Severityⓘopen violations
3 open DBI violations
Active Notices of Violation issued by the Department of Building Inspection.
Severe0
Serious1
Minor2

What to watch forⓘ

  1. Tenants here have reported no heat or no hot water.
    details ▸

    California law requires heating facilities in good working order, and plumbing facilities in good working order including hot and cold running water. A rental unit that substantially lacks either may be legally uninhabitable, which is the standard the implied warranty of habitability sets for every residential tenancy in the state.

    Ask how heat and hot water are supplied and who pays for them. If either fails once you live here, put the request to the landlord in writing and keep a copy.

    • California Tenant Guide
    • San Francisco Housing Code §701
  2. Fire safety problems have been reported here.
    Worth checkingⓘ
    Walk the exit route from the unit to the street and check the stairs and hallways are clear of stored items, and that fire doors close properly.
    details ▸

    California law requires safe fire or emergency exits leading to a street or hallway, and requires stairs, hallways and exits to be kept litter free. Storage areas, garages and basements must be kept free of combustible materials. San Francisco's Housing Code separately treats inadequate exits and inadequate fire protection equipment as conditions that make a building substandard, which is the finding behind a notice of violation.

311 Housing Complaints
Total complaints since 2010
187
11 per year avg.↓ Down 39% in the last 2 years (19 vs 31 prior 2 yrs)
Complaint severity
Last 5 years
60
Severeⓘ4
Seriousⓘ44
Minorⓘ12
Dept. of Building Inspection Violations
Total violations since 1996
365
12 per year avg.↓ Down 71% in the last 2 years (4 vs 14 prior 2 yrs)
Open violations
3
Severeⓘ0
Seriousⓘ1
Minorⓘ2

Top violation categories

5 yrsAll time
Fire safetyⓘ2 violations
Plumbingⓘ2 violations
Cleanliness & refuseⓘ1 violations
Electricalⓘ1 violations
Ventilation & lightⓘ1 violations
Heat / hot waterⓘ1 violations
Walls, ceilings & cabinetsⓘ1 violations
No specific condition stated12 violations
2 still open. See violation log below.

Top complaint types

5 yrsAll time
Infestation Rodent Insect19 complaints
Bathroom8 complaints
Electrical Non Hazard6 complaints
Doors Windows Broken Defective4 complaints
General Maintenance Not In List Above4 complaints
Infestation Bed Bugs3 complaints
Mold And Mildew3 complaints
Inadequately Maintained Building Exterior2 complaints
Elevators Everthing Else2 complaints
Elevators No Working Elevator 7 Or More Stories2 complaints
Light Wells Dirty Flooded2 complaints
Ventilation Inadequate Or None1 complaints
Electrical Hazardous Condition1 complaints
Plumbing Broken Leaking1 complaints
Security Inadequately Secured Perimeter1 complaints
Hot Water Lack Of Hot Water1 complaints
Hide violations (365) ↑See complaints (187) →

Violation log

365 DBI violations

AllOpenClosed
StatusFiledCategoryItemNOV Item Description
not activeMay 10, 2014other sectioninspector commentsit is the property owner's responsibility to be present or direct his/ her representative to attend, the re-inspection as scheduled on this notice of violation for the purpose of providing entry to the inspector of those areas not accessed during the initial inspection as specified, and/ or to provide access to all areas cited within this notice. provide all tenants with notification as required by california civil code section 1954 san francisco housing code section 303 (b), if any dwelling, apartment units or guest rooms are to be accessed during the re-inspection.
See something wrong? File a complaint with SF 311
  • California Tenant Guide
  • San Francisco Housing Code §1001(m), (n)
  • Tenants here have reported pests.
    Worth checkingⓘ
    Look along baseboards and inside low cabinets for droppings, greasy rub marks or tracks, and check whether the bins outside overflow and whether gaps around exterior doors are sealed.
    details ▸

    California law requires buildings and grounds to be kept clean and sanitary and free from debris, filth, rubbish, garbage, rodents and vermin. San Francisco requires property owners to keep their property free of vermin, and requires an owner or manager to respond to a tenant's bed bug complaint by hiring a licensed pest control operator.

    • California Tenant Guide
    • SF.gov, Keeping your building free of vermin
  • not activeFeb 25, 2014building sectionthis notice includes violations for the areas noted.this notice includes violations of the san francisco housing code. unless otherwise noted all violations were observed on the date of inspection at 1485 pine street, through out the common areas and in multiple guest rooms.
    not activeFeb 25, 2014building sectionrepair window glazing seal (1001(h),(j),& 708 hc)replace the window glazing in unit 304 on both windows. these are dual glazed sash frames which need to have dual glazed panes in them.
    not activeFeb 25, 2014building sectionrepair window sash frame (1001(h),708 hc)insure that the sash and frame in the windows of units 205 and 304 provide smooth and easy operation and a weather tight condition with a working latch. window is to remain at any desired open position with the balance of a counter weight or sash spring.
    not activeFeb 25, 2014plumbing and electrical sectionprovide hot water 505 (d)(3)hcthe housing code requires that each building reserves a minimum of 8 gallons of hot water per dwelling unit and that this water shall be delivered to each unit between 105 and 120 degrees fahrenheit. the water in unit 304 tested at 88 degrees with 3 readings. locate the source of the problem and correct in an approved manner to supply all units with hot water to meet these requirements.
    not activeFeb 25, 2014sanitation sectionremove dangerous articles of storage 1310 hcthere is an excess of personal belongings, storage and debris in units 216, 301, 309, 314 and 415. this unit is to be cleaned and storage reduced to eliminate the rodent harborage.
    not activeFeb 25, 2014sanitation sectionremove the egress obstruction 810 hcthis condition in units 216, 301, 309, 314 and 415 also creates an egress obstruction. personal belongings shall be permanently removed to clear a 3 foot wide access from the entry door to the bed, from the bed to the window, and from the window to the entry door. once personal belonging are reduced the unit shall be cleaned and sanitized.
    not activeFeb 25, 2014sanitation sectiondispose of rubbish and filth properly 1307 hcit is the occupants' responsibility to keep the area they control clean, sanitary and free of egress obstructions and fire hazards. it is the owner's responsibility to maintain the common areas and insure the occupants maintain the areas under their control to insure habitable conditions for the other residents.
    not activeFeb 25, 2014fire sectionremove egress obstruction (801,1001(l) hc)on the first floor at the back door the broom stick is to be removed and nails and screws keeping the door secured are to be removed. this is a required fire exit to remain free from obstruction.
    not activeFeb 25, 2014fire sectionremove egress obstruction (801,1001(l) hc)remove the hasps on the door and frames of guest rooms 104, 207, 212, 217 and 314.
    not activeFeb 25, 2014plumbing and electrical sectionrepair ceiling light fixture (1001e hc)repair the ceiling light fixtures in guest rooms 408 and 310.
    not activeFeb 25, 2014plumbing and electrical sectionremove cord wiring (1001-e hc)remove the extension cord traveling from unit 417 to the house outlet in the corridor.
    not activeFeb 25, 2014interior surfaces sectionpaint out the graffitti 1301 hcremove the graffiti, paint and repair the door to unit 206.
    not activeFeb 25, 2014plumbing and electrical sectionprovide adequate lighting 504 (g), 1001 (b)(10) and (d) hcprovide adequate electrical lighting in all common areas such as hallways, trash rooms, shower rooms, toilets and lobby. at the time of inspection there were a number of light bulbs burned out or missing.
    not activeFeb 25, 2014building sectionrepair the stucco and door jamb 703 hcat the rear exit door repair and paint the stucco surface and wooden door jamb to restore the weather protection.
    not activeFeb 25, 2014building sectionrepair the roof access door 706 & 807 & 912 hcrepair the exit door to the roof. exit doors to shall be a minimum one-and-three-eighths inch solid wood core or approved equal. doors and jambs shall be tight fitting, in good condition and self-closing. roof access doors shall be covered on the roof side with galvanized or otherwise weather proof metal. roof access doors will be installed with a primary locking device with a minimum one half inch dead latch and shall be operable from the interior without a key and no special knowledge or effort shall be required. the roof access door may also be locked from the inside with a movable bolt. additionally the roof access door shall be provided with a self closing device.
    not activeFeb 25, 2014building sectionprovide screen to restrict vermin 1306 hcinstall a galvanized steel screen to prohibit mice from entering the guest room 205 from the light well.
    not activeFeb 25, 2014other sectioninspector commentsit is the property owner's responsibility to be present or direct his/ her representative to attend, the re-inspection as scheduled on this notice of violation for the purpose of providing entry to the inspector of those areas not accessed during the initial inspection as specified, and/ or to provide access to all areas cited within this notice. provide all tenants with notification as required by california civil code section 1954 san francisco housing code section 303 (b), if any dwelling, apartment units or guest rooms are to be accessed during the re-inspection.
    not activeFeb 25, 2014building sectionrepair damaged walls 1001 (b, d, h) hcin unit 205 repair the holes in the walls around the sink pipes to eliminate visits from local rodents.
    not activeFeb 25, 2014smoke detection sectionprovide smoke detector (908,911 hc)provide smoke detectors in each sleeping quarter and in the path of the means of egress from the sleeping units to exit area.
    not activeFeb 25, 2014smoke detection sectionprovide carbon monoxide detectors detector (420 bc)provide carbon monoxide detectors laid out per the san francisco building code section 420. there shall be one unit in each guest room within the immediate floor and each adjacent floor, above and below a gas burning appliance to include stoves, dryers, furnaces, water heaters and boilers.
    not activeFeb 10, 2014building sectionthis notice includes violations for the areas noted.this notice includes violations of the san francisco housing code. unless otherwise noted all violations were observed on the date of inspection at 1485 pine street, in the common areas and all units.
    not activeFeb 10, 2014other sectionprovide heat to each occupied habitable room for 13 hrs between 5:00 a.m. and 11:00 a.m. and between 3:00 p.m. and 10:00 p.m. capable to maintaining a min. room temp. of 68 degrees f. (20 degrees c.). (701c hc)provide heat to each occupied habitable room for 13 hours, between 5:00 am and 11:00am and between 3:00 pm and 10:00 pm, maintaining a minimum room temperature of 68 degrees farenheit (20 degrees c).
    not activeFeb 10, 2014other sectionset timeclock to provide the required amount and hours of heat. (701c hc)your timer was photographed offering 4 hours of heat to the residents of this facility. make the necessary corrections to conform to the previously listed 13 hours of regulated time.
    not activeFeb 10, 2014other sectioninspector commentsit is the property owner's responsibility to be present or direct his/ her representative to attend, the re-inspection as scheduled on this notice of violation for the purpose of providing entry to the inspector of those areas not accessed during the initial inspection as specified, and/ or to provide access to all areas cited within this notice. provide all tenants with notification as required by california civil code section 1954 san francisco housing code section 303 (b), if any dwelling, apartment units or guest rooms are to be accessed during the re-inspection. important note: due to the nature of this violation, this property has been defined as a nuisance per section 1001-d of the san francisco housing code.
    not activeOct 1, 2013building sectionthis notice includes violations for the areas noted.unless otherwise noted all violations occur at 1485 pine street, san francisco
    not activeOct 1, 2013fire sectionkeep smoke enclosure doors closed (807 hc)remove all screws and tie strings which keep doors open at each floor at the north and south side of the staircase.
    not activeOct 1, 2013building sectionrepair toilet (1001f hc)it is insufficient to just recaulk the seam below the toilet. replace the wax ring under the toilet in the third floor bathroom to eliminate the leak.
    not activeOct 1, 2013fire sectionrepair smoke enclosure door closer (807,707 hc)repair or replace, as necessary, the automatic door closer on the second floor fire door.
    not activeOct 1, 2013sanitation sectioneliminate rodent infestation (1001b, 1306 hc)there is clear and present evidence of mice in the third floor trash room. perform rodent proofing as required. cover/seal all openings in the floor. provide regular pest control by an industry professional. provide a maintenance schedule.
    not activeOct 1, 2013sanitation sectioneliminate bedbug infestation (1001(b), 1306 sfhc)eliminate bedbug/rodent/cockroach infestation at all guestroom locations. pest control should be performed in all guest rooms whether occupied or not and in all common areas of the building. provide housing inspector all pest control reports and certifications at the time of re-inspection. all certifications should follow the protocol from the department of public health. unit 306: evidence of bed bugs was noted. a referral will be made to the environmental health section of the department of public health (for apts. 415-252-3805 for hotels 415-252-3857).
    not activeOct 1, 2013fire sectionrecharge/date tag fire extinguisher type 2a 10bc or equivalent (905,1001(m)hc)provide fire extinguisher type 2a 10bc or equivalent with current date tag accessible to each residential unit located no more than 70 feet away. at all expired fire extinguishers. note: only fire extinguishers certified or serviced by an industry professional are approved.
    not activeOct 1, 2013other sectioninspector commentsnuisance (401(2) (1001(d) hc it is the property owner's responsibility to be present or direct his/ her representative to attend, the re-inspection as scheduled on this notice of violation for the purpose of providing entry to the inspector of those areas not accessed during the initial inspection as specified, and/ or to provide access to all areas cited within this notice. if the property owner cannot attend the scheduled re-inspection (as specified on this notice) it is his/ her responsibility to secure a different inspection date and time with the inspector, and provide all tenants with notification as required by california civil code section 1954. san francisco housing code section 303. (b), if any dwelling, apartment units or guest rooms are to be accessed during the re-inspection.
    not activeMar 11, 2013building sectionthis notice includes violations for the areas noted.all common areas of 1485 pine street
    not activeMar 11, 2013plumbing and electrical sectionother plumbing and/or electrical violationselectrical circuits conitnue to break due to overload and the usage of appliances that require large capacity of amps. room to room inspection by management is therefore required to determine the cause and the elimination of items that can be causing the circuit overload, this overload can lead to the heating up of wires, which in turn can cause a fire. please advise tenants of the danger involved and limit them to the amount of electrical items used and kept in rooms. on day of reinspection provide access to all rooms in order to check the amount of appliances in rooms and help to eliminate the ongoing issue.
    not activeMar 11, 2013other sectioninspector commentsinspector comments regarding "follow up" reinspection: i have scheduled a reinspection of your building on friday, 13-april-2013 at 2:30 pm. reinspection of premise to include all areas referenced above. please contact inspector galvis to confirm appointment at 415-558-6513. it is the property owners responsibility to be present or direct his/her representative to attend, the reinspection as scheduled on this notice of violation for the purpose of providing entry to the inspector of those areas cited within this notice. if the property owner cannot attend the scheduled reinspection (as specified on this notice) it is his/her responsibility to secure a different inspection date and time with the inspector. on scheduled reinspection day, provide the inspector with a full access to all common and public areas per attached checklist. your cooperation is appreciated.
    not activeJan 25, 2013building sectionthis notice includes violations for the areas noted.all common areas of 1485 pine street
    not activeJan 25, 2013fire sectionprovide fire extinguisher type 2a 10bc or equivalent.(905, 1001(n)hc)replace missing fire extinguisher on fourth floor
    not activeJan 25, 2013other sectioninspector commentsinspector comments regarding "follow up" reinspection: i have scheduled a reinspection of your building on thursday, 28-february-2013 at 9:00 am. reinspection of premise to include all areas referenced above. please contact inspector galvis to confirm appointment at 415-558-6513. it is the property owners responsibility to be present or direct his/her representative to attend, the reinspection as scheduled on this notice of violation for the purpose of providing entry to the inspector of those areas cited within this notice. if the property owner cannot attend the scheduled reinspection (as specified on this notice) it is his/her responsibility to secure a different inspection date and time with the inspector. on scheduled reinspection day, provide the inspector with a full access to all common and public areas per attached checklist. your cooperation is appreciated.
    not activeSep 11, 2012building sectionthis notice includes violations for the areas noted.all common areas of 1485 pine street
    not activeSep 11, 2012other sectionprovide heat to each occupied habitable room for 13 hrs between 5:00 a.m. and 11:00 a.m. and between 3:00 p.m. and 10:00 p.m. capable to maintaining a min. room temp. of 68 degrees f. (20 degrees c.). (701c hc)on reinspection provide access to room that contains thermostat.
    not activeSep 11, 2012other sectioninspector commentsinspector comments regarding "follow up" reinspection: i have scheduled a reinspection of your building on thursday, 27-september-2012 at 9:00 am. reinspection of premise to include all areas referenced above. please contact inspector galvis to confirm appointment at 415-558-6513. it is the property owners responsibility to be present or direct his/her representative to attend, the reinspection as scheduled on this notice of violation for the purpose of providing entry to the inspector of those areas cited within this notice. if the property owner cannot attend the scheduled reinspection (as specified on this notice) it is his/her responsibility to secure a different inspection date and time with the inspector. on scheduled reinspection day, provide the inspector with a full access to all common and public areas per attached checklist. your cooperation is appreciated.
    not activeJul 26, 2012building sectionthis notice includes violations for the areas noted.all common areas of 1485 pine street
    not activeJul 26, 2012fire sectionremove egress obstruction at (801,1001(l) hc)remove padlock at roof access door and remove wood that is barricading door to side alley on first floor.
    not activeJul 26, 2012fire sectionreplace smoke enclosure door (807 707 hc)replace smoke enclosure door at roof access door.
    not activeJul 26, 2012plumbing and electrical sectionother plumbing and/or electrical violationsremove radiator lines or install radiators at exits at west side of building on the fourth and second floors, pipes are deemed a tripping hazard and can cause serious injury to tenants having to leave in an emergency out through fire escapes.
    not activeJul 26, 2012other sectionprovide heat to each occupied habitable room for 13 hrs between 5:00 a.m. and 11:00 a.m. and between 3:00 p.m. and 10:00 p.m. capable to maintaining a min. room temp. of 68 degrees f. (20 degrees c.). (701c hc)provide access to boiler room and room that contains thermostat on the reinspection date.
    not activeJul 26, 2012other sectioninspector commentsinspector comments regarding "follow up" reinspection: i have scheduled a reinspection of your building on friday, 03-august-2012 at 9:30 am. reinspection of premise to include all areas referenced above. please contact inspector galvis to confirm appointment at 415-558-6513. it is the property owners responsibility to be present or direct his/her representative to attend, the reinspection as scheduled on this notice of violation for the purpose of providing entry to the inspector of those areas cited within this notice. if the property owner cannot attend the scheduled reinspection (as specified on this notice) it is his/her responsibility to secure a different inspection date and time with the inspector. on scheduled reinspection day, provide the inspector with a full access to all common and public areas per attached checklist. your cooperation is appreciated.
    not activeNov 30, 2011building sectionthis notice includes violations for the areas noted.1485 pine street room# 401
    not activeNov 30, 2011building sectionrepair window sash frame (1001(h),708 hc)repair right side window in room# 401
    not activeMay 10, 2014
    other section · inspector comments
    it is the property owner's responsibility to be present or direct his/ her representative to attend, the re-inspection as scheduled on this notice of violation for the purpose of providing entry to the inspector of those areas not accessed during the initial inspection as specified, and/ or to provide access to all areas cited within this notice. provide all tenants with notification as required by california civil code section 1954 san francisco housing code section 303 (b), if any dwelling, apartment units or guest rooms are to be accessed during the re-inspection.
    not activeFeb 25, 2014
    building section · this notice includes violations for the areas noted.
    this notice includes violations of the san francisco housing code. unless otherwise noted all violations were observed on the date of inspection at 1485 pine street, through out the common areas and in multiple guest rooms.
    not activeFeb 25, 2014
    building section · repair window glazing seal (1001(h),(j),& 708 hc)
    replace the window glazing in unit 304 on both windows. these are dual glazed sash frames which need to have dual glazed panes in them.
    not activeFeb 25, 2014
    building section · repair window sash frame (1001(h),708 hc)
    insure that the sash and frame in the windows of units 205 and 304 provide smooth and easy operation and a weather tight condition with a working latch. window is to remain at any desired open position with the balance of a counter weight or sash spring.
    not activeFeb 25, 2014
    plumbing and electrical section · provide hot water 505 (d)(3)hc
    the housing code requires that each building reserves a minimum of 8 gallons of hot water per dwelling unit and that this water shall be delivered to each unit between 105 and 120 degrees fahrenheit. the water in unit 304 tested at 88 degrees with 3 readings. locate the source of the problem and correct in an approved manner to supply all units with hot water to meet these requirements.
    not activeFeb 25, 2014
    sanitation section · remove dangerous articles of storage 1310 hc
    there is an excess of personal belongings, storage and debris in units 216, 301, 309, 314 and 415. this unit is to be cleaned and storage reduced to eliminate the rodent harborage.
    not activeFeb 25, 2014
    sanitation section · remove the egress obstruction 810 hc
    this condition in units 216, 301, 309, 314 and 415 also creates an egress obstruction. personal belongings shall be permanently removed to clear a 3 foot wide access from the entry door to the bed, from the bed to the window, and from the window to the entry door. once personal belonging are reduced the unit shall be cleaned and sanitized.
    not activeFeb 25, 2014
    sanitation section · dispose of rubbish and filth properly 1307 hc
    it is the occupants' responsibility to keep the area they control clean, sanitary and free of egress obstructions and fire hazards. it is the owner's responsibility to maintain the common areas and insure the occupants maintain the areas under their control to insure habitable conditions for the other residents.
    not activeFeb 25, 2014
    fire section · remove egress obstruction (801,1001(l) hc)
    on the first floor at the back door the broom stick is to be removed and nails and screws keeping the door secured are to be removed. this is a required fire exit to remain free from obstruction.
    not activeFeb 25, 2014
    fire section · remove egress obstruction (801,1001(l) hc)
    remove the hasps on the door and frames of guest rooms 104, 207, 212, 217 and 314.
    not activeFeb 25, 2014
    plumbing and electrical section · repair ceiling light fixture (1001e hc)
    repair the ceiling light fixtures in guest rooms 408 and 310.
    not activeFeb 25, 2014
    plumbing and electrical section · remove cord wiring (1001-e hc)
    remove the extension cord traveling from unit 417 to the house outlet in the corridor.
    not activeFeb 25, 2014
    interior surfaces section · paint out the graffitti 1301 hc
    remove the graffiti, paint and repair the door to unit 206.
    not activeFeb 25, 2014
    plumbing and electrical section · provide adequate lighting 504 (g), 1001 (b)(10) and (d) hc
    provide adequate electrical lighting in all common areas such as hallways, trash rooms, shower rooms, toilets and lobby. at the time of inspection there were a number of light bulbs burned out or missing.
    not activeFeb 25, 2014
    building section · repair the stucco and door jamb 703 hc
    at the rear exit door repair and paint the stucco surface and wooden door jamb to restore the weather protection.
    not activeFeb 25, 2014
    building section · repair the roof access door 706 & 807 & 912 hc
    repair the exit door to the roof. exit doors to shall be a minimum one-and-three-eighths inch solid wood core or approved equal. doors and jambs shall be tight fitting, in good condition and self-closing. roof access doors shall be covered on the roof side with galvanized or otherwise weather proof metal. roof access doors will be installed with a primary locking device with a minimum one half inch dead latch and shall be operable from the interior without a key and no special knowledge or effort shall be required. the roof access door may also be locked from the inside with a movable bolt. additionally the roof access door shall be provided with a self closing device.
    not activeFeb 25, 2014
    building section · provide screen to restrict vermin 1306 hc
    install a galvanized steel screen to prohibit mice from entering the guest room 205 from the light well.
    not activeFeb 25, 2014
    other section · inspector comments
    it is the property owner's responsibility to be present or direct his/ her representative to attend, the re-inspection as scheduled on this notice of violation for the purpose of providing entry to the inspector of those areas not accessed during the initial inspection as specified, and/ or to provide access to all areas cited within this notice. provide all tenants with notification as required by california civil code section 1954 san francisco housing code section 303 (b), if any dwelling, apartment units or guest rooms are to be accessed during the re-inspection.
    not activeFeb 25, 2014
    building section · repair damaged walls 1001 (b, d, h) hc
    in unit 205 repair the holes in the walls around the sink pipes to eliminate visits from local rodents.
    not activeFeb 25, 2014
    smoke detection section · provide smoke detector (908,911 hc)
    provide smoke detectors in each sleeping quarter and in the path of the means of egress from the sleeping units to exit area.
    not activeFeb 25, 2014
    smoke detection section · provide carbon monoxide detectors detector (420 bc)
    provide carbon monoxide detectors laid out per the san francisco building code section 420. there shall be one unit in each guest room within the immediate floor and each adjacent floor, above and below a gas burning appliance to include stoves, dryers, furnaces, water heaters and boilers.
    not activeFeb 10, 2014
    building section · this notice includes violations for the areas noted.
    this notice includes violations of the san francisco housing code. unless otherwise noted all violations were observed on the date of inspection at 1485 pine street, in the common areas and all units.
    not activeFeb 10, 2014
    other section · provide heat to each occupied habitable room for 13 hrs between 5:00 a.m. and 11:00 a.m. and between 3:00 p.m. and 10:00 p.m. capable to maintaining a min. room temp. of 68 degrees f. (20 degrees c.). (701c hc)
    provide heat to each occupied habitable room for 13 hours, between 5:00 am and 11:00am and between 3:00 pm and 10:00 pm, maintaining a minimum room temperature of 68 degrees farenheit (20 degrees c).
    not activeFeb 10, 2014
    other section · set timeclock to provide the required amount and hours of heat. (701c hc)
    your timer was photographed offering 4 hours of heat to the residents of this facility. make the necessary corrections to conform to the previously listed 13 hours of regulated time.
    not activeFeb 10, 2014
    other section · inspector comments
    it is the property owner's responsibility to be present or direct his/ her representative to attend, the re-inspection as scheduled on this notice of violation for the purpose of providing entry to the inspector of those areas not accessed during the initial inspection as specified, and/ or to provide access to all areas cited within this notice. provide all tenants with notification as required by california civil code section 1954 san francisco housing code section 303 (b), if any dwelling, apartment units or guest rooms are to be accessed during the re-inspection. important note: due to the nature of this violation, this property has been defined as a nuisance per section 1001-d of the san francisco housing code.
    not activeOct 1, 2013
    building section · this notice includes violations for the areas noted.
    unless otherwise noted all violations occur at 1485 pine street, san francisco
    not activeOct 1, 2013
    fire section · keep smoke enclosure doors closed (807 hc)
    remove all screws and tie strings which keep doors open at each floor at the north and south side of the staircase.
    not activeOct 1, 2013
    building section · repair toilet (1001f hc)
    it is insufficient to just recaulk the seam below the toilet. replace the wax ring under the toilet in the third floor bathroom to eliminate the leak.
    not activeOct 1, 2013
    fire section · repair smoke enclosure door closer (807,707 hc)
    repair or replace, as necessary, the automatic door closer on the second floor fire door.
    not activeOct 1, 2013
    sanitation section · eliminate rodent infestation (1001b, 1306 hc)
    there is clear and present evidence of mice in the third floor trash room. perform rodent proofing as required. cover/seal all openings in the floor. provide regular pest control by an industry professional. provide a maintenance schedule.
    not activeOct 1, 2013
    sanitation section · eliminate bedbug infestation (1001(b), 1306 sfhc)
    eliminate bedbug/rodent/cockroach infestation at all guestroom locations. pest control should be performed in all guest rooms whether occupied or not and in all common areas of the building. provide housing inspector all pest control reports and certifications at the time of re-inspection. all certifications should follow the protocol from the department of public health. unit 306: evidence of bed bugs was noted. a referral will be made to the environmental health section of the department of public health (for apts. 415-252-3805 for hotels 415-252-3857).
    not activeOct 1, 2013
    fire section · recharge/date tag fire extinguisher type 2a 10bc or equivalent (905,1001(m)hc)
    provide fire extinguisher type 2a 10bc or equivalent with current date tag accessible to each residential unit located no more than 70 feet away. at all expired fire extinguishers. note: only fire extinguishers certified or serviced by an industry professional are approved.
    not activeOct 1, 2013
    other section · inspector comments
    nuisance (401(2) (1001(d) hc it is the property owner's responsibility to be present or direct his/ her representative to attend, the re-inspection as scheduled on this notice of violation for the purpose of providing entry to the inspector of those areas not accessed during the initial inspection as specified, and/ or to provide access to all areas cited within this notice. if the property owner cannot attend the scheduled re-inspection (as specified on this notice) it is his/ her responsibility to secure a different inspection date and time with the inspector, and provide all tenants with notification as required by california civil code section 1954. san francisco housing code section 303. (b), if any dwelling, apartment units or guest rooms are to be accessed during the re-inspection.
    not activeMar 11, 2013
    building section · this notice includes violations for the areas noted.
    all common areas of 1485 pine street
    not activeMar 11, 2013
    plumbing and electrical section · other plumbing and/or electrical violations
    electrical circuits conitnue to break due to overload and the usage of appliances that require large capacity of amps. room to room inspection by management is therefore required to determine the cause and the elimination of items that can be causing the circuit overload, this overload can lead to the heating up of wires, which in turn can cause a fire. please advise tenants of the danger involved and limit them to the amount of electrical items used and kept in rooms. on day of reinspection provide access to all rooms in order to check the amount of appliances in rooms and help to eliminate the ongoing issue.
    not activeMar 11, 2013
    other section · inspector comments
    inspector comments regarding "follow up" reinspection: i have scheduled a reinspection of your building on friday, 13-april-2013 at 2:30 pm. reinspection of premise to include all areas referenced above. please contact inspector galvis to confirm appointment at 415-558-6513. it is the property owners responsibility to be present or direct his/her representative to attend, the reinspection as scheduled on this notice of violation for the purpose of providing entry to the inspector of those areas cited within this notice. if the property owner cannot attend the scheduled reinspection (as specified on this notice) it is his/her responsibility to secure a different inspection date and time with the inspector. on scheduled reinspection day, provide the inspector with a full access to all common and public areas per attached checklist. your cooperation is appreciated.
    not activeJan 25, 2013
    building section · this notice includes violations for the areas noted.
    all common areas of 1485 pine street
    not activeJan 25, 2013
    fire section · provide fire extinguisher type 2a 10bc or equivalent.(905, 1001(n)hc)
    replace missing fire extinguisher on fourth floor
    not activeJan 25, 2013
    other section · inspector comments
    inspector comments regarding "follow up" reinspection: i have scheduled a reinspection of your building on thursday, 28-february-2013 at 9:00 am. reinspection of premise to include all areas referenced above. please contact inspector galvis to confirm appointment at 415-558-6513. it is the property owners responsibility to be present or direct his/her representative to attend, the reinspection as scheduled on this notice of violation for the purpose of providing entry to the inspector of those areas cited within this notice. if the property owner cannot attend the scheduled reinspection (as specified on this notice) it is his/her responsibility to secure a different inspection date and time with the inspector. on scheduled reinspection day, provide the inspector with a full access to all common and public areas per attached checklist. your cooperation is appreciated.
    not activeSep 11, 2012
    building section · this notice includes violations for the areas noted.
    all common areas of 1485 pine street
    not activeSep 11, 2012
    other section · provide heat to each occupied habitable room for 13 hrs between 5:00 a.m. and 11:00 a.m. and between 3:00 p.m. and 10:00 p.m. capable to maintaining a min. room temp. of 68 degrees f. (20 degrees c.). (701c hc)
    on reinspection provide access to room that contains thermostat.
    not activeSep 11, 2012
    other section · inspector comments
    inspector comments regarding "follow up" reinspection: i have scheduled a reinspection of your building on thursday, 27-september-2012 at 9:00 am. reinspection of premise to include all areas referenced above. please contact inspector galvis to confirm appointment at 415-558-6513. it is the property owners responsibility to be present or direct his/her representative to attend, the reinspection as scheduled on this notice of violation for the purpose of providing entry to the inspector of those areas cited within this notice. if the property owner cannot attend the scheduled reinspection (as specified on this notice) it is his/her responsibility to secure a different inspection date and time with the inspector. on scheduled reinspection day, provide the inspector with a full access to all common and public areas per attached checklist. your cooperation is appreciated.
    not activeJul 26, 2012
    building section · this notice includes violations for the areas noted.
    all common areas of 1485 pine street
    not activeJul 26, 2012
    fire section · remove egress obstruction at (801,1001(l) hc)
    remove padlock at roof access door and remove wood that is barricading door to side alley on first floor.
    not activeJul 26, 2012
    fire section · replace smoke enclosure door (807 707 hc)
    replace smoke enclosure door at roof access door.
    not activeJul 26, 2012
    plumbing and electrical section · other plumbing and/or electrical violations
    remove radiator lines or install radiators at exits at west side of building on the fourth and second floors, pipes are deemed a tripping hazard and can cause serious injury to tenants having to leave in an emergency out through fire escapes.
    not activeJul 26, 2012
    other section · provide heat to each occupied habitable room for 13 hrs between 5:00 a.m. and 11:00 a.m. and between 3:00 p.m. and 10:00 p.m. capable to maintaining a min. room temp. of 68 degrees f. (20 degrees c.). (701c hc)
    provide access to boiler room and room that contains thermostat on the reinspection date.
    not activeJul 26, 2012
    other section · inspector comments
    inspector comments regarding "follow up" reinspection: i have scheduled a reinspection of your building on friday, 03-august-2012 at 9:30 am. reinspection of premise to include all areas referenced above. please contact inspector galvis to confirm appointment at 415-558-6513. it is the property owners responsibility to be present or direct his/her representative to attend, the reinspection as scheduled on this notice of violation for the purpose of providing entry to the inspector of those areas cited within this notice. if the property owner cannot attend the scheduled reinspection (as specified on this notice) it is his/her responsibility to secure a different inspection date and time with the inspector. on scheduled reinspection day, provide the inspector with a full access to all common and public areas per attached checklist. your cooperation is appreciated.
    not activeNov 30, 2011
    building section · this notice includes violations for the areas noted.
    1485 pine street room# 401
    not activeNov 30, 2011
    building section · repair window sash frame (1001(h),708 hc)
    repair right side window in room# 401
    Page 2 of 8