not activeApr 28, 2009
other section · inspector comments
if the property owner cannot attend the scheduled reinspection (as specified on this notice) it is his/her responsibility to secure a different inspection date and time with the inspector, and provide all tenants with notification as required by california civil code section 1954 (san francisco housing code section 303(b), if any dwellings, apartment units or guest rooms are to be accessed during the reinspection.
not activeApr 14, 2009
Electrical
YOU FAILED TO COMPLY WITH NOTICE OF VIOLATION DATED 7/22/2010, STATING ELECTRICAL WORK WITHOUT BENEFIT OF AN ELECTRICAL PERMIT. NEW ELECTRICAL PANEL MANAGERS OFFICE 2ND FLOOR, SFEC 90.123 (C) AND FAILURE TO COMPLETE ELECTRICAL PERMIT #EW20100806702. THEREFORE THIS DEPARTMENT HAS INITIATED ABATEMENT PROCEEDING AGAINST THE PROPERTY.
not activeApr 14, 2009
Electrical
Electrical work without benefit of an electrical permit. New electrical panel managers office 2nd floor, SFEC 89.123(C).
not activeDec 23, 2008
building section · this notice includes violations for the areas noted.
complaint inspection at 3161 16th street - 16th street hotel regarding general maintenance items:
not activeDec 23, 2008
building section · you are required to correct the following on 3rd floor:
at third floor: 1. eliminate mold/mildew on shower room ceiling (1001b(13), 1002, 1301 hc) next to room #304: use approved mildewcide to eradicate mold/mildew infestation. prime and paint as necessary. clean or replace moldy shower curtain. 2. reinstall missing light bulbs from all public toilets and shower rooms. (1001 hc) use some secure means to prevent theft and the ongoing removal of light bulbs from public areas.
not activeDec 23, 2008
building section · you are required to correct the following on 5th floor:
at fifth floor: 1. remove unapproved cord wiring at 5th floor's public hallway (1001 hc) remove the extension cord supplying power from across the hallway into room #502. the subject cord is running through the door jamb. eliminate this hazardous condition and restore the power into room #501 from within. 2. repair/replace door closer at garbage room door (807,707 hc) the closer must be able to close and latch the door freely and without any outside assistance. 3. provide minimum 135 degree viewer for entry door of room #512 (max mounting ht of 58") (706 hc) san francisco security ordinance requires that all building numbers be posted and visible at the exterior and all individual unit numbers be posted at unit/apartment entry doors. each unit entry door must have a door viewer mounted at 57" - 58" from the floor.
not activeDec 23, 2008
building section · general requirements at public and common areas:
1. clean or sanitize area around garbage receptacles (904, 1001, 1307 hc) perform regular and periodic cleaning at all garbage rooms on all levels. 2. clean and vacuum carpeting in all public areas (904, 1001, 1307 hc) perform regular and periodic cleaning at all public areas. 3. safety observation at shower room: excessive water spillage was observed outside the shower stalls that can create a hazardous and slippery condition. monitor and take the necessary steps to minimize this condition on a daily basis.
not activeDec 23, 2008
other section · inspector comments regarding "follow up" reinspection:
i have scheduled a reinspection of your building on thursday, 08-january-2008 at 10:00 am. reinspection of premise to include all areas referenced above. please contact housing inspector tim mansur at (415) 558-6514 if you have any questions, want to reschedule or confirm the time or day of reinspection. your cooperation is appreciated.
not activeOct 31, 2008
building section · this notice includes violations for the areas noted.
mailbox legislation field survey at 16th street hotel - 3161 16th street. the ground floor appears to have sufficient room for the required us post office approved mail receptacles for all certified residential guest rooms only.
not activeOct 31, 2008
building section · provide an individual mail receptacle for each residential unit (1002(e) sfhc & section 41e of the san francisco administrative code)
hotel owner is responsible for making arrangements with the united states postal services for the installation of these receptacles (mail boxes) and delivery of mail thereto. installation and maintenance of the mail receptacles shall meet all of the specifications and requirements of the united states postal services. note: compliance with united states postal services specifications and requirements, and delivery of mail by the united postal services, will not be enforced by the department of building inspection. these requirements do not apply to tourist rooms.
not activeOct 31, 2008
other section · inspector comments regarding "follow up" reinspection:
i have scheduled a reinspection of your building on tuesday, 05-january-2009 at 12:30 p.m. reinspection of premise to include all areas referenced above. please contact housing inspector tim mansur at (415) 558-6514 if you have any questions, need a time extension, want to reschedule or confirm the time or day of reinspection. your cooperation is appreciated.
not activeJan 9, 2008
building section · this notice includes violations for the areas noted.
complaint inspection regarding lack of heat at the entire hotel in the mornings. heat comes on at night.
not activeJan 9, 2008
building section · set time clock to provide the required amount and hours of heat. (701c hc)
provide heat for 13 hours between 5:00 a.m. and 11:00 a.m. and between 3:00 p.m. and 10:00 p.m. capable to maintaining a minimum room temperature of 68 degrees. (701c hc)
not activeJan 9, 2008
other section · inspector comments regarding "follow up" reinspection:
i have scheduled a reinspection of your building on friday, 11-january-2008 at 10:00 am. reinspection of premise to include boiler room and time clock. your cooperation is appreciated.
not activeNov 8, 2007
building section · this notice includes violations for the areas noted.
routine safety inspection of public and common areas at 3161 16th street. chapters 1, 2, & 3 of the san francisco housing code require that the department of building inspection perform periodic health & safety inspections of residential property. this routine inspection was conducted to assure that all requirements have been met per attached routine inspection checklist.
not activeNov 8, 2007
fire section · repair or replace malfunctioning emergency exit lights in public hallways / stairs (504, 1001 hc)
have the emergency lights tested annually and replace any malfunctioning units or expired backup batteries as required.
not activeNov 8, 2007
smoke detection section · provide battery operated smoke detector at top of each enclosed stairs / by roof access (909, 911 hc)
a battery operated smoke detector is required at the top of each enclosed stairs / penthouse area. test smoke detectors on a regular basis and replace all batteries annually to maintain a working and functional device.
not activeNov 8, 2007
fire section · remove egress obstruction at top landind / by roof access (801,1001(l) hc)
remove abandoned tv and items from the public stairs.
not activeNov 8, 2007
fire section · maintain fire escape drop ladder in working condition (sec 908 hc)
lubricate and drop the ladder at least once a year.
not activeNov 8, 2007
fire section · remove all (i bolts) and any other pad locking devices from outside of room entry doors (707, 807 hc)
at entry door to rooms 315, 503, 505 & 505. check all security locks assembly and repair as required.
not activeNov 8, 2007
plumbing and electrical section · remove cord wiring / extension cords from public hallways (1001-e hc)
remove extension cord going through door jambs into receptacle in public hallway. at rooms 309 and 409.
not activeNov 8, 2007
interior surfaces section · clean and sanitize carpeting at interior / public hallways (1306 hc)
shampoo / vacuum carpeting on a regular basis. burned spots was noticed on the fourth floors. advise smokers not to through cigarette buts on the floor.
not activeNov 8, 2007
sanitation section · clean and sanitize garbage rooms daily (1306 hc)
on all floors. cockroach infestation was noted in garbage room at the third floor. provide routine and systematic pest control services until the infestation is eliminated.
not activeNov 8, 2007
interior surfaces section · repair damaged wall in public hallway (1001b,h,o hc)
patch and repair wall near room 405.
not activeNov 8, 2007
other section · inspector comments regarding "follow up" reinspection:
i have scheduled a reinspection of your building on monday, 10-december-2007 at 01:00 pm. reinspection of premise to include all areas referenced above. please contact housing inspector tim mansur at (415) 558-6514 if you have any questions, want to reschedule or confirm the time or day of reinspection. your cooperation is appreciated.
not activeJul 23, 2007
building section · this notice includes violations for the areas noted.
all work is in reference to room #302.
not activeJul 23, 2007
plumbing and electrical section · clean interior (1306 hc)
clean/sanitze carpet in #302.
not activeJul 23, 2007
plumbing and electrical section · repair sink (1001f hc)
repair or replace damaged sink in room #302.
not activeJul 23, 2007
other section · inspector comments
it is the property owner's responsibility to be present or direct his/her representative to attend, the reinspection as scheduled on this notice of violation for the purpose of providing entry to the inspector of those areas not accessed during the initial inspection as specified, and/or to provide access to all areas cited within this notice.
not activeJul 23, 2007
other section · inspector comments
if the property owner cannot attend the scheduled reinspection (as specified on this notice) it is his/her responsibility to secure a different inspection date and time with the inspector, and provide all tenants with notification as required by california civil code section 1954 (san francisco housing code section 303(b), if any dwellings, apartment units or guest rooms are to be accessed during the reinspection.
not activeMay 15, 2007
building section · this notice includes violations for the areas noted.
3161 16th street, unit #317.
not activeMay 15, 2007
security requirements section · provide single cylinder deadbolt locks with a minimum 1" throw for entry doors of unit #317. (706 hc)
repair defective and inoperable, non-locking device at entry door of unit #317. condition is unsafe and presents a security concern to all occupants.
not activeMay 15, 2007
fire section · repair smoke enclosure door (807 707 hc)
repair smoke enclosure entry door of unit #317. at time of inspection, framing, threshold and hinges were defective and in disrepair and require complete repair or replacement.
not activeMay 15, 2007
smoke detection section · replace smoke detector (908, 911 hc)
replace inoperable smoke detector positioned at ceiling of unit #317.
not activeMay 15, 2007
plumbing and electrical section · repair electrical outlet (1001e hc)
at time of inspection, it was observed that hanging light fixture from ceiling of unit #317 hung dangerously low and posed a hazard to occupant at its' current mid-level room position above sleeping area of unit. please repair or replace lighting fixture by securing fixture to top area of ceiling.
not activeMay 15, 2007
other section · inspector comments
it is the property owner's responsibility to be present or direct his/her representative to attend, the reinspection as scheduled on this notice of violation for the purpose of providing entry to the inspector of those areas not accessed during the initial inspection as specified, and/or to provide access to all areas cited within this notice. if the property owner cannot attend the scheduled reinspection (as specified on this notice) it is his/her responsibility to secure a different inspection date and time with the inspector, and provide all tenants with notification as required by california civil code section 1954 (san francisco housing code section 303(b), if any dwellings, apartment units or guest rooms are to be accessed during the reinspection. housing inspector richard marquez can be contacted between the hours of 8:00am to 9:00am and 4:00pm to 5:00pm, at 415/558-6211.
not activeMay 3, 2007
building section · this notice includes violations for the areas noted.
3161 16th street & common areas.
not activeMay 3, 2007
plumbing and electrical section · make necessary repairs to tub/shower (1001 hc)
repair defective and loose faucet handles for tubs on second and third floors of occupancy.
not activeMay 3, 2007
sanitation section · clean or sanitize (1306 hc)
clean and sanitize all carpeting of interior areas on all floors of occupancy, including interior stairways.
not activeMay 3, 2007
other section · inspector comments
it is the property owner's responsibility to be present or direct his/her representative to attend, the reinspection as scheduled on this notice of violation for the purpose of providing entry to the inspector of those areas not accessed during the initial inspection as specified, and/or to provide access to all areas cited within this notice. if the property owner cannot attend the scheduled reinspection (as specified on this notice) it is his/her responsibility to secure a different inspection date and time with the inspector, and provide all tenants with notification as required by california civil code section 1954 (san francisco housing code section 303(b), if any dwellings, apartment units or guest rooms are to be accessed during the reinspection. housing inspector richard marquez can be contacted between the hours of 8:00am to 9:00am and 4:00pm to 5:00pm, at 415/558-6211.
not activeMay 3, 2007
building section · this notice includes violations for the areas noted.
3161 16th street, unit #500.
not activeMay 3, 2007
other section · inspector comments
it is the property owner's responsibility to be present or direct his/her representative to attend, the reinspection as scheduled on this notice of violation for the purpose of providing entry to the inspector of those areas not accessed during the initial inspection as specified, and/or to provide access to all areas cited within this notice. if the property owner cannot attend the scheduled reinspection (as specified on this notice) it is his/her responsibility to secure a different inspection date and time with the inspector, and provide all tenants with notification as required by california civil code section 1954 (san francisco housing code section 303(b), if any dwellings, apartment units or guest rooms are to be accessed during the reinspection. housing inspector richard marquez can be contacted between the hours of 8:00am to 9:00am and 4:00pm to 5:00pm, at 415/558-6211.
not activeMay 3, 2007
plumbing and electrical section · repair sink (1001f hc)
repair defective and detaching faucet from sink in unit #500.
not activeMay 3, 2007
fire section · repair smoke enclosure door (807, 707 hc)
front entry door: wood deterioration was noted around door frame, door jamb, header & threshold; door frame and door would not effectively close and properly open, causing a security ordinance violation. repair/replace as required. after repairs, door should be tight-fitting, in good condition, and open & close easily; and all exterior locking devices on entry door should properly lock, providing security for occupants.
not activeMay 3, 2007
building section · this notice includes violations for the areas noted.
3161 16th street, unit #500.
not activeMay 3, 2007
plumbing and electrical section · repair sink (1001f hc)
repair detaching and defective faucet from sink in unit #500.
not activeMay 3, 2007
fire section · repair smoke enclosure door (807 707 hc)
repair or replace damaged entry door to unit #500. at time of inspection, it was observed that entry door did not properly lock, close or open; door jamb, door frame, header and threshold were all defective and require repair in order for door to effectively lock, securing safety for all occupants. moreover, door had a more than 1/2 inch gap at the top of door frame. please make door tight-fitting upon repair or replacement, disallowing air and moisture penetration into unit.
not activeMay 3, 2007
other section · inspector comments
it is the property owner's responsibility to be present or direct his/her representative to attend, the reinspection as scheduled on this notice of violation for the purpose of providing entry to the inspector of those areas not accessed during the initial inspection as specified, and/or to provide access to all areas cited within this notice. if the property owner cannot attend the scheduled reinspection (as specified on this notice) it is his/her responsibility to secure a different inspection date and time with the inspector, and provide all tenants with notification as required by california civil code section 1954 (san francisco housing code section 303(b), if any dwellings, apartment units or guest rooms are to be accessed during the reinspection. housing inspector richard marquez can be contacted between the hours of 8:00am to 9:00am and 4:00pm to 5:00pm, at 415/558-6211.
not activeApr 8, 2007
building section · this notice includes violations for the areas noted.
3161 16th street (sixteeth street hotel), unit #311.
not activeApr 8, 2007
plumbing and electrical section · repair sink (1001f hc)
repair leaking faucet and drainage at unit's sink.