2238 VICENTE ST

Sunset/Parkside · San Francisco, CA · Parcel 2434022 · Last violation Dec 27, 2024 · Last complaint Jul 25, 2026

NeighborhoodSunset/Parkside
More violations than 99% of nearby buildings
More violations than 99% of buildings and more complaints than 99% of buildings in Sunset/Parkside. Size-normalized against residential buildings in the neighborhood.
ViolationsComplaints
Activity TrendsLast 5 years
A steady level of activity over time
Last 2 yrs: 20 violations · 15 complaints
'22'26ViolationsComplaints
Severityⓘopen violations
29 open DBI violations
Active Notices of Violation issued by the Department of Building Inspection.
Severe0
Serious27
Minor2

What to watch forⓘ

  1. Fire safety problems have been reported here.
    Worth checkingⓘ
    Walk the exit route from the unit to the street and check the stairs and hallways are clear of stored items, and that fire doors close properly.
    details ▸

    California law requires safe fire or emergency exits leading to a street or hallway, and requires stairs, hallways and exits to be kept litter free. Storage areas, garages and basements must be kept free of combustible materials. San Francisco's Housing Code separately treats inadequate exits and inadequate fire protection equipment as conditions that make a building substandard, which is the finding behind a notice of violation.

    • California Tenant Guide
    • San Francisco Housing Code §1001(m), (n)
  2. Tenants here have reported no heat or no hot water.
    details ▸

    California law requires heating facilities in good working order, and plumbing facilities in good working order including hot and cold running water. A rental unit that substantially lacks either may be legally uninhabitable, which is the standard the implied warranty of habitability sets for every residential tenancy in the state.

311 Housing Complaints
Total complaints since 2022
18
4 per year avg.↑ Up 400% in the last 2 years (15 vs 3 prior 2 yrs)
Complaint severity
Last 5 years
18
Severeⓘ3
Seriousⓘ9
Minorⓘ6
Dept. of Building Inspection Violations
Total violations since 2001
88
3 per year avg.↑ Up 122% in the last 2 years (20 vs 9 prior 2 yrs)
Open violations
29
Severeⓘ0
Seriousⓘ27
Minorⓘ2

Top violation categories

5 yrsAll time
Plumbingⓘ6 violations
Exterior & windowsⓘ3 violations
Cleanliness & refuseⓘ3 violations
Floors & stairsⓘ1 violations
Electricalⓘ1 violations
Fire safetyⓘ1 violations
Ventilation & lightⓘ1 violations
Heat / hot waterⓘ1 violations
No specific condition stated12 violations
12 still open. See violation log below.

Top complaint types

5 yrsAll time
Mold And Mildew5 complaints
General Maintenance Not In List Above5 complaints
Electrical Hazardous Condition3 complaints
Plumbing Broken Leaking2 complaints
Infestation Rodent Insect1 complaints
Bathroom1 complaints
Paint Peeling1 complaints
Hide violations (88) ↑See complaints (18) →

Violation log

88 DBI violations

AllOpenClosed
StatusFiledCategoryItemNOV Item Description
not activeApr 19, 2012other sectionmiscellaneous violationscomplainant reported that water does not stay in the bathtub because the stopper does not work properly. please check and repair/replace as necessary.
See something wrong? File a complaint with SF 311

Ask how heat and hot water are supplied and who pays for them. If either fails once you live here, put the request to the landlord in writing and keep a copy.

  • California Tenant Guide
  • San Francisco Housing Code §701
  • Tenants here have reported mold.
    Worth checkingⓘ
    Look for dark spots on walls, floors and ceilings, and for dry or wet spots, flaking or bubbling, or a damp or moldy smell, especially in bathrooms and closets.
    details ▸

    San Francisco's Health Code treats visible or otherwise demonstrable mold or mildew in a residential building as a public health nuisance in its own right. Under state law, mold that the landlord has notice of and that affects livability or health can also breach the implied warranty of habitability.

    • California Tenant Guide
    • San Francisco Health Code §581(b)(6)
  • not activeApr 19, 2012other sectionimportant note: this property is defined as a nuisance per sec. 1001-d of the sfhc. please review the attached "notice of violation warnings" for information regarding failure to comply with this notice.it is the property owner's responsibility to be present or direct his/her representative to attend, the reinspection as scheduled on this notice of violation for the purpose of providing entry to the inspector of those areas not accessed during the initial inspection as specified, and/or to provide access to all areas cited within this notice. if the property owner cannot attend the scheduled reinspection (as specified on this notice) it is his/her responsibility to secure a different inspection date and time with the inspector, and provide all tenants with notification as required by california civil code section 1954 (san francisco housing code section 303(b)), if any dwellings, apartment units or guest rooms are to be accessed during the reinspection.
    not activeMar 7, 2012building sectionthis notice includes violations for the areas noted.2238 vicente street, unit #3 and common areas.
    not activeMar 7, 2012building sectionreplace broken glass window pane (1001(h),708 hc)at lightwell -unit #2.
    not activeMar 7, 2012building sectionprovide handrails (802(c),1001(b)(13)hc)at rear stairs to upper yard.
    not activeMar 7, 2012sanitation sectionclean and maintain (1306 hc)all common areas of the building, including parking garage, storage room, floor under rear stairs and passage way to the rear yard.
    not activeMar 7, 2012plumbing and electrical sectioncheck garage drainage pipes (1001f hc)complainant said that garage floor drain drains slowly, please check and repair as necessary.
    not activeMar 7, 2012plumbing and electrical sectionrepair sink (1001f hc)repair/replace unit #3's kitchen sink drain -not cleanable.
    not activeMar 7, 2012interior surfaces sectionrepair damaged ceilings (1001b,h,o hc)unit #3's bathroom.
    not activeMar 7, 2012interior surfaces sectionrepair damaged walls (1001b,h,o hc)unit #3, entry hallway, bathroom, kitchen and bedroom wall -under windows. remove peeling paint from bathroom door.
    not activeMar 7, 2012interior surfaces sectionrepair source of water damage (703,1001f hc)unit #3, weather-proof bedroom windows.
    not activeMar 7, 2012interior surfaces sectionpaint ceilings (1001b,1301 hc)after repairs are complete.
    not activeMar 7, 2012interior surfaces sectionpaint walls (1001b,1301 hc)after repairs are complete.
    not activeMar 7, 2012interior surfaces sectionother interior violationsrepair/replace unit #3's bathroom door lock.
    not activeMar 7, 2012plumbing and electrical sectionrepair lights (1001e hc)unit #3: replace missing cover of kitchen and bedroom ceiling lights. check bedroom ceiling light fixture and repair/replace as necessary. replace light at kitchen hood.
    not activeMar 7, 2012other sectionimportant note: this property is defined as a nuisance per sec. 1001-d of the sfhc. please review the attached "notice of violation warnings" for information regarding failure to comply with this notice.it is the property owner's responsibility to be present or direct his/her representative to attend, the reinspection as scheduled on this notice of violation for the purpose of providing entry to the inspector of those areas not accessed during the initial inspection as specified, and/or to provide access to all areas cited within this notice. if the property owner cannot attend the scheduled reinspection (as specified on this notice) it is his/her responsibility to secure a different inspection date and time with the inspector, and provide all tenants with notification as required by california civil code section 1954 (san francisco housing code section 303(b)), if any dwellings, apartment units or guest rooms are to be accessed during the reinspection.
    not activeJan 3, 2011building sectionthis notice includes violations for the areas noted.2238 vicente street, common areas.
    not activeJan 3, 2011fire sectionrecharge all fire extinguishers (905, 1001(m) hc)all fire extinguishers are required to be recharged and serviced annually and date tag must be posted and current. check the pressure gauge periodically as occasionally the seal may leak and the unit becomes ineffective. make sure that the date tag and pressure gauge are visible through the clear glass in locked cabinets.
    not activeJan 3, 2011building sectionrepair stairs (1001(b)(13)hc)rear stairs and decks: wood deterioration / decay was noted on structural components, including treads, steps, stringers and joists. some handrails, guardrails were either loose and/or insecure. repair or replace these areas as required to maintain a safe and sound structure. note: building permit is required to do this repairs.
    not activeJan 3, 2011building sectionbuilding permit required (301 hc) no structural/architectural plans are required for work less than 50%. for total replacement of stairs or deck or work over 50% of existing structure, then you must submit two sets of floor plans along with a copy of this notice with a building permit application.to repair stairs.
    not activeJan 3, 2011fire sectioninstall directional exit signs at (801, 1001(m) hc)basement.
    not activeJan 3, 2011fire sectionpermanently remove combustible storage or provide automatic fire sprinklers. (904, 1001(i) hc)basement storage room.
    not activeJan 3, 2011other sectionthis property is defined as a nuisance per sec. 1001-d of the sfhc.it is the property owner's responsibility to be present or direct his/her representative to attend, the reinspection as scheduled on this notice of violation for the purpose of providing entry to the inspector of those areas not accessed during the initial inspection as specified, and/or to provide access to all areas cited within this notice. if the property owner cannot attend the scheduled reinspection (as specified on this notice) it is his/her responsibility to secure a different inspection date and time with the inspector, and provide all tenants with notification as required by california civil code section 1954 (san francisco housing code section 303(b)), if any dwellings, apartment units or guest rooms are to be accessed during the reinspection.
    not activeNov 8, 2007building sectionthis notice includes violations for the areas noted.2238 vicente st. *routine inspection of the (common area) building sec.(303 a s.f.h.c.)
    not activeNov 8, 2007plumbing and electrical sectionother plumbing violationsecure missing hot water heater's single wall exhaust vent with (3) # 8 sheet metal screw for each pipe/fitting connections and the draft hoods
    not activeNov 8, 2007security requirements sectionremove egress obstruction(801) and (1001)hcrear stair ground floor exit door **life safety violation** remove currently installed barrel(slide) bolt locking device. in an emergency situation, evacuees must be able to exit the premises and open the door without any knowledge or struggle.
    not activeNov 8, 2007building sectionother building violationsrear stair: remove existing ladder to the roof.(no landing at the bottom of the ladder) obtain a building permit if roof ladder is to be relocated.
    not activeNov 8, 2007building sectionbuilding permit required (301 hc)for the relocating roof ladder when all work is complete the building inspector must inspect and sign the final inspection job card before the housing inspector can abate this violation. please present the signed job card indicating that work is complete to the housing inspector at reinspection day. note: before starting work the district building inspector must be notify.
    not activeNov 8, 2007building sectionprovide ventilation for garage (1001b(8) hc)louver/screen at the bottom section of the garage door
    not activeNov 8, 2007other sectioninspector commentsit is the property owner's responsibility to be present or direct his/her representative to attend, the reinspection as schedule on this notice of violation for the purpose of providing entry to the inspector of those areas not accessed during the initial inspection as specified, and/or to provide access to all areas cited within this notice. if the property owner cannot attend the scheduled reinspection (as specified on this notice) it is his/her responsibility to secure a different inspection date and time with the inspector, and provide all tenants with the inspector, and provide all tenants with notification as required by california civil code section 1954(san francisco housing code section 303(b),if any dwellings, apartment units or guest rooms are to be accessed during the reinspection.
    not activeNov 8, 2007other sectionprovide shutoff tool for gas utility shutoff (712 hc)install shut off tool in a visible and accessible location and adjacent to main gas valve.make sure that the type/size of the tool fits the existing valve(s)
    not activeNov 8, 2007other sectionpost enclosed gas meter instructional diagram in a public area. (712 hc)post gas diagram in a visible location so tenants are aware of emergency gas shut off procedures.
    not activeJan 5, 2001building sectionrepair damaged walls (1001b,h,o hc)complete patching wall where new alarm system has been installed
    not activeJan 5, 2001security requirements sectionprovide self-closing devices at exterior doors / gate (706 hc)provide automatic closing device at front gate for security purpose
    not activeJan 5, 2001other sectionprovide shutoff tool for gas utility shutoff (712 hc)—
    not activeJan 5, 2001other sectionpost enclosed gas meter instructional diagram in a public area. (712 hc)—
    not activeJan 5, 2001fire sectionpermanently remove combustible storage or provide automatic fire sprinklers. (904, 1001(i) hc)remove all stored items from underneath interior main stair case
    not activeJan 5, 2001fire sectionpermanently remove combustible storage. (904, 1001(i) hc)remove all stored items from underneath exterior fire escape stairs.
    not activeApr 19, 2012
    other section · miscellaneous violations
    complainant reported that water does not stay in the bathtub because the stopper does not work properly. please check and repair/replace as necessary.
    not activeApr 19, 2012
    other section · important note: this property is defined as a nuisance per sec. 1001-d of the sfhc. please review the attached "notice of violation warnings" for information regarding failure to comply with this notice.
    it is the property owner's responsibility to be present or direct his/her representative to attend, the reinspection as scheduled on this notice of violation for the purpose of providing entry to the inspector of those areas not accessed during the initial inspection as specified, and/or to provide access to all areas cited within this notice. if the property owner cannot attend the scheduled reinspection (as specified on this notice) it is his/her responsibility to secure a different inspection date and time with the inspector, and provide all tenants with notification as required by california civil code section 1954 (san francisco housing code section 303(b)), if any dwellings, apartment units or guest rooms are to be accessed during the reinspection.
    not activeMar 7, 2012
    building section · this notice includes violations for the areas noted.
    2238 vicente street, unit #3 and common areas.
    not activeMar 7, 2012
    building section · replace broken glass window pane (1001(h),708 hc)
    at lightwell -unit #2.
    not activeMar 7, 2012
    building section · provide handrails (802(c),1001(b)(13)hc)
    at rear stairs to upper yard.
    not activeMar 7, 2012
    sanitation section · clean and maintain (1306 hc)
    all common areas of the building, including parking garage, storage room, floor under rear stairs and passage way to the rear yard.
    not activeMar 7, 2012
    plumbing and electrical section · check garage drainage pipes (1001f hc)
    complainant said that garage floor drain drains slowly, please check and repair as necessary.
    not activeMar 7, 2012
    plumbing and electrical section · repair sink (1001f hc)
    repair/replace unit #3's kitchen sink drain -not cleanable.
    not activeMar 7, 2012
    interior surfaces section · repair damaged ceilings (1001b,h,o hc)
    unit #3's bathroom.
    not activeMar 7, 2012
    interior surfaces section · repair damaged walls (1001b,h,o hc)
    unit #3, entry hallway, bathroom, kitchen and bedroom wall -under windows. remove peeling paint from bathroom door.
    not activeMar 7, 2012
    interior surfaces section · repair source of water damage (703,1001f hc)
    unit #3, weather-proof bedroom windows.
    not activeMar 7, 2012
    interior surfaces section · paint ceilings (1001b,1301 hc)
    after repairs are complete.
    not activeMar 7, 2012
    interior surfaces section · paint walls (1001b,1301 hc)
    after repairs are complete.
    not activeMar 7, 2012
    interior surfaces section · other interior violations
    repair/replace unit #3's bathroom door lock.
    not activeMar 7, 2012
    plumbing and electrical section · repair lights (1001e hc)
    unit #3: replace missing cover of kitchen and bedroom ceiling lights. check bedroom ceiling light fixture and repair/replace as necessary. replace light at kitchen hood.
    not activeMar 7, 2012
    other section · important note: this property is defined as a nuisance per sec. 1001-d of the sfhc. please review the attached "notice of violation warnings" for information regarding failure to comply with this notice.
    it is the property owner's responsibility to be present or direct his/her representative to attend, the reinspection as scheduled on this notice of violation for the purpose of providing entry to the inspector of those areas not accessed during the initial inspection as specified, and/or to provide access to all areas cited within this notice. if the property owner cannot attend the scheduled reinspection (as specified on this notice) it is his/her responsibility to secure a different inspection date and time with the inspector, and provide all tenants with notification as required by california civil code section 1954 (san francisco housing code section 303(b)), if any dwellings, apartment units or guest rooms are to be accessed during the reinspection.
    not activeJan 3, 2011
    building section · this notice includes violations for the areas noted.
    2238 vicente street, common areas.
    not activeJan 3, 2011
    fire section · recharge all fire extinguishers (905, 1001(m) hc)
    all fire extinguishers are required to be recharged and serviced annually and date tag must be posted and current. check the pressure gauge periodically as occasionally the seal may leak and the unit becomes ineffective. make sure that the date tag and pressure gauge are visible through the clear glass in locked cabinets.
    not activeJan 3, 2011
    building section · repair stairs (1001(b)(13)hc)
    rear stairs and decks: wood deterioration / decay was noted on structural components, including treads, steps, stringers and joists. some handrails, guardrails were either loose and/or insecure. repair or replace these areas as required to maintain a safe and sound structure. note: building permit is required to do this repairs.
    not activeJan 3, 2011
    building section · building permit required (301 hc) no structural/architectural plans are required for work less than 50%. for total replacement of stairs or deck or work over 50% of existing structure, then you must submit two sets of floor plans along with a copy of this notice with a building permit application.
    to repair stairs.
    not activeJan 3, 2011
    fire section · install directional exit signs at (801, 1001(m) hc)
    basement.
    not activeJan 3, 2011
    fire section · permanently remove combustible storage or provide automatic fire sprinklers. (904, 1001(i) hc)
    basement storage room.
    not activeJan 3, 2011
    other section · this property is defined as a nuisance per sec. 1001-d of the sfhc.
    it is the property owner's responsibility to be present or direct his/her representative to attend, the reinspection as scheduled on this notice of violation for the purpose of providing entry to the inspector of those areas not accessed during the initial inspection as specified, and/or to provide access to all areas cited within this notice. if the property owner cannot attend the scheduled reinspection (as specified on this notice) it is his/her responsibility to secure a different inspection date and time with the inspector, and provide all tenants with notification as required by california civil code section 1954 (san francisco housing code section 303(b)), if any dwellings, apartment units or guest rooms are to be accessed during the reinspection.
    not activeNov 8, 2007
    building section · this notice includes violations for the areas noted.
    2238 vicente st. *routine inspection of the (common area) building sec.(303 a s.f.h.c.)
    not activeNov 8, 2007
    plumbing and electrical section · other plumbing violation
    secure missing hot water heater's single wall exhaust vent with (3) # 8 sheet metal screw for each pipe/fitting connections and the draft hoods
    not activeNov 8, 2007
    security requirements section · remove egress obstruction(801) and (1001)hc
    rear stair ground floor exit door **life safety violation** remove currently installed barrel(slide) bolt locking device. in an emergency situation, evacuees must be able to exit the premises and open the door without any knowledge or struggle.
    not activeNov 8, 2007
    building section · other building violations
    rear stair: remove existing ladder to the roof.(no landing at the bottom of the ladder) obtain a building permit if roof ladder is to be relocated.
    not activeNov 8, 2007
    building section · building permit required (301 hc)
    for the relocating roof ladder when all work is complete the building inspector must inspect and sign the final inspection job card before the housing inspector can abate this violation. please present the signed job card indicating that work is complete to the housing inspector at reinspection day. note: before starting work the district building inspector must be notify.
    not activeNov 8, 2007
    building section · provide ventilation for garage (1001b(8) hc)
    louver/screen at the bottom section of the garage door
    not activeNov 8, 2007
    other section · inspector comments
    it is the property owner's responsibility to be present or direct his/her representative to attend, the reinspection as schedule on this notice of violation for the purpose of providing entry to the inspector of those areas not accessed during the initial inspection as specified, and/or to provide access to all areas cited within this notice. if the property owner cannot attend the scheduled reinspection (as specified on this notice) it is his/her responsibility to secure a different inspection date and time with the inspector, and provide all tenants with the inspector, and provide all tenants with notification as required by california civil code section 1954(san francisco housing code section 303(b),if any dwellings, apartment units or guest rooms are to be accessed during the reinspection.
    not activeNov 8, 2007
    other section · provide shutoff tool for gas utility shutoff (712 hc)
    install shut off tool in a visible and accessible location and adjacent to main gas valve.make sure that the type/size of the tool fits the existing valve(s)
    not activeNov 8, 2007
    other section · post enclosed gas meter instructional diagram in a public area. (712 hc)
    post gas diagram in a visible location so tenants are aware of emergency gas shut off procedures.
    not activeJan 5, 2001
    building section · repair damaged walls (1001b,h,o hc)
    complete patching wall where new alarm system has been installed
    not activeJan 5, 2001
    security requirements section · provide self-closing devices at exterior doors / gate (706 hc)
    provide automatic closing device at front gate for security purpose
    not activeJan 5, 2001
    other section · provide shutoff tool for gas utility shutoff (712 hc)
    not activeJan 5, 2001
    other section · post enclosed gas meter instructional diagram in a public area. (712 hc)
    not activeJan 5, 2001
    fire section · permanently remove combustible storage or provide automatic fire sprinklers. (904, 1001(i) hc)
    remove all stored items from underneath interior main stair case
    not activeJan 5, 2001
    fire section · permanently remove combustible storage. (904, 1001(i) hc)
    remove all stored items from underneath exterior fire escape stairs.
    Page 2 of 2