not activeSep 12, 2014
security requirements section · provide adequate lighting 504g sfhc
provide a light bulb for the ceiling fixture in unit 7 and insure the fixture works.
not activeSep 12, 2014
interior surfaces section · find and fix the source of the leak 1001f sfhc
find and fix the source of the leak in the vanity cabinet of unit 2.
not activeSep 12, 2014
interior surfaces section · repair or replace the vanity cabinet 1001l sfhc
repair/remove/replace the vanity sink cabinet in unit 2.
not activeSep 12, 2014
interior surfaces section · provide a working door knob 1001d, j sfhc
provide a working door knob for the closet door in unit 2.
not activeSep 12, 2014
interior surfaces section · repair damaged walls 1001b, d, h sfhc
in unit 2 the walls shall be properly plastered as necessary to close the gaps, cracks and holes. after closing all gaps and holes, these walls are to be primed and painted to a durable and cleanable surface.
not activeSep 12, 2014
interior surfaces section · repair or replace the vanity cabinet 1001l sfhc
repair/remove/replace the vanity sink cabinet in unit 1.
not activeSep 12, 2014
interior surfaces section · replace window sash cords 1001h, 708 sfhc
replace the missing sash cords in unit 1.
not activeSep 12, 2014
interior surfaces section · repair damaged ceilings 1001b, d, j sfhc
in the second floor shower room, the ceiling shall be properly plastered as necessary to close the gaps, cracks and holes. after closing all gaps and holes, these areas are to be primed and painted to a durable and cleanable surface.
not activeSep 12, 2014
other section · inspector comments
it is the property owner's responsibility to be present or direct his/her representative to attend the re-inspection as scheduled on this notice of violation for the purpose of providing entry to the inspector of those areas not accessed during the initial inspection as specified, and/or to provide access to all areas cited within this notice. if the property owner cannot attend the scheduled re-inspection (as specified on this notice) it is his/her responsibility to secure a different inspection date and time with the inspector, and provide all tenants with notification as required by california civil code section 1954 (san francisco housing code section 303(b), if any dwellings, apartment units or guest rooms are to be accessed during the re-inspection.
not activeMar 25, 2014
building section · this notice includes violations for the areas noted.
common area of subject property.
not activeMar 25, 2014
building section · provide grab bars (505 (j) hc)
provide grab bars in all community bathrooms, including water-closet, lavatory and bathing facilities.
not activeMar 25, 2014
building section · building permit required (301 hc)
building permit required for above installation of grab bars.
not activeMar 25, 2014
other section · inspector comments
it is the property owner's responsibility to be present or direct his/her representative to attend, the reinspection as scheduled on this notice of violation for the purpose of providing entry to the inspector of those areas not accessed during the initial inspection as specified, and/or to provide access to all areas cited within this notice. if the property owner cannot attend the scheduled reinspection (as specified on this notice) it is his/her responsibility to secure a different inspection date and time with the inspector, and provide all tenants with notification as required by california civil code section 1954 (san francisco housing code section 303(b), if any dwellings, apartment units or guest rooms are to be accessed during the reinspection
not activeNov 19, 2008
building section · this notice includes violations for the areas noted.
all common areas of 284 golden gate avenue.
not activeNov 19, 2008
building section · other building violations
provide locking mailboxes for each residential unit (sec 1002 hc) *note* if mailboxes are wall mounted no building permit is required. if mailboxes are recessed in the wall a building permit is required. contact the u.s postal service for information regarding approved mailboxes.
not activeNov 19, 2008
other section · inspector comments
i have scheduled a reinspection of your building on monday, 22-december-2008 at 1:30 pm. reinspection of premise to include all areas referenced above. it is the property owner¿s responsibility to be present or direct his/her representative to attend, the reinspection as scheduled on this notice of violation for the purpose of providing entry to the inspector of those areas cited within this notice. if the property owner cannot attend the scheduled reinspection (as specified on this notice) it is his/her responsibility to secure a different inspection date and time with the inspector. on scheduled reinspection day, provide the inspector with a full access to all common and public areas per attached checklist. your cooperation is appreciated.
not activeMay 28, 2008
building section · this notice includes violations for the areas noted.
all common areas of 284 golden gate avenue
not activeMay 28, 2008
plumbing and electrical section · other plumbing and/or electrical violations
provide seismic braces to the hot water heater. (1001(f) hc) one approved strap required in upper 1/3 of tank and one in lower 1/3 of tank (4 inches above controls)
not activeMay 28, 2008
fire section · provide annual certification for central alarm system / panel (908, 909 hc)
the central alarm system must be tested and certified annually by a qualified professional vendor / electrical contractor. current certification must be visible and posted on the panel.
not activeMay 28, 2008
other section · post enclosed gas meter instructional diagram in a public area. (712 hc)
at gas metered area.
not activeMay 28, 2008
other section · provide shutoff tool for gas utility shutoff (712 hc)
at gas metered area.
not activeMay 28, 2008
other section · inspector comments
i have scheduled a reinspection of your building on friday, 27-june-2008 at 1:30 pm. reinspection of premise to include all areas referenced above. it is the property owner¿s responsibility to be present or direct his/her representative to attend, the reinspection as scheduled on this notice of violation for the purpose of providing entry to the inspector of those areas cited within this notice. if the property owner cannot attend the scheduled reinspection (as specified on this notice) it is his/her responsibility to secure a different inspection date and time with the inspector. on scheduled reinspection day, provide the inspector with a full access to all common and public areas per attached checklist. your cooperation is appreciated.
not activeAug 16, 2006
building section · replaster and paint walls and ceiling surfaces of common bathrooms,restrooms throughout the premises.1001hc./1301hc.
1)remove,contain and properly dispose of paint and plaster from walls and ceiling surfaces of public bathrooms and restrooms. 2)replaster,prime and paint walls and ceiling surfaces throughout.
not activeAug 16, 2006
building section · replace warn toilet seats to all commodes throughout the premises.1001hc./1306hc.
warn broken toilets seats in need to be replaced.
not activeAug 16, 2006
building section · install a mechanical ventilation system capable to provide 5 air changes per hour in each bathroom.504 (c) s.f.h.c.
1)hire the services of an electrical contractor and mechanical engineer in order to install a mechanical ventilation system in both common bathrooms.
not activeAug 16, 2006
building section · fire proof garbage storage areas in both public bathrooms.
1)line walls and ceiling surfaces of both garbage storage areas with 26 guage galvanized iron ( sheetmetal) all seems and joints shall be interlocking and tight. 2)install a sprinkle over the garbage recepticles.(plumbing permit required)
not activeJan 21, 2003
building section · this notice includes violations for the areas noted.
earle hotel, 284 golden gate ave.
not activeJan 21, 2003
fire section · failure to file for necessary permits in order to comply with the residential hotel sprinkler ordinance #170-02/904 s.f.h.c.
submit a building permit application with plans to the department of building inspection, within 7 days of this notice.
not activeOct 22, 2001
building section · this notice includes violations for the areas noted.
routine inspection of public, common areas and room to room inspection at 284 golden gate avenue.
not activeOct 22, 2001
sanitation section · clean or sanitize carpeting (1306 hc)
in room #14
not activeOct 22, 2001
fire section · permanently remove combustible storage or provide automatic fire sprinklers. (904, 1001(i) hc)
**hazardous condition** the following residential room are being used as a storage room: #3 and #4. remove excessive storage, combustible and boxes from rooms #3 and #4. provide clear access to windows for natural light, ventilation and emergency exit. note: the existing condition in rooms 3 & 4 are a life safety violations and must be corrected immediately.
not activeOct 22, 2001
plumbing and electrical section · provide designated moisture exhaust duct for dryer vent per attached mechanical code requirements. (504.3.1 umc)
note: dryer (forced air) exhaust vent pipe can not be connected to gravity water heater existing vent. restore connection to its original condition and comply with mechanical code requirements - see attached copy.
not activeOct 22, 2001
other section · inspector comments regarding reinspection:
i have scheduled a final reinspection of your hotel on 01/25/2002 at 10:30 am. reinspection of premise to include rooms #3 and #4. please call to confirm the time or day of reinspection. your cooperation is appreciated.
not activeMar 14, 2001
fire section · remove egress obstruction at fire escapes (801,1001(l) hc)
the path of egress from each apartment all the way to the street is to be kept clear of all obstructions at all times.
not activeMar 14, 2001
building section · remove roof deck ropes/wires or raise to 8' min (1001(b)(13) hc)
the wires/cables on the roof are a tripping hazard. they are to be removed or raised to a height of not less than 8 feet above the surface of the roof or safely attached to the sides of the building so as not to present a tripping hazard.
not activeMar 14, 2001
building section · repair window sash cords (1001(h) hc)
the sash cords in the windows of the public bathrooms/washrooms are to be repaired or replaced to ensure proper, safe operation of the windows.
not activeMar 14, 2001
smoke detection section · provide smoke detector at stairs (911 hc)
a battery operated smoke detector is to be fitted to the ceiling in the area of the penthouse door (the door that opens to the roof).
not activeMar 14, 2001
security requirements section · provide minimum 135 degree viewer for entry doors of following units (max mounting ht of 58") (706 hc)
all guestrooms are to be provided with viewfinder in the entry door. in addition all guestrooms are to be provided with identifying number.
not activeMar 14, 2001
security requirements section · other security violations
hasps are to be removed from doors/doorframes of those rooms where they are currently fitted. there are to be no hasps on guestroom entry doors at any time.
not activeMar 14, 2001
other section · inspector comments
the certificate of use (23 residential, 0 tourist), issued 04/26/1991, was posted in a public place within the hotel, as required. the weekly report was also posted but it was noted that the date on the weekly report was 10/29/2000. the weekly report is to be posted every monday for the previous week.
not activeMar 14, 2001
other section · inspector comments
the exterior door of the public bathroom/washroom (on the lower floor of the hotel) that opens to the fire escape on the side of the building is to be permanently unlocked as occupants of the top floor who flee from a fire by means of this fire escape will require unhindered access to the lower floor in order to make a safe exit from the hotel.
not activeDec 17, 1999
fire section · replace smoke enclosure door closer (807,707 hc)
as needed throughout.
not activeDec 17, 1999
security requirements section · provide sliding glass doors with auxiliary locking device in addition to primary locking device at following locations (706 hc)
privacy locks @ bathroom doors as needed throughout.
not activeMar 5, 1999
security requirements section · other security violations
repair defective deadlatch at penthouse door (roof door).
not activeMar 5, 1999
smoke detection section · provide smoke detector (908,911 hc)
battery smoke detector in units such as 7,6,21 and 24