. unless noted otherwise, all violations were observed on the date of inspection at 2500 arelious walker dr., common areas.
    not activeDec 13, 2022
    interior surfaces section · clean and sanitize (1306 hc)
    at the time of inspection, clean and sanitize what appears to be blood traces noted in the follow areas: a)front lobby, signage between elevator doors b)4th floor wall above rubber base, across from unit 423 c)4th floor unit 433 door
    not activeDec 13, 2022
    other section · inspector comments
    important note: due to the nature of this violation, this property has been defined as a nuisance per section 1001-d of the san francisco housing code. it is the property owner's responsibility to be present or direct his/her representative to attend the re-inspection as scheduled on this notice of violation for the purpose of providing entry to the inspector of those areas not accessed during the initial inspection as specified, and/or to provide access to all areas cited within this notice. if the property owner cannot attend the scheduled re-inspection (as specified on this notice) it is his/her responsibility to secure a different inspection date and time with the inspector. provide all tenants with notification as required by california civil code section 1954 (san francisco housing code section 303(b), if any dwellings, apartment units or guest rooms are to be accessed during the re-inspection. you can reach inspector chierici @ 628.652.3439 or by email at paul.chierici@sfgov.org.
    not activeJul 1, 2022
    building section · this notice includes violations for the areas noted.
    this notice includes violations of the san francisco housing code. unless noted otherwise, all violations were observed on the date of inspection at 2500 arelious walker dr., unit 432
    not activeJul 1, 2022
    building section · locate and repair source of water damage 703 & 1001(f) sfhc
    at time of inspection there was removed drywall from ceiling and walls at the tub surround and linen closet as reported to be the result of leaking water from unit above. locate source of damage and make necessary repairs. provide proof that the damage source has been located and repaired upon reinspection. if plumbing piping is replaced/added, a plumbing permit and corresponding inspection are required.
    not activeJul 1, 2022
    interior surfaces section · repair damaged ceilings and walls (1001b,h,o hc)
    replace all removed drywall at shower surround ceiling, walls and linen closet ceiling and walls. tape, top and finish as necessary. areas should be cleaned, sanitized and repainted with a mold resistant paint. due to the amount of drywall to be replaced a building permit is required. **you are required to obtain a building permit to correct this violation. when all work is complete the building inspector must inspect and sign the final inspection job card before the housing inspector can abate this violation. please present the signed job card indicating that work is complete to the housing inspector at reinspection day.**
    not activeJul 1, 2022
    other section · nuisance (1001(d))
    important note: due to the nature of this violation, this property has been defined as a nuisance per section 1001-d of the san francisco housing code.
    not activeJul 1, 2022
    other section · inspector comments
    repairs cited in this notice may require building, plumbing and/or electrical permits. when you apply for a permit, reference the complaint number from this notice of violation. it is the responsibility of the owner to obtain (or have others obtain) any required permits before beginning work that requires permit(s). this case can not be abated until the housing inspector makes a final inspection to verify that all violations have been corrected and all required permits have been obtained and finalized. on reinspection day, present to the housing inspector the job card, permit application and permits indicating that all required work under permit is complete. prior to reinspection by housing inspector, call building, electrical and/or plumbing inspector(s) for required inspection(s). it is the property owner's responsibility to be present or direct his/her representative to attend the re-inspection as scheduled on this notice of violation for the purpose of providing entry to the inspector of those areas not accessed during the initial inspection as specified, and/or to provide access to all areas cited within this notice. if the property owner cannot attend the scheduled re-inspection (as specified on this notice) it is his/her responsibility to secure a different inspection date and time with the inspector. provide all tenants with notification as required by california civil code section 1954 (san francisco housing code section 303(b), if any dwellings, apartment units or guest rooms are to be accessed during the re-inspection. you can reach inspector chierici @ 628.652.3439 or by email at paul.chierici@sfgov.org.
    not activeMay 12, 2022
    building section · this notice includes violations for the areas noted.
    this notice includes violations of the san francisco housing code. unless noted otherwise, all violations were observed on the date of inspection at 2500 arelios walker dr, common area door adjacent to 1107 carrol st.
    not activeMay 12, 2022
    building section · repair exterior door glazing 1001(b) sfhc
    at the time of inspection, the common area exterior glass door adjacent to 1107 carrol st. was shattered. replace glazing using an approved material and methods.
    not activeMay 12, 2022
    other section · nuisance (1001(d))
    important note: due to the nature of this violation, this property has been defined as a nuisance per section 1001-d of the san francisco housing code.
    not activeMay 12, 2022
    other section · inspector comments
    it is the property owner's responsibility to be present or direct his/her representative to attend the re-inspection as scheduled on this notice of violation for the purpose of providing entry to the inspector of those areas not accessed during the initial inspection as specified, and/or to provide access to all areas cited within this notice. if the property owner cannot attend the scheduled re-inspection (as specified on this notice) it is his/her responsibility to secure a different inspection date and time with the inspector. provide all tenants with notification as required by california civil code section 1954 (san francisco housing code section 303(b), if any dwellings, apartment units or guest rooms are to be accessed during the re-inspection. you can reach inspector chierici @ 628.652.3439 or by email at paul.chierici@sfgov.org.
    not activeFeb 14, 2022
    building section · this notice includes violations for the areas noted.
    this notice includes violations of the san francisco housing code. unless noted otherwise, all violations were observed on the date of inspection at 2500 arelious walker dr., unit 309.
    not activeFeb 14, 2022
    interior surfaces section · locate and repair source of water damage. 703 & 1001(f) sfhc
    at the time of inspection, water intrusian was noted at ceilings throughout the unit. locate and repair source of water damage. provide written documentation identifying the source of the damage and the steps taken to prevent future damage at re-inspection.
    not activeFeb 14, 2022
    interior surfaces section · repair damaged ceilings and walls (1001b,h,o hc)
    provide dehumidifiers and drying equipment for remediation of any moisture left residing in the unit. provide moisture monitoring logs along with a report and certificate of water mitigation service. replace drywall, tape, top prime and paint all affected areas. if more than 10 sq. ft of drywall is replaced a building permit is required.
    not activeFeb 14, 2022
    other section · nuisance (1001(d))
    important note: due to the nature of this violation, this property has been defined as a nuisance per section 1001-d of the san francisco housing code.
    not activeFeb 14, 2022
    other section · inspector comments
    it is the property owner's responsibility to be present or direct his/her representative to attend the re-inspection as scheduled on this notice of violation for the purpose of providing entry to the inspector of those areas not accessed during the initial inspection as specified, and/or to provide access to all areas cited within this notice. if the property owner cannot attend the scheduled re-inspection (as specified on this notice) it is his/her responsibility to secure a different inspection date and time with the inspector. provide all tenants with notification as required by california civil code section 1954 (san francisco housing code section 303(b), if any dwellings, apartment units or guest rooms are to be accessed during the re-inspection. you can reach inspector chierici @ 628.652.3439 or by email at paul.chierici@sfgov.org.
    not activeAug 17, 2021
    Heating equipment
    No permit to operate the boiler. serial no G17391337, CMC 1022. Monthly monitoring fee applies. Code Sec: SFBC 110A, Table 1A-K
    not activeAug 17, 2021
    Heating equipment
    No permit to operate the boiler. serial no G17391335, CMC 1022. Monthly monitoring fee applies. Code Sec: SFBC 110A, Table 1A-K
    Page 3 of 4