not activeOct 1, 2008
sanitation section · eliminate cockroach infestation (1001b, 1306 hc)
cockroach infestation has been referred to the health dept.
not activeOct 1, 2008
other section · inspector comments
it is the property owner's responsibility to be present or direct his/her representative to attend the reinspection as scheduled on this notice of violation for the purpose of providing entry to the inspector of those areas not accessed during the initial inspection as specified, and/or to provide access to all areas cited within this notice. if the property owner cannot attend the scheduled reinspection (as specified on this notice) it is his/her responsibility to secure a different inspection date and time with the inspector, and provide all tenants with notification as required by california civil code section 1954 (san francisco housing code section 303(b), if any dwellings, apartment units or guest rooms are to be accessed during the reinspection.
not activeJun 11, 2008
other section · inspections
it is the property owner's responsibility to be present or direct his/her representative to attend the re-inspection as scheduled on this notice of violation for the purpose of providing entry to those areas not accessed during the initial inspection and/or to provide access to all areas cited within this notice. if the property owner cannot attend the scheduled re-inspection (as specified on this notice) it is his/her responsibility to reschedule with the inspector, and provide all tenants with notification as required by california civil code section 1954 (san francisco housing code section 303 (b) if any dwellings, apartment units or guest rooms are to be accessed during the re-inspection.
not activeJun 11, 2008
building section · provide certification of professional maintenance and testing of central fire alarm system. sfhc 909.
not activeJun 11, 2008
building section · provide for the fire escape(s) a written report from a qualified service contractor/company stating that all components have been tested and are functional as required or demonstrate proper function of fire escape ladder. sfhc 908.
not activeJun 11, 2008
building section · provide self closing fire rated penthouse door. sfhc 805.
not activeJun 11, 2008
building section · remove unpermitted door obstructing egress at secondary exit stairs first floor. sfhc 801.
not activeJun 11, 2008
building section · replace exposed wired lamp socket serving storage area near basement electrical equipment. sfhc 1001(e).
not activeJun 11, 2008
building section · protect basement electrical service conductors in accordance with the sf electrical code. sfhc(e).
electrical permit required.
not activeMay 7, 2007
building section · repair window glazing seal (1001(h),(j),& 708 hc)
repair the broken window glass in the following areas of #312: 1)main room-window on the right, upper & lower sashes. 2)bathroom lower sash.
not activeMay 7, 2007
interior surfaces section · repair damaged ceilings (1001b,h hc)
repair the loose plaster and peeling paint on the ceiling of the main room of #312.
not activeMay 7, 2007
other section · miscellaneous violations
install a room number to the outside of the door of #312.
not activeMay 7, 2007
other section · inspector comments
it is the property owner's responsibility to be present or direct his/her representative to attend the reinspection as scheduled on this notice of violation for the purpose of providing entry to the inspector of those areas not accessed during the initial inspection as specified, and/or to provide access to all areas cited within this notice. if the property owner cannot attend the scheduled reinspection (as specified on this notice) it is his/her responsibility to secure a different inspection date and time with the inspector, and provide all tenants with notification as required by california civil code section 1954 (san francisco housing code section 303(b), if any dwellings, apartment units or guest rooms are to be accessed during the reinspection.
not activeOct 2, 2006
other section · repair defective or non-working elevator (1001(l), 713 hc)
repair the non-functioning elevator.
not activeOct 2, 2006
other section · inspector comments
it is the property owner's responsibility to be present or direct his/her representative to attend, the reinspection as scheduled on this notice of violation for the purpose of providing entry to the inspector of those areas not accessed during the initial inspection as specified, and/or to provide access to all areas cited within this notice. if the property owner cannot attend the scheduled reinspection (as specified on this notice) it is his/her responsibility to secure a different inspection date and time with the inspector, and provide all tenants with notification as required by california civil code section 1954 (san francisco housing code section 303(b), if any dwellings, apartment units or guest rooms are to be accessed during the reinspection.
not activeApr 10, 2006
other section · repair defective or non-working elevator (1001(l), 713 hc)
the elevator won't stop at certain floors. have a licensed elevator repair company service the elevator and make the needed repairs.
not activeApr 10, 2006
other section · it is the property owner's responsibility to be present or direct his/her representative to attend, the reinspection as scheduled on this notice of violation for the purpose of providing entry to the inspector of those areas not accessed during the initial inspection as specified, and/or to provide access to all areas cited within this notice. if the property owner cannot attend the scheduled reinspection (as specified on this notice) it is his/her responsibility to secure a different inspection date and time with the inspector, and provide all tenants with notification as required by california civil code section 1954 (san francisco housing code section 303(b), if any dwellings, apartment units or guest rooms are to be accessed during the reinspection.
not activeDec 5, 2005
building section · replace broken glass window (1001(h) & 708 hc)
replace the missing glass to the third floor elevator door. service the elevator doors if needed to insure that they stay on their tracks.
not activeOct 29, 2004
building section · 1)remove and replace stained,urine soaked carpeting in gr#511.1036hc. 2)replace heavily soiled box spring,mattress and bedding in gr#511.1308hc. 3)clean and sanitize premises throughout: a) wash down walls,windows,clean and sanitize bathroom fixtures,floors,soiled toilet unit and sink.1308hc. b)repair stoped up bathroom sink.1001hc.
insanitay premises,constituting a potentila health hazard.
not activeOct 29, 2004
building section · intensify pest and rodent control measures,until infestation is under control.1001hc.
premises in need of pest control.
not activeJul 6, 2004
building section · 1)remove treat and abate mold from bathroom medicine cabinet in gr#412.1306hc. 2)clean and desinfect public bathrooms,shower rooms and restrooms on routine basis. 3)replace cracked ,warn toilet seats on 3rd,4th floors.1001hc./1306hc. 4)replace moldy caulking around tub enclosure on 4th floor.1306hc.
1)presence of mold in the bathroom medicine cabinet. 2)insanitary public restrooms,shower rooms.
not activeJul 6, 2004
building section · replace cracked interior door casement in gr#412.1001hc.
cracked interior molding to entry door in gr#412,in need of replacement.
not activeJun 11, 2004
building section · 1)remove piles of bags,debgries,litter from gr#204. 2)clean and sanitize premises throughout.1306hc. 3)clean and shampoo carpeting.1306hc. 4)provide pest and rodent control to the premises until infestation is under control.1306hc./1001hc.
insanitay premises filled with debries.
not activeMar 24, 2004
building section · repair inoperative elevator unit.1001hc.
inoperative elevator unit. (reoccuring violation.)
not activeMar 19, 2004
building section · repair inoperative elevator unit.1001hc.
defective elevator unit currently serviced by daily city elevetor.
not activeJan 28, 2004
building section · water damaged bathroom ceiling surfaces in gr#312.
1)replace water damaged ceiling surfaces in gr#312. 2)remove source,eliminate mold and mildew from : a)bathroom windows in both gr#312,#412. b)guestroom window surfaces in gr#312.1306hc.
not activeJan 28, 2004
building section · water damaged ,exposed bathroom ceiling light in gr#312.
replace water damaged bathroom ceiling light in gr#312.1001hc.
not activeJan 28, 2004
building section · damaged windows sash and hardware.
1)replace broken sash cords to bathroom windows in both #312,#314.1001hc. 2)repair,weatherstripp rattling,leaking guestroom window in gr#312.1001hc.
not activeJan 23, 2003
building section · lack of heat to gr#211/#212.
provide 68 degrees f. to each habitable room,from: 5:00 am-11:00 am 3:00 pm-10:00 pm sec 701hc. repair malfunctioning boiler unit.1001hc.
not activeNov 14, 2002
building section · water damaged portion of guestroom ceiling surfaces in #206,due to overhead leaks from handwash basin of unit #306.
note:the overhead leaks were repaired prior inspection. 1)remove water damaged portion of ceiling surfaces in #206. 2)replaster and paint affected areas.1001hc.1301hc.
not activeApr 25, 2001
building section · this notice includes violations for the areas noted.
465 ellis st
not activeApr 25, 2001
smoke detection section · repair smoke detector (908 911 hc)
repair smoke detector at rooms # 501, 502, 504, 505, 507, 508, 403, 407, 409, 411, 412, 308, 309, 201, 203, 206, 208, 211. provive smoke detector to room # 208.
not activeApr 25, 2001
other section · inspector comments
no entry to rooms # 511, 512, 401, 402, 405, 406, 408, 301, 302, 303, 304, 306, 307, 310, 311, 312, 202, 204, 207, 210. check upon reinspection : time clock for heat location of thermostat drop ladder at fire escape.
not activeApr 25, 2001
interior surfaces section · paint ceilings (1001b,1301 hc)
repair peeling paint at room # 505. repair peeling paint at bathroom floor next to room # 209.
not activeApr 25, 2001
other section · provide heat to each occupied habitable room for 13 hrs between 5:00 a.m. and 11:00 a.m. and between 3:00 p.m. and 10:00 p.m. capable to maintaining a min. room temp. of 68 degrees f. (20 degrees c.). (701c hc)
provide heat to rooms # 403, 212.
not activeApr 25, 2001
plumbing and electrical section · repair lightswitch (1001e hc)
repair expose wires at room # 409.
not activeApr 25, 2001
plumbing and electrical section · repair toilet (1001f hc)
restore toilet at hallway adjacent to room # 410. repair toilet adjacent to room # 310.
not activeApr 25, 2001
interior surfaces section · repair damaged ceilings (1001b,h,o hc)
repair damaged ceiling at rear stairway neat to room # 308. repair ceiling and at bathroom next to room # 209.
not activeMar 28, 2001
building section · stoped up toilet in #412 causing ceiling damage in bathroom #312.
1)unstop toilet in #412.1001hc. 2)reconnect dangling ceiling light.in #412 3)reconnect detached smoke detector.in #412
not activeMar 28, 2001
building section · water damaged bathroom ceiling in #312.
replaster and spot paint water damaged bathroom ceiling in #312.1001hc./1301hc.
not activeFeb 27, 2001
building section · insanitary carpeting in #306.
install new padding and carpeting in #306.1306hc.
not activeFeb 27, 2001
building section · insanitary hallway walls
wash down hallway wall surfaces on routine basis.1306hc.
not activeFeb 27, 2001
building section · missing light bulbs in public toilets
replace missng light bulbs in public toilets/bathrooms.504hc.
not activeJan 24, 2001
other section · malfunctioning boiler unit. lack of heat to a variety of guestrooms.
1)repair malfunctionig boiler unit by a licensed certified boiler contractor. 2)provide 68 degrees f. to each guestroom between 5:00 am-11:00 am 3:00 pm-10:00 pm.sec 701hc.
not activeJan 3, 2001
building section · inoperative radiator.
repair inoperative radiator.701hc.
not activeJan 3, 2001
building section · lack of smoke detector.
install a single station smoke detector.908hc.
not activeJan 3, 2001
building section · soiled insanitary carpeting.
replace insanitary carpeting.1306hc.
not activeJan 3, 2001
building section · window glass in need to be reputtied.
reputty/properly glaze windows.1001hc.
not activeDec 21, 2000
building section · insanitary premises.
clean and desinfect premises throughout.1306hc. wash down sink,cleand and sanitize windows.1306hc.
not activeDec 21, 2000
building section · soiled carpeting.
replace soiled carpeting.1306hc.