stoop
MAP
LeaderboardAbout

62 TURK ST

Tenderloin · San Francisco, CA · Parcel 0340009 · Last violation Aug 18, 2025 · Last complaint Aug 13, 2026

NeighborhoodTenderloin
Above-average violations for the neighborhood
More violations than 71% of buildings and more complaints than 80% of buildings in Tenderloin. Size-normalized against residential buildings in the neighborhood.
ViolationsComplaints
Activity TrendsLast 5 years
A steady level of activity over time
Last 2 yrs: 6 violations · 12 complaints
'23'26ViolationsComplaints
Severityⓘopen violations
All DBI violations have been resolved
Notices of Violation issued by the Department of Building Inspection, by current status.
Severe0
Serious0
Minor0
311 Housing Complaints
Total complaints since 2010
25
1 per year avg.↑ Up 1100% in the last 2 years (12 vs 1 prior 2 yrs)
Complaint severity
Last 5 years
13
Severeⓘ2
Seriousⓘ8
Minorⓘ3
Dept. of Building Inspection Violations
Total violations since 1996
209
7 per year avg.↑ Rising — no prior history
Open violations
0
No open DBI violations on record.

Top violation categories

5 yrsAll time
interior surfaces section3 violations
building section1 violations
other section1 violations
sanitation section1 violations

Top complaint types

5 yrsAll time
Infestation Rodent Insect4 complaints
General Maintenance Not In List Above3 complaints
Mold And Mildew2 complaints
Infestation Bed Bugs1 complaints
Hot Water Lack Of Hot Water1 complaints
Fire Hazard1 complaints
Bathroom1 complaints
Hide violations (209) ↑See complaints (25) →

Violation log

209 DBI violations

AllOpenClosed
StatusFiledCategoryItemNOV Item Description
not activeMay 4, 2007fire sectionrepair fire proofing with approved materials (hc 1001(m), 809)repair all damaged wall and ceiling surfaces in the basement and boiler room. repairs can be made with 5/8" type x drywall, 26 guage sheet metal, cement board, or equivalent. edges must be fire taped or sealed with fire foam or fire caulk.
See something wrong? File a complaint with SF 311
not activeNov 30, 2005building sectioninstall sequential guestroom numbers to all entry doors.706hc./1001hc.—
not activeNov 30, 2005building section1)remove excessive construction debries, old furnishing, discarded household items from basement and storage room areas.1001hc. 2)contain all combustible paints, thinners, solvents in metal cabinets.1001hc.clothered basement/storage areas.
not activeNov 30, 2005building section1)remove plastic cover extended over smoke detectors in gr#317,614.1001hc. 2)install a cover over exposed wall switch in common bathroom adjacent to gr#623.,gr#623.1001hc. 3)repair/replace treshold in gr#605.1001hc.a variety of maintanance violations at various locations.
not activeNov 30, 2005building section1)install/adjust self closing devices/self latching devices and necessary hardware, to all common bathroom and toilet room door.912hc. 2)install self closing devices to each fire door leading to front exterior fire escape.712hc.common bathroom doors as well as hallway doors leading to fire excape are lacking door closures.
not activeNov 30, 2005building sectioninstall and date tag approoved type of fire extinguishers ( type 2a-10bc) or equivalent,on all floors as well as in the common areas.905hc.lack of hallway fire extinguishers.
not activeNov 30, 2005building sectionreplace all burnt out, missing bulbs from illuminated exit signs on the 5 th floor.1001h.c./801h.c.burnt out light bulbs in 5th floor exit sign.
not activeNov 30, 2005building section1)provide four gallon of hot water storage capacity per guestroom.sec. 505 d(4)s.f.h.c. 2)properly vent, strap and provide a trp drain line for the exisitng water heaters.1001hc.premises are currently lacking 300 gallons of hot water capacity.
not activeNov 30, 2005building section1)clean and sanitize gr#302,316,410,419,512,614.1306hc. 2)eliminate excessive storage, flamables in gr#302.1001hc 3)intensify pest control measures until roach,bed bugs and vermin infestation is under control.1001hc. 4)replace damaged,insanitary box spring and mattress in gr#401,614.1308hc. 5)remove and abate mold on wall surfaces in gr#614.1306hc.insanitary premises,filled with debries.
not activeNov 30, 2005building sectionrepair fireproofing to basement, storage room and boiler room ceiling surfaces with 5/8 of an inch sheetrock type x.1001hc.multiple holes along basement ceiling surfaces,in need of repairs.
not activeNov 30, 2005building section1)install a handrail on top of the stairs at the winding tread, connecting ground floor with basement area.1001hc. 2)secure loose existing railingto basement stairs.1001hc.lack of requiered handrail at top of basement stairs.
not activeFeb 8, 2005building section1)repair inoperative boiler unit. provide heat from : 5:00 am-11:00 am 3:00 pm-10:00 pm.sec. 701hc.inoperative boiler unit.lack of heat to the units.
not activeOct 21, 2004building section1)provide a toilet tank cover to all lavatories lacking same in each public bathroom/restroom.1001hc. 2)install privacy locks to each public tub room,6th floor toilet room.1001hc. 3)unstop drain,clean and sanitize public bathroom floor surfaces in: 3rd floor,4th floor,5th floor,6th floor public shower rooms.1001hc. 4)replace missing shower heads in 4th floor,5th floor,6th floor public shower rooms. 5)provide a drain cover in 4th floor shower room adjacent to hallway window.1001hc.insanitary,stoped up ,unmaintained public bathrooms.
not activeOct 21, 2004building section1)repair defective roof surfaces causing water damage to ceiling surfaces in gr#622.1001hc. 2)remove,contain and properly dispose of water damaged paint and plaster from ceiling surfaces in gr#622.1001hc. 3)replaster and paint afected ceiling surfaces throughout.1301hc.water damaged ceiling surfces in gr#622.
not activeOct 21, 2004building sectionrepair,putty,glaze and seal all loose ,rattling hallway windows along public hallways and stairways.1001hc.hallway window panes are loose and rattling.
not activeOct 21, 2004building sectionintensify pest and rodent control measures until roachesw,bedbugs,mice are under control.1001hc.repeated tenant complaints of severe infestation of pests and rodents throughout the premises.
not activeOct 21, 2004building section1)locate source and eliminate mold and mildew from walls and ceiling surfaces in : a)3rd floor public shower room. b)replaster and repair damaged wall surfaces in 3rd floor toilet room ,6th floor shower room above shower head. c)replaster and paint walls and ceilings of each and every public shower room/bathroom.1301hc.public bathrooms in need to be painted.
not activeOct 21, 2004building sectioncaulk and seal above,side of window seals causing water seepage in gr#620.1001hc.water seepage through window seal in gr#620.
not activeOct 21, 2004building sectionreplace missing handrail between 4th and 5th floors.1001hc.staircase between 4th and 5th floors are lacking requiered handrails.
not activeJul 7, 2004———
not activeFeb 17, 2004building sectionfloor surfaces in gr#622 were littered filled with debries in need to be cleaned.clean insanitary floor surfaces in gr#622.1306hc. 2)replace soiled water damaged carpeting.1306hc.
not activeJan 2, 2004building sectiondefective roof surfaces,causing overhead leaks to 6th floor hallway.1)have roof surfaces repaired by a licensed roofing contractor. 2)replace all water damaged plaster along hallway ceiling surfaces,with 5/8 of an inch sheetrock type x.1001hc.
not activeDec 8, 2003building sectionmissing handrail along secondary stairs.replace missing handrail to rear secondary stairs between 5th and 6th floors.1001hc
not activeDec 8, 2003building sectionmissing garbage chute cover.install missing garbage chute cover to 3rd floor hopper inlet.1001hc.
not activeDec 8, 2003building sectioninspectors comments.it is the property owner?s responsibility to be present or direct his/her representative to attend, the reinspection as scheduled on this notice of violation for the purpose of providing entry to the inspector of those areas not accessed during the initial inspection as specified, and/or to provide access to all areas cited within this notice. if the property owner cannot attend the scheduled reinspection (as specified on this notice) it is his/her responsibility to secure a different inspection date and time with the inspector, and provide all tenants with notification as required by california civil code section 1954 (san francisco housing code section 303(b)), if any dwellings, apartment units or guest rooms are to be accessed during the reinspection.
not activeDec 8, 2003building sectionlack of a requiered smoke detector in gr#421.install a smoke detector in gr#421.908hc.
not activeDec 8, 2003building sectionlack of privacy lock to 4th ,5th,6th floor public tub rooms.1)install a privacy lock,cover door openings on 4th, 5th, 6th floor tub rooms.1001hc. 2)install a privacy lock to 3rd floor toilet room.1001hc.
not activeDec 8, 2003building sectiondetached linoleum floor covering in front of public bathroom door across gr#522,#622.reglue detached vinyl floor covering in front of 5th,6th floor public shower rooms.1001hc.
not activeDec 8, 2003building sectionleaking roof surfaces causing ceiling damage to gr#622.1)repair leaking roof surfaces.1001hc. 2)resheetrock and paint damaged ceiling surfaces.1001hc./1301hc. 3)replace water damaged carpeting.1001hc. 4)clean premises throughout.1306hc.
not activeDec 8, 2003building sectionpeeling paint and plaster along hallway ceiling surfaces on 3rd through 6th floors.repair,replaster damaged portions of walls and ceiling surfaces in: 3rd floor hallway area above fire extinguisher across front interior stairs. 4th floor hallway wall surfaces adjacent to gr#409. 6th floor hallway wall surfaces side of #609. peeling wall surfaces,side of hallway stairs leading to roof.1001hc./1301hc.
not activeJun 11, 2003interior surfaces sectionrepair/patch hole in wall near window unit #603repair hole in wall #603 near window (1001hc)
not activeJun 11, 2003interior surfaces sectionremove cord wiring on roof leading to satelite dishremove cord wiring on roof (401hc)
not activeJun 11, 2003interior surfaces sectioninstall peephole in entry door unit #603install peephole entry door $603 (706(2)(vi)hc)
not activeJun 11, 2003interior surfaces sectionpatch hole in ceiling unit #603 caused by leaking roofpatch hole in ceiling and repaint entire ceiling (1001hc)
not activeJun 11, 2003interior surfaces sectionremove all debris from rear fire escaperemove egress obstructions rear fire escape (810hc)
not activeJun 11, 2003interior surfaces sectionclean and maintain all bathrooms throughoutmaintain all bathrooms in a sanitary manner (1001hc)
not activeJun 11, 2003interior surfaces sectionrepair roof above unit #603make repairs to roof above unit #603 to prevent further leakage (703hc)
not activeJun 6, 2003building sectionfailure to file for necessary permits in order to comply with the residential hotel sprinkler ordinance #170-02.submit a building permit application with plans to the department of building inspection within 15 days of this notice to comply with the residential hotel sprinkler ordinance #170-02, section 904 s.f.h.c.
not activeApr 9, 2003building sectioninsanitary,warn tubs,leaking drain line,bathroom floors in disrepair.1)replace warn,painted,chiped tubs on 4th,5th,6th floors.1001hc. 2)resurfaces and paint floor surfaces in each and every public restroom,shower room,tub room.1001hc. 3)replace door frame to 4th floor shower room.1001hc. 4)repair overhead leaks in 3rd floor shower room,causing ceiling damage to 2nd floor shower room.1001hc. replace water damaged bathroom ceiling with 5/8 of an inch sheetrock type x.1001hc.
not activeDec 6, 2002building sectioninoperative elevator.repair inoperative elevator.1001hc.
not activeSep 5, 2002building section4th floor bathroom out of order due to a broken toilet unit.1)replace toilet unit.1001hc. 2)reinstate 4th floor public bathroom.1001hc.
not activeJul 15, 2002building sectiondamaged,cracked door jamb,loose hardware to entry door gr#505.1)replace damaged door jamb to entry door gr#505. 2)replace hinges and hardware,to assure proper closure.1001hc./706hc.
not activeOct 29, 2001fire sectionremove egress obstruction at (801,1001(l) hc)remove all storage from the public hallways
not activeOct 29, 2001fire sectionrecharge/date tag fire extinguisher type 2a 10bc or equivalent (905,1001(m)hc)recharge and provide current date tags for the fire extinguishers on the 3rd and 6th floors.
not activeOct 29, 2001fire sectionremove egress obstruction at (801,1001(l) hc)provide unobstructed egress to the public street from the rear fire escape. ***path of travel from the bottom of the drop ladder to the public street must be clearly marked and cannot be blocked by any lock requiring a key, special knowledge or special effort.***
not activeOct 29, 2001security requirements sectionprovide minimum 135 degree viewer for entry doors of following units (max mounting ht of 58") (706 hc)replace the missing or damaged door viewers for the following rooms: 502, 514, 517 and 615.
not activeOct 29, 2001building sectionrepair garbage chute (1001 hc)replace the missing garbage chute hopper doors.
not activeOct 29, 2001security requirements sectionrepair self-closing devices at exterior doors (706 hc)adjust the automatic door closers on the doors accessing the front fire escapes. doors must close and lock without any outside assistance.
not activeOct 29, 2001fire sectionrepair, maintain fire escape drop ladder in working condition (sec 908 hc)service the rear fire escape so that the drop ladder extends easily and fully. ***keep handle at fire escape so that it can be lowered in the event of an emergency.***
not activeOct 29, 2001interior surfaces sectionrepair damaged ceilings (1001b,h,o hc)repair the damaged walls/ceilings in the following rooms: 1)#222 (wall); 2)#414 (wall); 3)#515 (wall); 4)5th floor shower room (wall & ceiling); 5)#603 (ceiling); and 6)#617 (wall) repaint the affected areas
not activeMay 4, 2007
fire section · repair fire proofing with approved materials (hc 1001(m), 809)
repair all damaged wall and ceiling surfaces in the basement and boiler room. repairs can be made with 5/8" type x drywall, 26 guage sheet metal, cement board, or equivalent. edges must be fire taped or sealed with fire foam or fire caulk.
not activeNov 30, 2005
building section · install sequential guestroom numbers to all entry doors.706hc./1001hc.
not activeNov 30, 2005
building section · 1)remove excessive construction debries, old furnishing, discarded household items from basement and storage room areas.1001hc. 2)contain all combustible paints, thinners, solvents in metal cabinets.1001hc.
clothered basement/storage areas.
not activeNov 30, 2005
building section · 1)remove plastic cover extended over smoke detectors in gr#317,614.1001hc. 2)install a cover over exposed wall switch in common bathroom adjacent to gr#623.,gr#623.1001hc. 3)repair/replace treshold in gr#605.1001hc.
a variety of maintanance violations at various locations.
not activeNov 30, 2005
building section · 1)install/adjust self closing devices/self latching devices and necessary hardware, to all common bathroom and toilet room door.912hc. 2)install self closing devices to each fire door leading to front exterior fire escape.712hc.
common bathroom doors as well as hallway doors leading to fire excape are lacking door closures.
not activeNov 30, 2005
building section · install and date tag approoved type of fire extinguishers ( type 2a-10bc) or equivalent,on all floors as well as in the common areas.905hc.
lack of hallway fire extinguishers.
not activeNov 30, 2005
building section · replace all burnt out, missing bulbs from illuminated exit signs on the 5 th floor.1001h.c./801h.c.
burnt out light bulbs in 5th floor exit sign.
not activeNov 30, 2005
building section · 1)provide four gallon of hot water storage capacity per guestroom.sec. 505 d(4)s.f.h.c. 2)properly vent, strap and provide a trp drain line for the exisitng water heaters.1001hc.
premises are currently lacking 300 gallons of hot water capacity.
not activeNov 30, 2005
building section · 1)clean and sanitize gr#302,316,410,419,512,614.1306hc. 2)eliminate excessive storage, flamables in gr#302.1001hc 3)intensify pest control measures until roach,bed bugs and vermin infestation is under control.1001hc. 4)replace damaged,insanitary box spring and mattress in gr#401,614.1308hc. 5)remove and abate mold on wall surfaces in gr#614.1306hc.
insanitary premises,filled with debries.
not activeNov 30, 2005
building section · repair fireproofing to basement, storage room and boiler room ceiling surfaces with 5/8 of an inch sheetrock type x.1001hc.
multiple holes along basement ceiling surfaces,in need of repairs.
not activeNov 30, 2005
building section · 1)install a handrail on top of the stairs at the winding tread, connecting ground floor with basement area.1001hc. 2)secure loose existing railingto basement stairs.1001hc.
lack of requiered handrail at top of basement stairs.
not activeFeb 8, 2005
building section · 1)repair inoperative boiler unit. provide heat from : 5:00 am-11:00 am 3:00 pm-10:00 pm.sec. 701hc.
inoperative boiler unit.lack of heat to the units.
not activeOct 21, 2004
building section · 1)provide a toilet tank cover to all lavatories lacking same in each public bathroom/restroom.1001hc. 2)install privacy locks to each public tub room,6th floor toilet room.1001hc. 3)unstop drain,clean and sanitize public bathroom floor surfaces in: 3rd floor,4th floor,5th floor,6th floor public shower rooms.1001hc. 4)replace missing shower heads in 4th floor,5th floor,6th floor public shower rooms. 5)provide a drain cover in 4th floor shower room adjacent to hallway window.1001hc.
insanitary,stoped up ,unmaintained public bathrooms.
not activeOct 21, 2004
building section · 1)repair defective roof surfaces causing water damage to ceiling surfaces in gr#622.1001hc. 2)remove,contain and properly dispose of water damaged paint and plaster from ceiling surfaces in gr#622.1001hc. 3)replaster and paint afected ceiling surfaces throughout.1301hc.
water damaged ceiling surfces in gr#622.
not activeOct 21, 2004
building section · repair,putty,glaze and seal all loose ,rattling hallway windows along public hallways and stairways.1001hc.
hallway window panes are loose and rattling.
not activeOct 21, 2004
building section · intensify pest and rodent control measures until roachesw,bedbugs,mice are under control.1001hc.
repeated tenant complaints of severe infestation of pests and rodents throughout the premises.
not activeOct 21, 2004
building section · 1)locate source and eliminate mold and mildew from walls and ceiling surfaces in : a)3rd floor public shower room. b)replaster and repair damaged wall surfaces in 3rd floor toilet room ,6th floor shower room above shower head. c)replaster and paint walls and ceilings of each and every public shower room/bathroom.1301hc.
public bathrooms in need to be painted.
not activeOct 21, 2004
building section · caulk and seal above,side of window seals causing water seepage in gr#620.1001hc.
water seepage through window seal in gr#620.
not activeOct 21, 2004
building section · replace missing handrail between 4th and 5th floors.1001hc.
staircase between 4th and 5th floors are lacking requiered handrails.
not activeJul 7, 2004
—
not activeFeb 17, 2004
building section · floor surfaces in gr#622 were littered filled with debries in need to be cleaned.
clean insanitary floor surfaces in gr#622.1306hc. 2)replace soiled water damaged carpeting.1306hc.
not activeJan 2, 2004
building section · defective roof surfaces,causing overhead leaks to 6th floor hallway.
1)have roof surfaces repaired by a licensed roofing contractor. 2)replace all water damaged plaster along hallway ceiling surfaces,with 5/8 of an inch sheetrock type x.1001hc.
not activeDec 8, 2003
building section · missing handrail along secondary stairs.
replace missing handrail to rear secondary stairs between 5th and 6th floors.1001hc
not activeDec 8, 2003
building section · missing garbage chute cover.
install missing garbage chute cover to 3rd floor hopper inlet.1001hc.
not activeDec 8, 2003
building section · inspectors comments.
it is the property owner?s responsibility to be present or direct his/her representative to attend, the reinspection as scheduled on this notice of violation for the purpose of providing entry to the inspector of those areas not accessed during the initial inspection as specified, and/or to provide access to all areas cited within this notice. if the property owner cannot attend the scheduled reinspection (as specified on this notice) it is his/her responsibility to secure a different inspection date and time with the inspector, and provide all tenants with notification as required by california civil code section 1954 (san francisco housing code section 303(b)), if any dwellings, apartment units or guest rooms are to be accessed during the reinspection.
not activeDec 8, 2003
building section · lack of a requiered smoke detector in gr#421.
install a smoke detector in gr#421.908hc.
not activeDec 8, 2003
building section · lack of privacy lock to 4th ,5th,6th floor public tub rooms.
1)install a privacy lock,cover door openings on 4th, 5th, 6th floor tub rooms.1001hc. 2)install a privacy lock to 3rd floor toilet room.1001hc.
not activeDec 8, 2003
building section · detached linoleum floor covering in front of public bathroom door across gr#522,#622.
reglue detached vinyl floor covering in front of 5th,6th floor public shower rooms.1001hc.
not activeDec 8, 2003
building section · leaking roof surfaces causing ceiling damage to gr#622.
1)repair leaking roof surfaces.1001hc. 2)resheetrock and paint damaged ceiling surfaces.1001hc./1301hc. 3)replace water damaged carpeting.1001hc. 4)clean premises throughout.1306hc.
not activeDec 8, 2003
building section · peeling paint and plaster along hallway ceiling surfaces on 3rd through 6th floors.
repair,replaster damaged portions of walls and ceiling surfaces in: 3rd floor hallway area above fire extinguisher across front interior stairs. 4th floor hallway wall surfaces adjacent to gr#409. 6th floor hallway wall surfaces side of #609. peeling wall surfaces,side of hallway stairs leading to roof.1001hc./1301hc.
not activeJun 11, 2003
interior surfaces section · repair/patch hole in wall near window unit #603
repair hole in wall #603 near window (1001hc)
not activeJun 11, 2003
interior surfaces section · remove cord wiring on roof leading to satelite dish
remove cord wiring on roof (401hc)
not activeJun 11, 2003
interior surfaces section · install peephole in entry door unit #603
install peephole entry door $603 (706(2)(vi)hc)
not activeJun 11, 2003
interior surfaces section · patch hole in ceiling unit #603 caused by leaking roof
patch hole in ceiling and repaint entire ceiling (1001hc)
not activeJun 11, 2003
interior surfaces section · remove all debris from rear fire escape
remove egress obstructions rear fire escape (810hc)
not activeJun 11, 2003
interior surfaces section · clean and maintain all bathrooms throughout
maintain all bathrooms in a sanitary manner (1001hc)
not activeJun 11, 2003
interior surfaces section · repair roof above unit #603
make repairs to roof above unit #603 to prevent further leakage (703hc)
not activeJun 6, 2003
building section · failure to file for necessary permits in order to comply with the residential hotel sprinkler ordinance #170-02.
submit a building permit application with plans to the department of building inspection within 15 days of this notice to comply with the residential hotel sprinkler ordinance #170-02, section 904 s.f.h.c.
not activeApr 9, 2003
building section · insanitary,warn tubs,leaking drain line,bathroom floors in disrepair.
1)replace warn,painted,chiped tubs on 4th,5th,6th floors.1001hc. 2)resurfaces and paint floor surfaces in each and every public restroom,shower room,tub room.1001hc. 3)replace door frame to 4th floor shower room.1001hc. 4)repair overhead leaks in 3rd floor shower room,causing ceiling damage to 2nd floor shower room.1001hc. replace water damaged bathroom ceiling with 5/8 of an inch sheetrock type x.1001hc.
not activeDec 6, 2002
building section · inoperative elevator.
repair inoperative elevator.1001hc.
not activeSep 5, 2002
building section · 4th floor bathroom out of order due to a broken toilet unit.
1)replace toilet unit.1001hc. 2)reinstate 4th floor public bathroom.1001hc.
not activeJul 15, 2002
building section · damaged,cracked door jamb,loose hardware to entry door gr#505.
1)replace damaged door jamb to entry door gr#505. 2)replace hinges and hardware,to assure proper closure.1001hc./706hc.
not activeOct 29, 2001
fire section · remove egress obstruction at (801,1001(l) hc)
remove all storage from the public hallways
not activeOct 29, 2001
fire section · recharge/date tag fire extinguisher type 2a 10bc or equivalent (905,1001(m)hc)
recharge and provide current date tags for the fire extinguishers on the 3rd and 6th floors.
not activeOct 29, 2001
fire section · remove egress obstruction at (801,1001(l) hc)
provide unobstructed egress to the public street from the rear fire escape. ***path of travel from the bottom of the drop ladder to the public street must be clearly marked and cannot be blocked by any lock requiring a key, special knowledge or special effort.***
not activeOct 29, 2001
security requirements section · provide minimum 135 degree viewer for entry doors of following units (max mounting ht of 58") (706 hc)
replace the missing or damaged door viewers for the following rooms: 502, 514, 517 and 615.
not activeOct 29, 2001
building section · repair garbage chute (1001 hc)
replace the missing garbage chute hopper doors.
not activeOct 29, 2001
security requirements section · repair self-closing devices at exterior doors (706 hc)
adjust the automatic door closers on the doors accessing the front fire escapes. doors must close and lock without any outside assistance.
not activeOct 29, 2001
fire section · repair, maintain fire escape drop ladder in working condition (sec 908 hc)
service the rear fire escape so that the drop ladder extends easily and fully. ***keep handle at fire escape so that it can be lowered in the event of an emergency.***
not activeOct 29, 2001
interior surfaces section · repair damaged ceilings (1001b,h,o hc)
repair the damaged walls/ceilings in the following rooms: 1)#222 (wall); 2)#414 (wall); 3)#515 (wall); 4)5th floor shower room (wall & ceiling); 5)#603 (ceiling); and 6)#617 (wall) repaint the affected areas
Page 2 of 5
← PrevNext →