10 OSCEOLA LN

Bayview Hunters Point · San Francisco, CA · Parcel 4715012 · Last violation Aug 10, 2026 · Last complaint Aug 7, 2026

NeighborhoodBayview Hunters Point
More violations than 99% of nearby buildings
More violations than 99% of buildings and more complaints than 97% of buildings in Bayview Hunters Point. Size-normalized against residential buildings in the neighborhood.
ViolationsComplaints
Activity TrendsLast 5 years
A steady level of activity over time
Last 2 yrs: 46 violations · 13 complaints
'21'26ViolationsComplaints
Severityⓘopen violations
1 open fire-safety violation
Active Notices of Violation issued by the Department of Building Inspection.
Severe1
Serious2
Minor8
311 Housing Complaints
Total complaints since 2016
34
3 per year avg.↑ Up 30% in the last 2 years (13 vs 10 prior 2 yrs)
Complaint severity
Last 5 years
26
Severeⓘ2
Seriousⓘ12
Minorⓘ12
Dept. of Building Inspection Violations
Total violations since 1998
191
7 per year avg.↑ Up 1050% in the last 2 years (46 vs 4 prior 2 yrs)
Open violations
11
Severeⓘ1
Seriousⓘ2
Minorⓘ8

Top violation categories

5 yrsAll time
other sectionⓘ48 violations
building sectionⓘ42 violations
interior surfaces section36 violations
fire sectionⓘ22 violations
smoke detection section15 violations
security requirements section13 violations
plumbing and electrical section9 violations
sanitation section6 violations

Top complaint types

5 yrsAll time
Infestation Rodent Insect11 complaints
General Maintenance Not In List Above8 complaints
Garbage Receptacles3 complaints
Mold And Mildew2 complaints
Heat Lack Of Heat2 complaints
Doors Windows Broken Defective2 complaints
Ventilation Inadequate Or None1 complaints
Electrical Non Hazard1 complaints
Inadequately Maintained Building Exterior1 complaints
Infestation Bed Bugs1 complaints
Plumbing Broken Leaking1 complaints
Security Inadequately Secured Perimeter1 complaints
Hide violations (191) ↑See complaints (34) →

Violation log

191 DBI violations

AllOpenClosed
StatusFiledCategoryItemNOV Item Description
not activeJul 25, 2022building sectionthis notice includes violations for the areas noted.this notice includes violations of the san francisco housing code. unless noted otherwise, all violations were observed on the date of inspection at 20 osceola ln, common areas.
See something wrong? File a complaint with SF 311
not activeJul 25, 2022other sectioninspector commentsit is the property owner's responsibility to be present or direct his/her representative to attend the re-inspection as scheduled on this notice of violation for the purpose of providing entry to the inspector of those areas not accessed during the initial inspection as specified, and/or to provide access to all areas cited within this notice. if the property owner cannot attend the scheduled re-inspection (as specified on this notice) it is his/her responsibility to secure a different inspection date and time with the inspector. provide all tenants with notification as required by california civil code section 1954 (san francisco housing code section 303(b), if any dwellings, apartment units or guest rooms are to be accessed during the re-inspection. you can reach inspector chierici @ 628.652.3439 or by email at paul.chierici@sfgov.org.
not activeJul 25, 2022plumbing and electrical sectionrepair ceiling light fixture (1001e hc)ensure ceiling light fixture at front entry is secured tightly to its junction box in an approved manner.
not activeJul 25, 2022fire sectionrepair fire proofing with approved materials (hc 1001 (n), 809)repair the damaged wall at the rear second floor stairwell with approved materials: lath and 3/4" plaster or type-x drywall, to maintain its approved fire rating.
not activeJul 25, 2022fire sectionprovide fire extinguisher type 2a 10bc or equivalent.(905, 1001(n)hc)missing fire extinguisher at second level wall cabinet. provide an a approved fire extinguisher. all fire extinguishers are required to be recharged and serviced annually and service date tag must be current and posted by a qualified professional vendor. check the pressure gauge periodically as occasionally the seal may leak and the unit becomes ineffective.
not activeJul 25, 2022security requirements sectionrepair gate latch (706 hc) (1001 hc)the front security gate latch was broken and not allowing the gate to latch. the rear security gate when closed does not lock from the exterior side. repair the gates so that they self close, latch and lock without assisstance using approved materials and methods.
not activeJul 25, 2022other sectionnuisance (1001(d))important note: due to the nature of this violation, this property has been defined as a nuisance per section 1001-d of the san francisco housing code.
not activeSep 10, 2021other sectioninspector commentsit is the property owner's responsibility to be present or direct his/her representative to attend the re-inspection as scheduled on this notice of violation for the purpose of providing entry to the inspector of those areas not accessed during the initial inspection as specified, and/or to provide access to all areas cited within this notice. if the property owner cannot attend the scheduled re-inspection (as specified on this notice) it is his/her responsibility to secure a different inspection date and time with the inspector. provide all tenants with notification as required by california civil code section 1954 (san francisco housing code section 303(b), if any dwellings, apartment units or guest rooms are to be accessed during the re-inspection. you can reach inspector chierici @ 628.652.3439 or by email at paul.chierici@sfgov.org.
not activeSep 10, 2021building sectionthis notice includes violations for the areas noted.20 osceola ln 2nd floor common area
not activeSep 10, 2021fire sectionprovide fire extinguisher type 2a 10bc or equivalent.(905, 1001(n)hc)at the time of re-inspection for another complaint, the 2nd floor stairwell fire exstinguisher was missing as seen from the la salle av. replace in kind. all fire extinguishers are required to be recharged and serviced annually and service date tag must be current and posted by a qualified professional vendor. check the pressure gauge periodically as occasionally the seal may leaks and the unit becomes ineffective.
not activeNov 8, 2019fire sectionremove egress obstruction (801,1001(l) hc)remove all storage/trash at fire escape.
not activeNov 8, 2019fire sectionrecharge/date tag fire extinguisher type 2a 10bc or equivalent (905,1001(m)hc)all fire extinguishers are required to be recharged and serviced annually and service date tag must be current and posted by a qualified professional vendor. check the pressure gauge periodically as occasionally the seal may leak and the unit becomes ineffective.
not activeNov 8, 2019other sectioninspector commentsit is the property owner's responsibility to be present or direct his/her representative to attend the re-inspection as scheduled on this notice of violation for the purpose of providing entry to the inspector of those areas not accessed during the initial inspection as specified, and/or to provide access to all areas cited within this notice. if the property owner cannot attend the scheduled re-inspection (as specified on this notice) it is his/her responsibility to secure a different inspection date and time with the inspector. provide all tenants with notification as required by california civil code section 1954 (san francisco housing code section 303(b), if any dwellings, apartment units or guest rooms are to be accessed during the re-inspection. you can reach inspector wu @ 415-575-6844 or by email at timothy.wu@sfgov.org.
not activeNov 8, 2019building sectionthis notice includes violations for the areas noted.20 osceola lane common area. complaint generated routine inspection initiated by cts #201998791.
not activeNov 8, 2019security requirements sectionrepair or replace self-closing device at exterior door (706 hc)repair door closer for steel gate along la salle ave. note: this doors must remain in closed position at all times. the closer must be able to close and latch the door(s) freely and without any outside assistance.
not activeNov 4, 2019building sectionthis notice includes violations for the areas noted.20 osceola lane, unit #3
not activeNov 4, 2019fire sectionrepair egress obstruction (801,1001(l) hc)the door leading to the fire escape from the bedroom is stuck. provide a doornob for the door and repair/replace door as required for door to open and lock freely.
not activeNov 4, 2019interior surfaces sectionrepair floor covering (1001b,j,o hc)repair floors at the following locations: a) the edge on the bathroom linoleum floor is lifting. b) the edge on the carpet underneath window at bedroom leading to fire escape is lifting exposing carpet nails. c) the carpet at the kitchen transition is lifting. repair or replace and restore surface to maintain a cleanable sanitary surface and eliminate tripping hazard.
not activeNov 4, 2019plumbing and electrical sectionprovide adequate lighting (504(g), 1001 (b10) hc)repair/replace inoperable lights in bathroom.
not activeNov 4, 2019other sectioninspector commentsit is the property owner's responsibility to be present or direct his/her representative to attend the re-inspection as scheduled on this notice of violation for the purpose of providing entry to the inspector of those areas not accessed during the initial inspection as specified, and/or to provide access to all areas cited within this notice. if the property owner cannot attend the scheduled re-inspection (as specified on this notice) it is his/her responsibility to secure a different inspection date and time with the inspector. provide all tenants with notification as required by california civil code section 1954 (san francisco housing code section 303(b), if any dwellings, apartment units or guest rooms are to be accessed during the re-inspection. you can reach inspector wu @ 415-575-6844 or by email at timothy.wu@sfgov.org.
not activeNov 4, 2019interior surfaces sectionrepair damaged interior doors/handles (1001b hc)repair damaged interior door/handles at the following locations: a) the lock for the bathroom is not able to lock. repair/replace as required. b) replace deliminating bedroom door. c) re-install cabinet door in front of bathroom hallway. d) repair gaps on bedroom door moulding adjacent to bathroom.
not activeNov 4, 2019smoke detection sectionprovide smoke and carbon monoxide detectors. (911 sfhc, 907.2.11 sfbc)ensure a working smoke detectors is at each sleeping room and adjacent hallways. install according to manufacturer's specifications. ensure a working a carbon monoxide detector is at each unit and/or floor. install according to manufacturer's specifications. note: combination carbon monoxide detector-alarms and smoke detector-alarms can be used in areas that require both type detector-alarms.
not activeOct 25, 2018plumbing and electrical sectionremove stoppage in drains (1001f hc)it has been reported the drain has been clogged multiple times and created a sewage overflow onto the living room carpet. provide a report from a license contractor indicating the cause for the sewer blockage and preventative measures for future sewer blockage.
not activeOct 25, 2018interior surfaces sectionrepair floor covering (1001b,j,o hc)clean and santize or replace carpet at living room due to sewer overflow at kitchen sink. if the carpet is to be clean and sanitize, provide receipt for service.
not activeOct 25, 2018fire sectionrepair, maintain fire escape drop ladder in working condition (sec 908 hc)note: on reinspection day, property manager, owner or the owner's agent needs to demonstrate the workability of the fire escape ladders. provide a written and signed report from a qualified service company or contractor stating that all parts and cables have been tested and are functional or you are required to lower the ladder on re-inspection day to verify its proper full release. all fire escape drop ladders must be maintained and serviced annually, particularly the cable and all moving parts. lubricate and drop the ladder at least once a year.
not activeOct 25, 2018building sectionthis notice includes violations for the areas noted.20 osceola lane common area. complaint generated routine inspection initiated by cts #201801491.
not activeOct 25, 2018other sectioninspector commentsit is the property owner's responsibility to be present or direct his/her representative to attend the re-inspection as scheduled on this notice of violation for the purpose of providing entry to the inspector of those areas not accessed during the initial inspection as specified, and/or to provide access to all areas cited within this notice. if the property owner cannot attend the scheduled re-inspection (as specified on this notice) it is his/her responsibility to secure a different inspection date and time with the inspector, and provide all tenants with notification as required by california civil code section 1954 (san francisco housing code section 303(b), if any dwellings, apartment units or guest rooms are to be accessed during the re-inspection. you can reach inspector wu @ 415-575-6844 or by email at timothy.wu@sfgov.org.
not activeOct 25, 2018interior surfaces sectionrepair damaged cabinets in kitchen. 1001(b) sfhcrepair warped/damaged bottom of kitchen sink cabinet.
not activeOct 25, 2018fire sectionrecharge/date tag fire extinguisher type 2a 10bc or equivalent (905,1001(m)hc)all fire extinguishers are required to be recharged and serviced annually and service date tag must be current and posted by a qualified professional vendor. check the pressure gauge periodically as occasionally the seal may leak and the unit becomes ineffective. at the time of inspection, the tag for the fire extinguisher was expired.
not activeOct 25, 2018fire sectionremove egress obstruction (801,1001(l) hc)remove all storage/garbage at fire escape.
not activeOct 25, 2018building sectionthis notice includes violations for the areas noted.20 osceola lane, unit 3
not activeOct 25, 2018plumbing and electrical sectionprovide adequate lighting (504(g), 1001 (b10) hc)replace light bulb or repair/fix light fixture at hallway as required.
not activeOct 25, 2018smoke detection sectionprovide a minimum of one carbon monixide alarm/smoke detector per dwelling unit/apartment (907.2.11) (sfbc)ensure a working smoke detectors is at each sleeping room and adjacent hallways. install according to manufacturer's specifications. ensure a working a carbon monoxide detector is at each unit. install according to manufacturer's specifications. a combination carbon monoxide detector-alarms and smoke detector-alarms can be used in areas that require both type detector-alarms. provide an affidavit-self certification for the smoke detector & carbon monoxide alarms, see attached.
not activeOct 25, 2018other sectioninspector commentsit is the property owner's responsibility to be present or direct his/her representative to attend the re-inspection as scheduled on this notice of violation for the purpose of providing entry to the inspector of those areas not accessed during the initial inspection as specified, and/or to provide access to all areas cited within this notice. if the property owner cannot attend the scheduled re-inspection (as specified on this notice) it is his/her responsibility to secure a different inspection date and time with the inspector, and provide all tenants with notification as required by california civil code section 1954 (san francisco housing code section 303(b), if any dwellings, apartment units or guest rooms are to be accessed during the re-inspection. you can reach inspector wu @ 415-575-6844 or by email at timothy.wu@sfgov.org.
not activeOct 25, 2018security requirements sectionrepair or replace self-closing device at exterior door (706 hc)repair door latch for steel gate at the back and front entrance. note: this doors must remain in closed position at all times. the closer must be able to close and latch the door(s) freely and without any outside assistance.
not activeSep 25, 2018security requirements sectionrepair or replace self-closing device at exterior door (706 hc)repair door closer for steel gate front entrance. note: this doors must remain in closed position at all times. the closer must be able to close and latch the door(s) freely and without any outside assistance.
not activeSep 25, 2018sanitation sectionclean or sanitize (1306 hc)clean and sanitize hallways, stairs and front entry.
not activeSep 25, 2018fire sectionprovide fire extinguisher type 2a 10bc or equivalent. (905, 1001(n)hc)replace missing fire extinguisher at 2nd floor.
not activeSep 25, 2018smoke detection sectionprovide a minimum of one carbon monixide alarm/smoke detector per dwelling unit/apartment (907.2.11) (sfbc)ensure a working smoke detectors is at each sleeping room and adjacent hallways. install according to manufacturer's specifications. ensure a working a carbon monoxide detector is at each unit. install according to manufacturer's specifications. a combination carbon monoxide detector-alarms and smoke detector-alarms can be used in areas that require both type detector-alarms. provide an affidavit-self certification for the smoke detector & carbon monoxide alarms, see attached.
not activeSep 25, 2018plumbing and electrical sectionprovide adequate lighting (504(g), 1001 (b10) hc)repair/replace inoperable lights in front entry.
not activeSep 25, 2018smoke detection sectionstructural maintenance (604(a)hc)exterior wood and metal decks, balconies, fire escapes, and other building areas that are weather exposed shall be inspected by a licensed general contractor, or a structural pest control licensee, or a licensed professional architect or engineer. verify that the system is in general safe condition, and free from hazardous dry rot, fungus, or decay, or improper alteration. provide proof of compliance. submit attached 604 affidavit form.
not activeSep 25, 2018building sectionthis notice includes violations for the areas noted.90 osceola lane, common area
not activeSep 25, 2018other sectioninspector commentsit is the property owner's responsibility to be present or direct his/her representative to attend the re-inspection as scheduled on this notice of violation for the purpose of providing entry to the inspector of those areas not accessed during the initial inspection as specified, and/or to provide access to all areas cited within this notice. if the property owner cannot attend the scheduled re-inspection (as specified on this notice) it is his/her responsibility to secure a different inspection date and time with the inspector, and provide all tenants with notification as required by california civil code section 1954 (san francisco housing code section 303(b), if any dwellings, apartment units or guest rooms are to be accessed during the re-inspection.
not activeSep 20, 2018smoke detection sectionprovide smoke and carbon monoxide detectors. (911 sfhc, 907.2.11 sfbc)at the time of inspection, the smoke detector is low in battery. ensure a working smoke detectors is at each sleeping room and adjacent hallways. install according to manufacturer's specifications. ensure a working a carbon monoxide detector is at each unit and/or floor. install according to manufacturer's specifications. note: combination carbon monoxide detector-alarms and smoke detector-alarms can be used in areas that require both type detector-alarms.
not activeSep 20, 2018building sectionthis notice includes violations for the areas noted.40 osceola lane, common area
not activeSep 20, 2018other sectioninspector commentsit is the property owner's responsibility to be present or direct his/her representative to attend the re-inspection as scheduled on this notice of violation for the purpose of providing entry to the inspector of those areas not accessed during the initial inspection as specified, and/or to provide access to all areas cited within this notice. if the property owner cannot attend the scheduled re-inspection (as specified on this notice) it is his/her responsibility to secure a different inspection date and time with the inspector, and provide all tenants with notification as required by california civil code section 1954 (san francisco housing code section 303(b), if any dwellings, apartment units or guest rooms are to be accessed during the re-inspection.
not activeSep 20, 2018building sectionprovide handrails (802(c),1001(b)(13)hc)secure loose handrail at the lower stairs.
not activeSep 20, 2018plumbing and electrical sectionrepair light (1001e hc)replace missing ceiling light cover at hallway. ensure all lights work at hallway.
not activeSep 20, 2018building sectionthis notice includes violations for the areas noted.40 osceola lane, unit #1
not activeSep 20, 2018sanitation sectioneliminate rodent infestation 1001b, d, 1306 sfhceliminate rodent infestation in the unit and providing professional pest control services by a licensed pest control professional. provide written documentation of pest control services received at time of re-inspection.
not activeJul 25, 2022
building section · this notice includes violations for the areas noted.
this notice includes violations of the san francisco housing code. unless noted otherwise, all violations were observed on the date of inspection at 20 osceola ln, common areas.
not activeJul 25, 2022
other section · inspector comments
it is the property owner's responsibility to be present or direct his/her representative to attend the re-inspection as scheduled on this notice of violation for the purpose of providing entry to the inspector of those areas not accessed during the initial inspection as specified, and/or to provide access to all areas cited within this notice. if the property owner cannot attend the scheduled re-inspection (as specified on this notice) it is his/her responsibility to secure a different inspection date and time with the inspector. provide all tenants with notification as required by california civil code section 1954 (san francisco housing code section 303(b), if any dwellings, apartment units or guest rooms are to be accessed during the re-inspection. you can reach inspector chierici @ 628.652.3439 or by email at paul.chierici@sfgov.org.
not activeJul 25, 2022
plumbing and electrical section · repair ceiling light fixture (1001e hc)
ensure ceiling light fixture at front entry is secured tightly to its junction box in an approved manner.
not activeJul 25, 2022
fire section · repair fire proofing with approved materials (hc 1001 (n), 809)
repair the damaged wall at the rear second floor stairwell with approved materials: lath and 3/4" plaster or type-x drywall, to maintain its approved fire rating.
not activeJul 25, 2022
fire section · provide fire extinguisher type 2a 10bc or equivalent.(905, 1001(n)hc)
missing fire extinguisher at second level wall cabinet. provide an a approved fire extinguisher. all fire extinguishers are required to be recharged and serviced annually and service date tag must be current and posted by a qualified professional vendor. check the pressure gauge periodically as occasionally the seal may leak and the unit becomes ineffective.
not activeJul 25, 2022
security requirements section · repair gate latch (706 hc) (1001 hc)
the front security gate latch was broken and not allowing the gate to latch. the rear security gate when closed does not lock from the exterior side. repair the gates so that they self close, latch and lock without assisstance using approved materials and methods.
not activeJul 25, 2022
other section · nuisance (1001(d))
important note: due to the nature of this violation, this property has been defined as a nuisance per section 1001-d of the san francisco housing code.
not activeSep 10, 2021
other section · inspector comments
it is the property owner's responsibility to be present or direct his/her representative to attend the re-inspection as scheduled on this notice of violation for the purpose of providing entry to the inspector of those areas not accessed during the initial inspection as specified, and/or to provide access to all areas cited within this notice. if the property owner cannot attend the scheduled re-inspection (as specified on this notice) it is his/her responsibility to secure a different inspection date and time with the inspector. provide all tenants with notification as required by california civil code section 1954 (san francisco housing code section 303(b), if any dwellings, apartment units or guest rooms are to be accessed during the re-inspection. you can reach inspector chierici @ 628.652.3439 or by email at paul.chierici@sfgov.org.
not activeSep 10, 2021
building section · this notice includes violations for the areas noted.
20 osceola ln 2nd floor common area
not activeSep 10, 2021
fire section · provide fire extinguisher type 2a 10bc or equivalent.(905, 1001(n)hc)
at the time of re-inspection for another complaint, the 2nd floor stairwell fire exstinguisher was missing as seen from the la salle av. replace in kind. all fire extinguishers are required to be recharged and serviced annually and service date tag must be current and posted by a qualified professional vendor. check the pressure gauge periodically as occasionally the seal may leaks and the unit becomes ineffective.
not activeNov 8, 2019
fire section · remove egress obstruction (801,1001(l) hc)
remove all storage/trash at fire escape.
not activeNov 8, 2019
fire section · recharge/date tag fire extinguisher type 2a 10bc or equivalent (905,1001(m)hc)
all fire extinguishers are required to be recharged and serviced annually and service date tag must be current and posted by a qualified professional vendor. check the pressure gauge periodically as occasionally the seal may leak and the unit becomes ineffective.
not activeNov 8, 2019
other section · inspector comments
it is the property owner's responsibility to be present or direct his/her representative to attend the re-inspection as scheduled on this notice of violation for the purpose of providing entry to the inspector of those areas not accessed during the initial inspection as specified, and/or to provide access to all areas cited within this notice. if the property owner cannot attend the scheduled re-inspection (as specified on this notice) it is his/her responsibility to secure a different inspection date and time with the inspector. provide all tenants with notification as required by california civil code section 1954 (san francisco housing code section 303(b), if any dwellings, apartment units or guest rooms are to be accessed during the re-inspection. you can reach inspector wu @ 415-575-6844 or by email at timothy.wu@sfgov.org.
not activeNov 8, 2019
building section · this notice includes violations for the areas noted.
20 osceola lane common area. complaint generated routine inspection initiated by cts #201998791.
not activeNov 8, 2019
security requirements section · repair or replace self-closing device at exterior door (706 hc)
repair door closer for steel gate along la salle ave. note: this doors must remain in closed position at all times. the closer must be able to close and latch the door(s) freely and without any outside assistance.
not activeNov 4, 2019
building section · this notice includes violations for the areas noted.
20 osceola lane, unit #3
not activeNov 4, 2019
fire section · repair egress obstruction (801,1001(l) hc)
the door leading to the fire escape from the bedroom is stuck. provide a doornob for the door and repair/replace door as required for door to open and lock freely.
not activeNov 4, 2019
interior surfaces section · repair floor covering (1001b,j,o hc)
repair floors at the following locations: a) the edge on the bathroom linoleum floor is lifting. b) the edge on the carpet underneath window at bedroom leading to fire escape is lifting exposing carpet nails. c) the carpet at the kitchen transition is lifting. repair or replace and restore surface to maintain a cleanable sanitary surface and eliminate tripping hazard.
not activeNov 4, 2019
plumbing and electrical section · provide adequate lighting (504(g), 1001 (b10) hc)
repair/replace inoperable lights in bathroom.
not activeNov 4, 2019
other section · inspector comments
it is the property owner's responsibility to be present or direct his/her representative to attend the re-inspection as scheduled on this notice of violation for the purpose of providing entry to the inspector of those areas not accessed during the initial inspection as specified, and/or to provide access to all areas cited within this notice. if the property owner cannot attend the scheduled re-inspection (as specified on this notice) it is his/her responsibility to secure a different inspection date and time with the inspector. provide all tenants with notification as required by california civil code section 1954 (san francisco housing code section 303(b), if any dwellings, apartment units or guest rooms are to be accessed during the re-inspection. you can reach inspector wu @ 415-575-6844 or by email at timothy.wu@sfgov.org.
not activeNov 4, 2019
interior surfaces section · repair damaged interior doors/handles (1001b hc)
repair damaged interior door/handles at the following locations: a) the lock for the bathroom is not able to lock. repair/replace as required. b) replace deliminating bedroom door. c) re-install cabinet door in front of bathroom hallway. d) repair gaps on bedroom door moulding adjacent to bathroom.
not activeNov 4, 2019
smoke detection section · provide smoke and carbon monoxide detectors. (911 sfhc, 907.2.11 sfbc)
ensure a working smoke detectors is at each sleeping room and adjacent hallways. install according to manufacturer's specifications. ensure a working a carbon monoxide detector is at each unit and/or floor. install according to manufacturer's specifications. note: combination carbon monoxide detector-alarms and smoke detector-alarms can be used in areas that require both type detector-alarms.
not activeOct 25, 2018
plumbing and electrical section · remove stoppage in drains (1001f hc)
it has been reported the drain has been clogged multiple times and created a sewage overflow onto the living room carpet. provide a report from a license contractor indicating the cause for the sewer blockage and preventative measures for future sewer blockage.
not activeOct 25, 2018
interior surfaces section · repair floor covering (1001b,j,o hc)
clean and santize or replace carpet at living room due to sewer overflow at kitchen sink. if the carpet is to be clean and sanitize, provide receipt for service.
not activeOct 25, 2018
fire section · repair, maintain fire escape drop ladder in working condition (sec 908 hc)
note: on reinspection day, property manager, owner or the owner's agent needs to demonstrate the workability of the fire escape ladders. provide a written and signed report from a qualified service company or contractor stating that all parts and cables have been tested and are functional or you are required to lower the ladder on re-inspection day to verify its proper full release. all fire escape drop ladders must be maintained and serviced annually, particularly the cable and all moving parts. lubricate and drop the ladder at least once a year.
not activeOct 25, 2018
building section · this notice includes violations for the areas noted.
20 osceola lane common area. complaint generated routine inspection initiated by cts #201801491.
not activeOct 25, 2018
other section · inspector comments
it is the property owner's responsibility to be present or direct his/her representative to attend the re-inspection as scheduled on this notice of violation for the purpose of providing entry to the inspector of those areas not accessed during the initial inspection as specified, and/or to provide access to all areas cited within this notice. if the property owner cannot attend the scheduled re-inspection (as specified on this notice) it is his/her responsibility to secure a different inspection date and time with the inspector, and provide all tenants with notification as required by california civil code section 1954 (san francisco housing code section 303(b), if any dwellings, apartment units or guest rooms are to be accessed during the re-inspection. you can reach inspector wu @ 415-575-6844 or by email at timothy.wu@sfgov.org.
not activeOct 25, 2018
interior surfaces section · repair damaged cabinets in kitchen. 1001(b) sfhc
repair warped/damaged bottom of kitchen sink cabinet.
not activeOct 25, 2018
fire section · recharge/date tag fire extinguisher type 2a 10bc or equivalent (905,1001(m)hc)
all fire extinguishers are required to be recharged and serviced annually and service date tag must be current and posted by a qualified professional vendor. check the pressure gauge periodically as occasionally the seal may leak and the unit becomes ineffective. at the time of inspection, the tag for the fire extinguisher was expired.
not activeOct 25, 2018
fire section · remove egress obstruction (801,1001(l) hc)
remove all storage/garbage at fire escape.
not activeOct 25, 2018
building section · this notice includes violations for the areas noted.
20 osceola lane, unit 3
not activeOct 25, 2018
plumbing and electrical section · provide adequate lighting (504(g), 1001 (b10) hc)
replace light bulb or repair/fix light fixture at hallway as required.
not activeOct 25, 2018
smoke detection section · provide a minimum of one carbon monixide alarm/smoke detector per dwelling unit/apartment (907.2.11) (sfbc)
ensure a working smoke detectors is at each sleeping room and adjacent hallways. install according to manufacturer's specifications. ensure a working a carbon monoxide detector is at each unit. install according to manufacturer's specifications. a combination carbon monoxide detector-alarms and smoke detector-alarms can be used in areas that require both type detector-alarms. provide an affidavit-self certification for the smoke detector & carbon monoxide alarms, see attached.
not activeOct 25, 2018
other section · inspector comments
it is the property owner's responsibility to be present or direct his/her representative to attend the re-inspection as scheduled on this notice of violation for the purpose of providing entry to the inspector of those areas not accessed during the initial inspection as specified, and/or to provide access to all areas cited within this notice. if the property owner cannot attend the scheduled re-inspection (as specified on this notice) it is his/her responsibility to secure a different inspection date and time with the inspector, and provide all tenants with notification as required by california civil code section 1954 (san francisco housing code section 303(b), if any dwellings, apartment units or guest rooms are to be accessed during the re-inspection. you can reach inspector wu @ 415-575-6844 or by email at timothy.wu@sfgov.org.
not activeOct 25, 2018
security requirements section · repair or replace self-closing device at exterior door (706 hc)
repair door latch for steel gate at the back and front entrance. note: this doors must remain in closed position at all times. the closer must be able to close and latch the door(s) freely and without any outside assistance.
not activeSep 25, 2018
security requirements section · repair or replace self-closing device at exterior door (706 hc)
repair door closer for steel gate front entrance. note: this doors must remain in closed position at all times. the closer must be able to close and latch the door(s) freely and without any outside assistance.
not activeSep 25, 2018
sanitation section · clean or sanitize (1306 hc)
clean and sanitize hallways, stairs and front entry.
not activeSep 25, 2018
fire section · provide fire extinguisher type 2a 10bc or equivalent. (905, 1001(n)hc)
replace missing fire extinguisher at 2nd floor.
not activeSep 25, 2018
smoke detection section · provide a minimum of one carbon monixide alarm/smoke detector per dwelling unit/apartment (907.2.11) (sfbc)
ensure a working smoke detectors is at each sleeping room and adjacent hallways. install according to manufacturer's specifications. ensure a working a carbon monoxide detector is at each unit. install according to manufacturer's specifications. a combination carbon monoxide detector-alarms and smoke detector-alarms can be used in areas that require both type detector-alarms. provide an affidavit-self certification for the smoke detector & carbon monoxide alarms, see attached.
not activeSep 25, 2018
plumbing and electrical section · provide adequate lighting (504(g), 1001 (b10) hc)
repair/replace inoperable lights in front entry.
not activeSep 25, 2018
smoke detection section · structural maintenance (604(a)hc)
exterior wood and metal decks, balconies, fire escapes, and other building areas that are weather exposed shall be inspected by a licensed general contractor, or a structural pest control licensee, or a licensed professional architect or engineer. verify that the system is in general safe condition, and free from hazardous dry rot, fungus, or decay, or improper alteration. provide proof of compliance. submit attached 604 affidavit form.
not activeSep 25, 2018
building section · this notice includes violations for the areas noted.
90 osceola lane, common area
not activeSep 25, 2018
other section · inspector comments
it is the property owner's responsibility to be present or direct his/her representative to attend the re-inspection as scheduled on this notice of violation for the purpose of providing entry to the inspector of those areas not accessed during the initial inspection as specified, and/or to provide access to all areas cited within this notice. if the property owner cannot attend the scheduled re-inspection (as specified on this notice) it is his/her responsibility to secure a different inspection date and time with the inspector, and provide all tenants with notification as required by california civil code section 1954 (san francisco housing code section 303(b), if any dwellings, apartment units or guest rooms are to be accessed during the re-inspection.
not activeSep 20, 2018
smoke detection section · provide smoke and carbon monoxide detectors. (911 sfhc, 907.2.11 sfbc)
at the time of inspection, the smoke detector is low in battery. ensure a working smoke detectors is at each sleeping room and adjacent hallways. install according to manufacturer's specifications. ensure a working a carbon monoxide detector is at each unit and/or floor. install according to manufacturer's specifications. note: combination carbon monoxide detector-alarms and smoke detector-alarms can be used in areas that require both type detector-alarms.
not activeSep 20, 2018
building section · this notice includes violations for the areas noted.
40 osceola lane, common area
not activeSep 20, 2018
other section · inspector comments
it is the property owner's responsibility to be present or direct his/her representative to attend the re-inspection as scheduled on this notice of violation for the purpose of providing entry to the inspector of those areas not accessed during the initial inspection as specified, and/or to provide access to all areas cited within this notice. if the property owner cannot attend the scheduled re-inspection (as specified on this notice) it is his/her responsibility to secure a different inspection date and time with the inspector, and provide all tenants with notification as required by california civil code section 1954 (san francisco housing code section 303(b), if any dwellings, apartment units or guest rooms are to be accessed during the re-inspection.
not activeSep 20, 2018
building section · provide handrails (802(c),1001(b)(13)hc)
secure loose handrail at the lower stairs.
not activeSep 20, 2018
plumbing and electrical section · repair light (1001e hc)
replace missing ceiling light cover at hallway. ensure all lights work at hallway.
not activeSep 20, 2018
building section · this notice includes violations for the areas noted.
40 osceola lane, unit #1
not activeSep 20, 2018
sanitation section · eliminate rodent infestation 1001b, d, 1306 sfhc
eliminate rodent infestation in the unit and providing professional pest control services by a licensed pest control professional. provide written documentation of pest control services received at time of re-inspection.