not activeJun 7, 2022
interior surfaces section · eliminate mold/mildew on walls (1301,1001b(13),1306 hc)
at time of inspection, mold was present on walls near window frames throughout the unit. eliminate mold in approved manner.
not activeJun 7, 2022
building section · repair window (1001(h),(j),& 708 hc)
at time of inspection, windows in upstair bedroom cannot be operated properly. repair or replace and adjust as needed so windows operate correctly, can be latched and provides adequate seal.
not activeJun 7, 2022
interior surfaces section · repair damaged walls (1001b,h,o hc)
at time of inspection, signs of leak damage were present on the walls in bathroom. repair and repaint the walls in approved manners. at time of inspection, no active leak was observed. however, there were signs of possible leak in the past. locate and repair source of leak if necessary.
not activeJun 7, 2022
interior surfaces section · repair damaged walls (1001b,h,o hc)
at time of inspection, several spots of walls throughout the unit were damaged. repair and repaint the walls in approved manners.
not activeJun 7, 2022
interior surfaces section · disturbing lead based paint can be extremely dangerous to dwelling occupants and visitors, particularly to young children, pregnant women, pets, and to people performing work on the premises. for interior or exterior paint removal : always wet the surface, contain and properly dispose of leaded paint. if you are unsure whether the paint is leaded, you should test it prior to performing any work. if the paint is found to contain lead, you should consult with an expert about appropriate procedures. proper containment and 3-day notification is required for exterior jobs of more than 10 sq.ft. (sec.3423, sfbc) informational packets are available at (415) 558-6088. you can contact the san francisco childhood lead poisoning prevention program at: (415) 252-3800 for free advice. if you cause lead dust to be created, you could be liable for any illness caused by the dust. ordinance #446-97.
not activeJun 7, 2022
other section · inspector comments
it is the property owner's responsibility to be present or direct his/her representative to attend the re-inspection as scheduled on this notice of violation for the purpose of providing entry to the inspector of those areas not accessed during the initial inspection as specified, and/or to provide access to all areas cited within this notice. if the property owner cannot attend the scheduled reinspection (as specified on this notice) it is his/her responsibility to secure a different inspection date and time with the inspector. provide all tenants with notification as required by california civil code section 1954 (san francisco housing code section 303(b), if any dwellings, apartment units or guest rooms are to be accessed during the re-inspection. you can reach inspector lee @ 415-793-7947 or by email at joy.lee@sfgov.org.
not activeMay 25, 2021
building section · violation location
1005 laguna st. apt. i
not activeMay 25, 2021
building section · remove egress obstruction (801,1001(l)hc) means of egress (1008.1.6)cbc) nuisance (401(2)(1001(d)hc)
secondary egress is obstructed by a dilapitated window. provide second egress.
not activeMay 25, 2021
building section · repair windows (1001(h),708 hc)
repair window in the master bedroom. at the time of inspection, windows were not able to open.
not activeMay 25, 2021
building section · building permit required (301 hc)
if replacement of enitre window in master bedroom is required to repair window to good working condition a building permit will be required you are required to obtain a building permit to correct this violation. submit a copy of this "notice of violation" with your application and reference the complaint number on your building permit application. call the building inspector for periodic and or final inspection(s). when all work is complete, the building inspector must perform the final inspection and sign the job card, before the housing inspector can abate this violation. please present the signed job card indicating that work is complete to the housing inspector on the reinspection day.
not activeMay 25, 2021
other section · inspectors comments
"repairs cited in this notice may require building, plumbing and / or electrical permits. when you apply for a permit, reference the complaint number from this notice of violation. it is the responsibility of the owner to obtain (or have others obtain) any required permits before beginning work that requires permit(s). this case can not be abated until the housing inspector makes a final inspection to verify that all violations have been corrected and all required permits have been obtained and finalized. on reinspection day, present to the housing inspector the job card, permit application and permits indicating that all required work under permit is complete. prior to reinspection by housing inspector, call building, electrical and/or plumbing inspector(s) for required inspection(s). it is the property owner's responsibility to be present or direct his/her representative to attend the re-inspection as scheduled on this notice of violation for the purpose of providing entry to the inspector of those areas not accessed during the initial inspection as specified, and/or to provide access to all areas cited within this notice. if the property owner cannot attend the scheduled re-inspection (as specified on this notice) it is his/her responsibility to secure a different inspection date and time with the inspector. provide all tenants with notification as required by california civil code section 1954 (san francisco housing code section 303(b), if any dwellings, apartment units or guest rooms are to be accessed during the re-inspection. "
not activeDec 18, 2019
Heating equipment
No permit to operate the boiler. serial no A93CC0129, CMC 1022. Monthly monitoring fee applies. Code Sec: SFBC 110A, Table 1A-K
not activeFeb 21, 2018
Heating equipment
No permit to operate the boiler. serial no 8891771, CMC 1022
not activeOct 30, 2017
DBI code violation
1.) A building you owned on September 15, 2017, was noticed as part of the mandatory Soft Story Retrofit Program. You have failed to submit the permit application with plans for Seismic Retrofit work. This building is in violation of the requirements of the San Francisco Building Code regarding earthquake safety. The owner of this building has not complied with the Soft Story Retrofit Program as required by S.F.E.B.C. 405D.2. 2.) Monthly Monitoring Fee (S.F.B.C. 102A.3, Table 1A-K). 3.) Do not remove the posted "Earthquake Warning" Placard (S.F.E.B.C 405D.6.1).
not activeJun 1, 2016
Heating equipment
No permit to operate the boiler. serial no 8891771, CMC 1022
not activeJun 1, 2016
Heating equipment
No permit to operate the boiler. serial no 8891771, CMC 1022
not activeJun 1, 2016
Heating equipment
No permit to operate the boiler. serial no A93CC0129, CMC 1022
not activeJun 1, 2016
Heating equipment
No permit to operate the boiler. serial no A93CC0129, CMC 1022
not activeNov 4, 2015
Heating equipment
No permit to operate the boiler. serial no URNG1204G00810, CMC 1022
not activeNov 4, 2015
Heating equipment
No permit to operate the boiler. serial no URNG1204G00810, CMC 1022
not activeMar 9, 2012
Heating equipment
No permit to operate the boiler. CMC 1022, serial no MH000965483
not activeJan 3, 2011
building section · this notice includes violations for the areas noted.
unit #g of the subject property.
not activeJan 3, 2011
plumbing and electrical section · repair sink (1001f hc)
repair hole in kitchen sink next to faucet.
not activeJan 3, 2011
plumbing and electrical section · repair lightswitch (1001e hc)
repair/replace inoperable lightswitch/light in bedroom
not activeJan 3, 2011
building section · repair window sash frame (1001(h),708 hc)
repair window frames in bedrooms to prevent air intrusion.
not activeJan 3, 2011
other section · inspector comments
it is the property owner's responsibility to be present or direct his/her representative to attend the re-inspection as scheduled on this notice of violation for the purpose of providing entry to the inspector of those areas not accessed during the initial inspection as specified, and/or to provide access to all areas cited within this notice. if the property owner cannot attend the scheduled re-inspection (as specified on this notice) it is his/her responsibility to secure a different inspection date and time with the inspector, and provide all tenants with notification as required by california civil code section 1954 (san francisco housing code section 303(b), if any dwellings, apartment units or guest rooms are to be accessed during the re-inspection.
not activeSep 2, 2010
Heating equipment
No permit to operate the boiler. CMC 1023
not activeSep 2, 2010
Heating equipment
OPERATE THE BOILER SN# M96250-341. CMC 1022.0
not activeJul 22, 2010
building section · this notice includes violations for the areas noted.
complaint inspection at 1055 laguna street, unit "m"
not activeJul 22, 2010
building section · repair door bell (1001 hc)
repair non-operating door bell.
not activeJul 22, 2010
other section · provide heat to each occupied habitable room for 13 hrs between 5:00 a.m. and 11:00 a.m. and between 3:00 p.m. and 10:00 p.m. capable to maintaining a min. room temp. of 68 degrees f. (20 degrees c.). (701c hc)
repair non-operating wall mounted heater. restore heater to full operation.
not activeJul 22, 2010
interior surfaces section · eliminate mold/mildew at cabinets (1301,1001b(13),1306 hc)
eliminate mold/mildew underneath the bathroom sink. mold/mildew was visible in and adjacent to base cabinet holding sink.
not activeJul 22, 2010
other section · inspector comments
it is the property owner's responsibility to be present or direct his/her representative to attend the re-inspection as scheduled on this notice of violation for the purpose of providing entry to the inspector of those areas not accessed during the initial inspection as specified, and/or to provide access to all areas cited within this notice. if the property owner cannot attend the scheduled re-inspection (as specified on this notice) it is his/her responsibility to secure a different inspection date and time with the inspector, and provide all tenants with notification as required by california civil code section 1954 (san francisco housing code section 303b), if any dwellings, apartment units or guest rooms are to be accessed during the re-inspection.
not activeMay 24, 2007
building section · this notice includes violations for the areas noted.
1035, 1045, and 1055 laguna st. common areas.
not activeMay 24, 2007
fire section · repair fire proofing with approved materials (hc 1001(m), 809)
at mechanical room behind 1035 laguna st.
not activeMay 24, 2007
fire section · remove egress obstruction (801,1001(l) hc)
remove locked deadlatch hardware from penthouse door to roof. door must not be locked with a key on the interior, but may be fastened on the inside by a movable bolt or dead latch lock.
not activeMay 24, 2007
other section · inspector comments
it is the property owner's responsibility to be present or direct his/ her representative to attend, the reinspection as scheduled on this notice of violation for the purpose of providing entry to the inspector of those areas not accessed during the initial inspection as specified, and/ or to provide access to all areas cited within this notice. if the property owner cannot attend the scheduled reinspection (as specified on this notice) it is his/ her responsibility to secure a different inspection date and time with the inspector, and provide all tenants with notification as required by california civil code section 1954. san francisco housing code section 303.(b), if any dwelling, apartment units or guest rooms are to be accessed during the reinspection.
not activeMay 22, 2007
building section · this notice includes violations for the areas noted.
1107-1157 turk street.
not activeMay 22, 2007
security requirements section · provide primary locking devices at exterior doors (706 hc)
1107-1157 turk st: provide a closing device at entry door or iron gate of each apt. unit.
not activeMay 22, 2007
security requirements section · provide deadlatch locks with min 1/2" throw at exit doors (706 hc)
1107-1157 turk st: remove deadbolt locks from all gate doors and replace with deadlatch hardware.
not activeMay 22, 2007
other section · inspector comments
it is the property owner's responsibility to be present or direct his/ her representative to attend, the reinspection as scheduled on this notice of violation for the purpose of providing entry to the inspector of those areas not accessed during the initial inspection as specified, and/ or to provide access to all areas cited within this notice. if the property owner cannot attend the scheduled reinspection (as specified on this notice) it is his/ her responsibility to secure a different inspection date and time with the inspector, and provide all tenants with notification as required by california civil code section 1954. san francisco housing code section 303.(b), if any dwelling, apartment units or guest rooms are to be accessed during the reinspection.
not activeMay 3, 2007
building section · this notice includes violations for the areas noted.
1015 laguna st. common area.
not activeMay 3, 2007
fire section · fire escape maintenance and repair (908 hc)
regular fire escape maintenance required. note: property manager, owner or the owner's agent needs to provide proof of the workability of the fire escape ladders. a non-working fire escape is a life safty hazard and must be corrected immediately. provide a written and signed report from a qualified service company or contractor stating that all parts and cables have been tested and are functional or you are required to lower the ladder on re-inspection day to verify its proper full release. note: manufacturers recommend that the fire escape drop ladder be maintained and serviced annually, particularly the cable and all moving parts. lubricate and drop the ladder at least once a year.
not activeMay 3, 2007
fire section · provide date tag for all fire extinguishers (905 hc)
submit records to verify that all units are protected. provide fire extinguisher type 2a 10bc or equivalent with date tag. note: only extinguishers serviced by an industry professional are approved.
not activeMay 3, 2007
plumbing and electrical section · water heaters (1301 upc)
provide approved lateral bracing at water heater.
not activeMay 3, 2007
security requirements section · building address i.d. (706(a)(9)hc)
provide designated missing unit/apartment identification numbers to all units. including #1001 c, and 1005 g, j.
not activeMay 3, 2007
other section · inspector comments
it is the property owner's responsibility to be present or direct his/ her representative to attend, the reinspection as scheduled on this notice of violation for the purpose of providing entry to the inspector of those areas not accessed during the initial inspection as specified, and/ or to provide access to all areas cited within this notice. if the property owner cannot attend the scheduled reinspection (as specified on this notice) it is his/ her responsibility to secure a different inspection date and time with the inspector, and provide all tenants with notification as required by california civil code section 1954. san francisco housing code section 303.(b), if any dwelling, apartment units or guest rooms are to be accessed during the reinspection.
not activeAug 8, 2005
building section · this notice includes violations for the areas noted.
1045 laguna street, #j.
not activeAug 8, 2005
interior surfaces section · repair floor covering (1001b,j,o hc)
repair/replace carpet at entry of unit & kitchen transition. tripping hazard at entry foyer & kitchen transition.
not activeAug 8, 2005
other section · inspector comments
it is the property owner's responsibility to be present or direct his/her representative to attend, the reinspection as scheduled on this notice of violation for the purpose of providing entry to the inspector of those areas not accessed during the initial inspection as specified, and/or to provide access to all areas cited within this notice.