stoop
MAP
LeaderboardAbout

62 TURK ST

Tenderloin · San Francisco, CA · Parcel 0340009 · Last violation Aug 18, 2025 · Last complaint Aug 13, 2026

NeighborhoodTenderloin
Above-average violations for the neighborhood
More violations than 71% of buildings and more complaints than 80% of buildings in Tenderloin. Size-normalized against residential buildings in the neighborhood.
ViolationsComplaints
Activity TrendsLast 5 years
A steady level of activity over time
Last 2 yrs: 6 violations · 12 complaints
'23'26ViolationsComplaints
Severityⓘopen violations
All DBI violations have been resolved
Notices of Violation issued by the Department of Building Inspection, by current status.
Severe0
Serious0
Minor0
311 Housing Complaints
Total complaints since 2010
25
1 per year avg.↑ Up 1100% in the last 2 years (12 vs 1 prior 2 yrs)
Complaint severity
Last 5 years
13
Severeⓘ2
Seriousⓘ8
Minorⓘ3
Dept. of Building Inspection Violations
Total violations since 1996
209
7 per year avg.↑ Rising — no prior history
Open violations
0
No open DBI violations on record.

Top violation categories

5 yrsAll time
interior surfaces section3 violations
building section1 violations
other section1 violations
sanitation section1 violations

Top complaint types

5 yrsAll time
Infestation Rodent Insect4 complaints
General Maintenance Not In List Above3 complaints
Mold And Mildew2 complaints
Infestation Bed Bugs1 complaints
Hot Water Lack Of Hot Water1 complaints
Fire Hazard1 complaints
Bathroom1 complaints
Hide violations (209) ↑See complaints (25) →

Violation log

209 DBI violations

AllOpenClosed
StatusFiledCategoryItemNOV Item Description
not activeAug 29, 2000other sectionmiscellaneous violationsrestore bathrooms next to or adjacent to room # 323, 206. addendum 02/02/2001 no entry to rooms # 607, 619, 620, 301, 302, 304, 307, 323, 209, 215, 216, 103. repair smoke detectors (sfhc 908,911) at rooms #609, 617, 618, 623, 514, 511, 507, 407, 410, 420, 303, 310, 314, 318, 315, 207, 211, 221, 218, 221, 102, 103, 104, 105. repair sink at rooms (sfhc 1001) # 609, 617, 517, 511, 333, 314. remove pad locks from rooms (sfhc 801) # 619, 301, 302, 304, 222, repair radiator (heat) (sfhc 701) at room # 522 . repair broken glass at fire extinguisher cabinet (sfhc 905) next to room # 608. repair light to rear stairway between 5and 6 floor. repair window (sfhc 1001 at room # 517 (window and frame has been removed). repair broken window (sfhc 1010 ) at room # 518. repair damaged ceiling (sfhc 1001,1301) at room # 420 restore windows to rooms (sfhc 1001, 504,707,1010) # 101, 102, 104, 105. (windows are boarded up, eliminating light and ventilation. remove rubbish from lightwell below rooms # 511(eastside) and 518 (westside). provide certification for central alarm system. reinspection 02/22/2001 at 1:00 p.m.
See something wrong? File a complaint with SF 311
not activeAug 29, 2000interior surfaces sectionrepair damaged ceilings (1001b,h,o hc)repair water damaged ceiling at rooms #402, 412, 311 . repair water damaged ceiling at lobby next to room #101.
not activeAug 29, 2000building sectionbuilding permit required (301 hc)provide a building permit for repair of fire damaged at room # 408. provide a building permit for a mechanical ventilation system at bathrooms next to or adajacent to rooms #107, 108.
not activeAug 29, 2000plumbing and electrical sectionother plumbing and/or electrical violationsrepair bath tub faucet next to room # 623.
not activeAug 29, 2000interior surfaces sectionpaint ceilings (1001b,1301 hc)repair peeling paint at ceiling -rooms # 504, 502, 308, 210 . repair damaged ceiling at bathroom adjacent to room # 607, 522, 407, 420, 320, 307, 220, repair peeling at floors at bathrooms adjacent to rooms # 607, 623, 522, 407, 307, 107, 108.
not activeAug 29, 2000other sectioninspector commentsno entry to rooms # 601, 605, 607, 609, 617, 619, 618, 623, 620, 525, 518, 514, 517, 511, 507, 407, 409, 410, 420, 318, 323, 314, 312, 310, 315, 333, 309, 307, 303, 301, 302, 304, 207, 211, 209, 215, 221, 216, 222, 218, 221, 101, 102, 103, 104, 105, 108. no entry to managers rooms # 204, 202, 201, 203, 205, 206.
not activeAug 29, 2000building sectionrepair stairs (1001(b)(13)hc)repair lose step at main stairway adjacent to room # 307 (between second and third floor).
not activeAug 29, 2000building sectionrepair window sash cords (1001(h) hc)repair sash cords at bathrooms adjacent to or next to rooms # 220, 423,
not activeDec 28, 1999fire sectionprovide date tag for fire extinguisher type 2a 10bc or equivalent (905, 1001(m) hc)missing by #411
not activeDec 28, 1999fire sectionremove egress obstruction at (801,1001(l) hc)rubbish/trash fire escape and xmas lights
not activeJun 2, 1999fire sectionother fire violationscover transom to entry door room 623 with material to maintain 1 hour fire rated corridor h.c 807
not activeJun 2, 1999smoke detection sectionprovide smoke detector (908,911 hc)at top of stairs to roof
not activeJun 2, 1999security requirements sectionother security violationsdoor handle rooms 516,505
not activeJun 2, 1999fire sectionprovide fire extinguisher type 2a 10bc or equivalent.(905, 1001(m)hc)3rd floor and 4th floor
not activeJun 2, 1999interior surfaces sectionpaint ceilings (1001b,1301 hc)patch and paint ceilings in the following rooms:622,620,601,317,211,8, shower room across from 622
not activeJun 2, 1999interior surfaces sectiondisturbing lead based paint can be extremely dangerous to dwelling occupants and visitors, particularly to young children, pregnant women, pets, and to people performing work on the premises. for interior or exterior paint removal : always wet the surface, contain and properly dispose of leaded paint. if you are unsure whether the paint is leaded, you should test it prior to performing any work. if the paint is found to contain lead, you should consult with an expert about appropriate procedures. proper containment and 3-day notification is required for exterior jobs of more than 10 sq.ft. (sec.3604, sfbc) informational packets are available at (415) 558-6088. you can contact the san francisco childhood lead poisoning prevention program at: (415) 554-8930 for free advice. if you cause lead dust to be created, you could be liable for any illness caused by the dust. ordinance #446-97.—
not activeJun 2, 1999plumbing and electrical sectionprovide adequate lighting (504g hc)rear staircase to roof porvide light bulb and rear staircase between 5th and 6th floor provide light bulb
not activeJun 2, 1999interior surfaces sectionrepair damaged walls (1001b,h,o hc)—
not activeJun 2, 1999interior surfaces sectionreplace floor covering (1001b,j,o hc)provide floor covering or sand and paint floor in the following rooms:633, 210,8,6th floor bathroom next to 601
not activeJun 2, 1999interior surfaces sectionpaint walls (1001b,1301 hc)patch and paint walls in the following rooms:514,516,317,8
not activeJun 2, 1999security requirements sectionprovide minimum 135 degree viewer for entry doors of following units (max mounting ht of 58") (706 hc)room 408
not activeJun 2, 1999smoke detection sectionrepair smoke detector (908 911 hc)repair or replace smoke detectors in all guest rooms including: 621,620,618,616,615,522,519,516,514,501,410,316,311,303, 221,214
not activeJun 2, 1999sanitation sectioneliminate cockroach infestation (1001b, 1306 hc)—
not activeJun 2, 1999security requirements sectionprovide self-closing devices at exterior doors (706 hc)provide self closing deveces on all doors opening onto corridors including 4th floor bathroom, 3rd floor bathroom (next to 307) shower room door next to room 8
not activeJun 2, 1999plumbing and electrical sectionother plumbing and/or electrical violationsrepair leaking radiator 407 1001 h.c.
not activeJun 2, 1999plumbing and electrical sectionrepair sink (1001f hc)repair or replace leaking faucet room 407
not activeJun 2, 1999other sectionmiscellaneous violationsdiscontinue cooking in all guest rooms including 218,521,621 h.c.
not activeJun 2, 1999building sectionrepair stairs (1001(b)(13)hc)main staircase from lobby to 2nd floor 3rd and 4th steps from the bottom, rear staircase to the roof: repair tread covering where covering is found to be torn.
not activeJun 2, 1999building sectionrepair handrails (802(c),1001(b)(13)hc)repair handrail on main staircase form lobby to 2nd floor
not activeJun 2, 1999fire sectioninstall directional signs at (801, 1001(m) hc)4th floor,provide exit sign on corridor door next to elevator
not activeApr 29, 1998interior surfaces sectionrepair damaged ceilings (1001b,h,o hc)in unit #602 & common hall by unit #609.
not activeApr 29, 1998interior surfaces sectionrepair damaged walls (1001b,h,o hc)in unit #602.
not activeApr 29, 1998interior surfaces sectiondisturbing lead based paint can be extremely dangerous to dwelling occupants and visitors, particularly to young children, pregnant women, pets, and to people performing work on the premises. for interior or exterior paint removal : always wet the surface, contain and properly dispose of leaded paint. if you are unsure whether the paint is leaded, you should test it prior to performing any work. if the paint is found to contain lead, you should consult with an expert about appropriate procedures. proper containment and 3-day notification is required for exterior jobs of more than 10 sq.ft. (sec.3604, sfbc) informational packets are available at (415) 558-6088. you can contact the san francisco childhood lead poisoning prevention program at: (415) 554-8930 for free advice. if you cause lead dust to be created, you could be liable for any illness caused by the dust. ordinance #446-97.where work is required.
not activeApr 29, 1998interior surfaces sectionremove or cover damaged paint in an approved manner to prevent a lead hazard. see attached lead hazard warning. (1301 hc)where work is required.
not activeApr 29, 1998interior surfaces sectionpaint walls (1001b,1301 hc)where work is rquired.
not activeApr 29, 1998security requirements sectionother security violationsprovide deadlatch & assure complete self-closing of front door of unit #602. 706hc provide deadlatches & assure complete closing of all fire exit doors on all floors. 706hc
not activeApr 29, 1998plumbing and electrical sectionrepair sink (1001f hc)provide sink in unit #602.
not activeApr 29, 1998fire sectionprovide date tag for fire extinguisher type 2a 10bc or equivalent (905, 1001(m) hc)on 4th floor.
not activeApr 29, 1998sanitation sectionclean or sanitize (1306 hc)pigeon feces from window ledges & fire escape on 6th floor off room 602.
not activeApr 29, 1998sanitation sectionremove rubbish or trash (1306,1307 hc)rear stairs & back lightwell area.
not activeApr 29, 1998building sectionrepair window sash frame (1001(h),708 hc)provide window sash for window located off 6th floor landing.
not activeApr 29, 1998interior surfaces sectionpaint ceilings (1001b,1301 hc)where work is required.
not activeApr 29, 1998interior surfaces sectionrepair source of water damage (703,1001f hc)prior to any implementation of cosmetic repairs.
not activeApr 29, 1998interior surfaces sectionlocate source of water damage (703, 1001f hc)prior to implementation of any cosmetic repairs.
not activeNov 24, 1997fire sectionrecharge/date tag fire extinguisher type 2a 10bc or equivalent (905,1001(m)hc)recharge all expired fire extinguishers in the public hallways.
not activeJul 15, 1997building sectionreplace broken glass window pane (1001(h),708 hc)unit # 6.
not activeJul 15, 1997smoke detection sectionreplace smoke detector (908, 911 hc)repair/replace smoke detectors in unit # 605, 518, 510, 508, 410, 416, 418, 323, 319, 317, 208, 217 & 4.
not activeJul 15, 1997fire sectionremove egress obstruction at (801,1001(l) hc)remove grocery push cart at 5th floor hallways. remove pad lock at entry door of unit # 304 & 619.
not activeMay 22, 1997other sectioninspector commentsno violations.
not activeMay 8, 1997building sectionreplace broken glass window pane (1001(h),708 hc)hotel 3rd hallway - replace broken glass in the lightwell window. 1001 hc.
not activeAug 29, 2000
other section · miscellaneous violations
restore bathrooms next to or adjacent to room # 323, 206. addendum 02/02/2001 no entry to rooms # 607, 619, 620, 301, 302, 304, 307, 323, 209, 215, 216, 103. repair smoke detectors (sfhc 908,911) at rooms #609, 617, 618, 623, 514, 511, 507, 407, 410, 420, 303, 310, 314, 318, 315, 207, 211, 221, 218, 221, 102, 103, 104, 105. repair sink at rooms (sfhc 1001) # 609, 617, 517, 511, 333, 314. remove pad locks from rooms (sfhc 801) # 619, 301, 302, 304, 222, repair radiator (heat) (sfhc 701) at room # 522 . repair broken glass at fire extinguisher cabinet (sfhc 905) next to room # 608. repair light to rear stairway between 5and 6 floor. repair window (sfhc 1001 at room # 517 (window and frame has been removed). repair broken window (sfhc 1010 ) at room # 518. repair damaged ceiling (sfhc 1001,1301) at room # 420 restore windows to rooms (sfhc 1001, 504,707,1010) # 101, 102, 104, 105. (windows are boarded up, eliminating light and ventilation. remove rubbish from lightwell below rooms # 511(eastside) and 518 (westside). provide certification for central alarm system. reinspection 02/22/2001 at 1:00 p.m.
not activeAug 29, 2000
interior surfaces section · repair damaged ceilings (1001b,h,o hc)
repair water damaged ceiling at rooms #402, 412, 311 . repair water damaged ceiling at lobby next to room #101.
not activeAug 29, 2000
building section · building permit required (301 hc)
provide a building permit for repair of fire damaged at room # 408. provide a building permit for a mechanical ventilation system at bathrooms next to or adajacent to rooms #107, 108.
not activeAug 29, 2000
plumbing and electrical section · other plumbing and/or electrical violations
repair bath tub faucet next to room # 623.
not activeAug 29, 2000
interior surfaces section · paint ceilings (1001b,1301 hc)
repair peeling paint at ceiling -rooms # 504, 502, 308, 210 . repair damaged ceiling at bathroom adjacent to room # 607, 522, 407, 420, 320, 307, 220, repair peeling at floors at bathrooms adjacent to rooms # 607, 623, 522, 407, 307, 107, 108.
not activeAug 29, 2000
other section · inspector comments
no entry to rooms # 601, 605, 607, 609, 617, 619, 618, 623, 620, 525, 518, 514, 517, 511, 507, 407, 409, 410, 420, 318, 323, 314, 312, 310, 315, 333, 309, 307, 303, 301, 302, 304, 207, 211, 209, 215, 221, 216, 222, 218, 221, 101, 102, 103, 104, 105, 108. no entry to managers rooms # 204, 202, 201, 203, 205, 206.
not activeAug 29, 2000
building section · repair stairs (1001(b)(13)hc)
repair lose step at main stairway adjacent to room # 307 (between second and third floor).
not activeAug 29, 2000
building section · repair window sash cords (1001(h) hc)
repair sash cords at bathrooms adjacent to or next to rooms # 220, 423,
not activeDec 28, 1999
fire section · provide date tag for fire extinguisher type 2a 10bc or equivalent (905, 1001(m) hc)
missing by #411
not activeDec 28, 1999
fire section · remove egress obstruction at (801,1001(l) hc)
rubbish/trash fire escape and xmas lights
not activeJun 2, 1999
fire section · other fire violations
cover transom to entry door room 623 with material to maintain 1 hour fire rated corridor h.c 807
not activeJun 2, 1999
smoke detection section · provide smoke detector (908,911 hc)
at top of stairs to roof
not activeJun 2, 1999
security requirements section · other security violations
door handle rooms 516,505
not activeJun 2, 1999
fire section · provide fire extinguisher type 2a 10bc or equivalent.(905, 1001(m)hc)
3rd floor and 4th floor
not activeJun 2, 1999
interior surfaces section · paint ceilings (1001b,1301 hc)
patch and paint ceilings in the following rooms:622,620,601,317,211,8, shower room across from 622
not activeJun 2, 1999
interior surfaces section · disturbing lead based paint can be extremely dangerous to dwelling occupants and visitors, particularly to young children, pregnant women, pets, and to people performing work on the premises. for interior or exterior paint removal : always wet the surface, contain and properly dispose of leaded paint. if you are unsure whether the paint is leaded, you should test it prior to performing any work. if the paint is found to contain lead, you should consult with an expert about appropriate procedures. proper containment and 3-day notification is required for exterior jobs of more than 10 sq.ft. (sec.3604, sfbc) informational packets are available at (415) 558-6088. you can contact the san francisco childhood lead poisoning prevention program at: (415) 554-8930 for free advice. if you cause lead dust to be created, you could be liable for any illness caused by the dust. ordinance #446-97.
not activeJun 2, 1999
plumbing and electrical section · provide adequate lighting (504g hc)
rear staircase to roof porvide light bulb and rear staircase between 5th and 6th floor provide light bulb
not activeJun 2, 1999
interior surfaces section · repair damaged walls (1001b,h,o hc)
not activeJun 2, 1999
interior surfaces section · replace floor covering (1001b,j,o hc)
provide floor covering or sand and paint floor in the following rooms:633, 210,8,6th floor bathroom next to 601
not activeJun 2, 1999
interior surfaces section · paint walls (1001b,1301 hc)
patch and paint walls in the following rooms:514,516,317,8
not activeJun 2, 1999
security requirements section · provide minimum 135 degree viewer for entry doors of following units (max mounting ht of 58") (706 hc)
room 408
not activeJun 2, 1999
smoke detection section · repair smoke detector (908 911 hc)
repair or replace smoke detectors in all guest rooms including: 621,620,618,616,615,522,519,516,514,501,410,316,311,303, 221,214
not activeJun 2, 1999
sanitation section · eliminate cockroach infestation (1001b, 1306 hc)
not activeJun 2, 1999
security requirements section · provide self-closing devices at exterior doors (706 hc)
provide self closing deveces on all doors opening onto corridors including 4th floor bathroom, 3rd floor bathroom (next to 307) shower room door next to room 8
not activeJun 2, 1999
plumbing and electrical section · other plumbing and/or electrical violations
repair leaking radiator 407 1001 h.c.
not activeJun 2, 1999
plumbing and electrical section · repair sink (1001f hc)
repair or replace leaking faucet room 407
not activeJun 2, 1999
other section · miscellaneous violations
discontinue cooking in all guest rooms including 218,521,621 h.c.
not activeJun 2, 1999
building section · repair stairs (1001(b)(13)hc)
main staircase from lobby to 2nd floor 3rd and 4th steps from the bottom, rear staircase to the roof: repair tread covering where covering is found to be torn.
not activeJun 2, 1999
building section · repair handrails (802(c),1001(b)(13)hc)
repair handrail on main staircase form lobby to 2nd floor
not activeJun 2, 1999
fire section · install directional signs at (801, 1001(m) hc)
4th floor,provide exit sign on corridor door next to elevator
not activeApr 29, 1998
interior surfaces section · repair damaged ceilings (1001b,h,o hc)
in unit #602 & common hall by unit #609.
not activeApr 29, 1998
interior surfaces section · repair damaged walls (1001b,h,o hc)
in unit #602.
not activeApr 29, 1998
interior surfaces section · disturbing lead based paint can be extremely dangerous to dwelling occupants and visitors, particularly to young children, pregnant women, pets, and to people performing work on the premises. for interior or exterior paint removal : always wet the surface, contain and properly dispose of leaded paint. if you are unsure whether the paint is leaded, you should test it prior to performing any work. if the paint is found to contain lead, you should consult with an expert about appropriate procedures. proper containment and 3-day notification is required for exterior jobs of more than 10 sq.ft. (sec.3604, sfbc) informational packets are available at (415) 558-6088. you can contact the san francisco childhood lead poisoning prevention program at: (415) 554-8930 for free advice. if you cause lead dust to be created, you could be liable for any illness caused by the dust. ordinance #446-97.
where work is required.
not activeApr 29, 1998
interior surfaces section · remove or cover damaged paint in an approved manner to prevent a lead hazard. see attached lead hazard warning. (1301 hc)
where work is required.
not activeApr 29, 1998
interior surfaces section · paint walls (1001b,1301 hc)
where work is rquired.
not activeApr 29, 1998
security requirements section · other security violations
provide deadlatch & assure complete self-closing of front door of unit #602. 706hc provide deadlatches & assure complete closing of all fire exit doors on all floors. 706hc
not activeApr 29, 1998
plumbing and electrical section · repair sink (1001f hc)
provide sink in unit #602.
not activeApr 29, 1998
fire section · provide date tag for fire extinguisher type 2a 10bc or equivalent (905, 1001(m) hc)
on 4th floor.
not activeApr 29, 1998
sanitation section · clean or sanitize (1306 hc)
pigeon feces from window ledges & fire escape on 6th floor off room 602.
not activeApr 29, 1998
sanitation section · remove rubbish or trash (1306,1307 hc)
rear stairs & back lightwell area.
not activeApr 29, 1998
building section · repair window sash frame (1001(h),708 hc)
provide window sash for window located off 6th floor landing.
not activeApr 29, 1998
interior surfaces section · paint ceilings (1001b,1301 hc)
where work is required.
not activeApr 29, 1998
interior surfaces section · repair source of water damage (703,1001f hc)
prior to any implementation of cosmetic repairs.
not activeApr 29, 1998
interior surfaces section · locate source of water damage (703, 1001f hc)
prior to implementation of any cosmetic repairs.
not activeNov 24, 1997
fire section · recharge/date tag fire extinguisher type 2a 10bc or equivalent (905,1001(m)hc)
recharge all expired fire extinguishers in the public hallways.
not activeJul 15, 1997
building section · replace broken glass window pane (1001(h),708 hc)
unit # 6.
not activeJul 15, 1997
smoke detection section · replace smoke detector (908, 911 hc)
repair/replace smoke detectors in unit # 605, 518, 510, 508, 410, 416, 418, 323, 319, 317, 208, 217 & 4.
not activeJul 15, 1997
fire section · remove egress obstruction at (801,1001(l) hc)
remove grocery push cart at 5th floor hallways. remove pad lock at entry door of unit # 304 & 619.
not activeMay 22, 1997
other section · inspector comments
no violations.
not activeMay 8, 1997
building section · replace broken glass window pane (1001(h),708 hc)
hotel 3rd hallway - replace broken glass in the lightwell window. 1001 hc.
Page 4 of 5
← PrevNext →