OpenMar 18, 2022
building section · this notice includes violations for the areas noted.
common areas
OpenMar 18, 2022
building section · comply with self certification affidavit for smoke alarms and carbon monoxide detectors (420.4, 907.2.11, 3401.6.1 sfbc)
return the self certification affidavit to the address listed at the bottom of the form or hand it to the inspector on scheduled re-inspection date.
OpenMar 18, 2022
building section · comply with section 604 of the san francisco housing code(604 hc)
please provide the department of building inspection(dbi) with a completed compliance affidavit for section 604 of the san francisco housing code (see attached notice & affidavit). please disregard if you have already submitted you affidavit as required. to verify dbi receipt of your affidavit you may call or email clerical supervisor bernedette perez at 415 558-6165, or bernadette.perez@sfgov.org
OpenMar 18, 2022
fire section · recharge/date tag fire extinguisher type 2a 10bc or equivalent (905,1001(m)hc)
fire extingushers are tags are out of date. have a certified company recharge and provide new tags.
OpenMar 18, 2022
other section · inspector comments
nuisance (401(2) (1001(d) hc) it is the property owner's responsibility to be present or direct his/her representative to attend the reinspection as scheduled on this notice of violation for the purpose of providing entry to the inspector of those areas not accessed during the initial inspection as specified, and/or to provide access to all areas cited within this notice. if the property owner cannot attend the scheduled reinspection (as specified on this notice) it is his/her responsibility to secure a different inspection time/date with the inspector, and provide all tenants with notification as required by california civil code section 1954 (san francisco housing code section 303(b)), if any dwellings, apartment units or guest rooms are to be accessed during the reinspection.
not activeMar 9, 2022
building section · this notice includes violations for the areas noted.
284 golden gate st. apt#18
not activeMar 9, 2022
other section · provide heat to each occupied habitable sro room for 13 hrs between 5:00 a.m. and 11:00 a.m. and between 3:00 p.m. and 10:00 p.m. capable to maintaining a min. room temp. of 68 degrees f. (20 degrees c.). (701c hc)
no heat source was found in unit during inspection. provide heat per the housing code minimium requirements.
not activeMar 9, 2022
other section · inspector comments
nuisance (401(2) (1001(d) hc) it is the property owner's responsibility to be present or direct his/her representative to attend the reinspection as scheduled on this notice of violation for the purpose of providing entry to the inspector of those areas not accessed during the initial inspection as specified, and/or to provide access to all areas cited within this notice. if the property owner cannot attend the scheduled reinspection (as specified on this notice) it is his/her responsibility to secure a different inspection time/date with the inspector, and provide all tenants with notification as required by california civil code section 1954 (san francisco housing code section 303(b)), if any dwellings, apartment units or guest rooms are to be accessed during the reinspection.
not activeSep 12, 2014
building section · this notice includes violations for the areas noted.
this notice includes violations of the san francisco housing code. unless noted otherwise, all violations were observed on the date of inspection at 284 golden gate avenue.
not activeSep 12, 2014
building section · repair or replace the brick chimney and flue lining 1001g sfhc
the chimney behind the roof access penthouse has been compromised. there are partial courses of brick and sections of clay flue liner missing. repair or replace this chimney to support the mechanical systems below in an approved manner.
not activeSep 12, 2014
building section · building permit required (301 hc)
you are required to obtain a building permit to correct this violation. when applying for a building permit, reference the complaint number from this notice of violation. the building inspector must perform periodic and final inspections and sign the job card before the housing division can abate this violation.
not activeSep 12, 2014
building section · provide weather proofing at roof (1001(h),703 hc)
the roof access penthouse roofing material is re-directing water into the flue of the brick chimney. once the conditions of the chimney have been resolved a weather proof roofing condition shall be offered to correct this problem.
not activeSep 12, 2014
plumbing and electrical section · make necessary repairs to shower 1001f sfhc
the third floor shower has a crack through the fiberglass material causing a leak situation. repair, restore or replace the shower stall to provide a water tight finish with a sanitary, smooth, cleanable surface finish.
not activeSep 12, 2014
fire section · remove egress obstruction 801, 1001(l) sfhc
remove the television and trash cans from the third floor landing. the trash cans should be in an approved indoor trash area or open to blue sky.
not activeSep 12, 2014
plumbing and electrical section · provide a cover plate 1001e sfhc
in unit 22 there is an open junction box for a light switch near the sink basin. provide an approved cover plate.
not activeSep 12, 2014
plumbing and electrical section · repair sink (1001f hc)
in unit 24 there is an active leak at the sink faucet and in the p trap. find the source of each leak and repair as necessary.
not activeSep 12, 2014
plumbing and electrical section · replace broken glass window panes 1001h, 708 sfhc
in unit 24, replace the broken glass panel in the window.
not activeSep 12, 2014
plumbing and electrical section · repair window sash frame 1001h, 708 sfhc
in unit 24, repair the window sash frame. insure that the sash and frame provide smooth and easy operation and a weather tight condition with a working latch. window is to remain at any desired open position with the balance of a counter weight.
not activeSep 12, 2014
plumbing and electrical section · replace window sash cords 1001h, 708 sfhc
replace the missing/broken sash cords in unit 24.
not activeSep 12, 2014
plumbing and electrical section · replace the missing tile 1001b, d, j sfhc
in the third floor toilet room there is a missing ceramic tile creating an insanitary condition that cannot be cleaned properly. replace the missing tile and finish as necessary.
not activeSep 12, 2014
plumbing and electrical section · replace window sash cords 1001h, 708 sfhc
in the third floor toilet and tub room, replace the missing sash cords and counter balances. insure that the sash and frame provide smooth and easy operation and a weather tight condition with a working latch. window is to remain at any desired open position with the balance of a counter weight.
not activeSep 12, 2014
plumbing and electrical section · repair damaged walls 1001 b, d, h, 1301 sfhc
in unit 25 under the window, the wall shall be properly plastered as necessary to close all gaps, cracks and holes. after repairing, these walls are to be primed and painted to a durable and cleanable surface.
not activeSep 12, 2014
plumbing and electrical section · repair damaged walls 1001 b, d, h, 1301 sfhc
in unit 27 behind the door, the wall shall be properly plastered as necessary to close all gaps, cracks and holes. after repairing, these walls are to be primed and painted to a durable and cleanable surface.
not activeSep 12, 2014
sanitation section · repair damaged ceilings 1001 b ,d, h, 1301 sfhc
in unit 27, the ceiling shall be properly plastered as necessary to close all gaps, cracks and holes. after repairing, these areas are to be primed and painted to a durable and cleanable surface.
not activeSep 12, 2014
sanitation section · repair the leaking faucet 1001f sfhc
in unit 27 the hot water faucet has a steady stream with the faucet handle turned all the way off. repair or replace the faucet as necessary.
not activeSep 12, 2014
sanitation section · repair the leaking faucet 1001f sfhc
in unit 17 the hot water supply line has a leak. repair or replace this supply line as necessary to fix the leak.
not activeSep 12, 2014
sanitation section · provide adequate lighting 504g sfhc
in the south end of the hallway of the third floor near the fire escape, there is a missing light bulb. replace the light bulb to provide adequate lighting to this area.
not activeSep 12, 2014
sanitation section · provide adequate lighting 504g sfhc
provide a fixture at the landing between the second and third floor to provide adequate lighting to this area.
not activeSep 12, 2014
sanitation section · remove the unsecured carpet 1001b, d, j sfhc
the loose area rugs at the top of the stairs create a trip hazard. remove the area rugs and provide a secured, durable and cleanable floor surface.
not activeSep 12, 2014
sanitation section · repair damaged ceilings 1001 b ,d, h, 1301 sfhc
in unit 26, the ceiling shall be properly plastered as necessary to close all gaps, cracks and holes. after repairing, these areas are to be primed and painted to a durable and cleanable surface.
not activeSep 12, 2014
sanitation section · repair damaged walls 1001 b ,d, h, 1301 sfhc
in unit 26, the walls around the p trap shall be properly plastered as necessary to close all gaps, cracks and holes. after repairing, this area is to be primed and painted to a durable and cleanable surface.
not activeSep 12, 2014
sanitation section · replace the broken weather stripping 1001d sfhc
at the front door to guest room 26, replace the broken weather stripping.
not activeSep 12, 2014
sanitation section · remove the egress obstruction 801, 1001l sfhc
remove the hasps and pad lock on the guest room 20 entry door.
not activeSep 12, 2014
interior surfaces section · repair the damaged walls 1001 b, d, j
in unit 19, the walls behind the door shall be properly plastered as necessary to close all gaps, cracks and holes. after repairing, this area is to be primed and painted to a durable and cleanable surface.
not activeSep 12, 2014
interior surfaces section · replace floor covering (1001b,j,o hc)
in units 1, 2, 7, 8, 9, 17, 19, 26 and in the common hallway areas shrinkage of the wood flooring has created gaps which provide areas of potential harborage for vermin and creates an insanitary condition. this condition can not be cleaned properly. repair/restore or provide new flooring of the owner's choosing to create a smooth, durable and cleanable surface. acceptable alternatives include but are not limited to wood, tile, vct, linoleum or carpet.
not activeSep 12, 2014
interior surfaces section · provide adequate lighting 504g sfhc
provide a light bulb and insure the ceiling fixture works properly in unit 17.
not activeSep 12, 2014
interior surfaces section · replace window sash cords 1001h, 708 sfhc
in unit 17, the bay of 3 windows requires sash cords in all locations.
not activeSep 12, 2014
interior surfaces section · replace broken window glass 1001h, 708 sfhc
in the bay of 3 windows in unit 17, there are 2 panels of broken glass. replace the broken panels of glass.
not activeSep 12, 2014
interior surfaces section · repair the damaged ceiling 1001 b, d, j
in unit 15, find and fix the source of the leak causing the ceiling to fall. the ceiling shall be properly plastered as necessary to close all gaps, cracks and holes. after repairing, this area is to be primed and painted to a durable and cleanable surface.
not activeSep 12, 2014
interior surfaces section · remove egress obstruction 801, 1001l sfhc
reduce/remove/relocate the storage of personal belongings behind the door in unit 15 to allow free and easy exiting.
not activeSep 12, 2014
interior surfaces section · provide adequate lighting 504g sfhc
provide a light bulb and insure the ceiling fixture works properly in unit 15.
not activeSep 12, 2014
interior surfaces section · remove egress obstruction 801, 1001l sfhc
reduce/remove/relocate the storage of personal belongings behind the door in unit 14 to allow free and easy exiting.
not activeSep 12, 2014
interior surfaces section · provide a working door knob 1001d, j sfhc
provide a working door knob to the guest room number 14.
not activeSep 12, 2014
security requirements section · replace broken glass panes 1001h, 708 sfhc
replace the broken glass panel in unit 9 window.
not activeSep 12, 2014
security requirements section · replace window sash cords 1001h sfhc
in unit 9 replace the missing window sash cords.
not activeSep 12, 2014
security requirements section · repair damaged walls 1001b, d, j sfhc
in unit 9 the wall shall be properly plastered as necessary to close the gaps, cracks and holes. after closing all gaps and holes, these walls are to be primed and painted to a durable and cleanable surface.
not activeSep 12, 2014
security requirements section · repair damaged ceilings 1001b, d, j sfhc
in unit 9 the ceiling shall be properly plastered as necessary to close the gaps, cracks and holes. after closing all gaps and holes, these areas are to be primed and painted to a durable and cleanable surface.
not activeSep 12, 2014
security requirements section · replace window sash cords 1001h sfhc
in unit 8 replace the missing window sash cords.
not activeSep 12, 2014
security requirements section · repair damaged ceilings 1001b, d, j sfhc
in unit 8 the ceiling above the sink shall be properly plastered as necessary to close the gaps, cracks and holes. after closing all gaps and holes, these areas are to be primed and painted to a durable and cleanable surface.
not activeSep 12, 2014
security requirements section · remove egress obstruction 801, 1001l sfhc
reduce/remove/relocate the storage of personal belongings behind the door in unit 8 to allow free and easy exiting.