not activeJul 11, 2016
other section · inspector comments
it is the property owner's responsibility to be present or direct his/her representative to attend the re-inspection as scheduled on this notice of violation for the purpose of providing entry to the inspector of those areas not accessed during the initial inspection as specified, and/or to provide access to all areas cited within this notice. if the property owner cannot attend the scheduled re-inspection (as specified on this notice) it is his/her responsibility to secure a different inspection date and time with the inspector, and provide all tenants with notification as required by california civil code section 1954 (san francisco housing code section 303(b), if any dwellings, apartment units or guest rooms are to be accessed during the re-inspection. important note: due to the violations noted, this property is defined as a nuisance per sec. 1001-d of the sfhc. please review the attached "notice of violation warnings" for information regarding failure to comply with this notice.
not activeJul 11, 2016
plumbing and electrical section · repair toilet (1001f hc)
the toilet fixtures in the following locations are loose and must be secured. 1) middle toilet room on 5th floor. 2) middle toilet room on 4th floor.
not activeJul 11, 2016
plumbing and electrical section · provide adequate lighting (504g hc)
the lighting in the shower room on the 5th floor wasn't working at the time of inspection. replace the bulb or make the needed repairs to provide the required light.
not activeJul 11, 2016
building section · inspectors comment
violations cited are located in the common areas.
not activeJul 11, 2016
interior surfaces section · repair damaged door (1001b,h hc)
repair/replace the damaged door to the middle bathroom on the 5th floor.
not activeOct 13, 2015
interior surfaces section · repair floor covering (1001b,j hc)
replace the damaged, missing floor tiles in rm. 208.
not activeOct 13, 2015
interior surfaces section · other interior violations
seal all potential bedbug entry points to rm. 210 including cracks and holes at the closet and bed area.
not activeOct 13, 2015
other section · inspector comments
it is the property owner's responsibility to be present or direct his/her representative to attend the re-inspection as scheduled on this notice of violation for the purpose of providing entry to the inspector of those areas not accessed during the initial inspection as specified, and/or to provide access to all areas cited within this notice. if the property owner cannot attend the scheduled re-inspection (as specified on this notice) it is his/her responsibility to secure a different inspection date and time with the inspector, and provide all tenants with notification as required by california civil code section 1954 (san francisco housing code section 303(b), if any dwellings, apartment units or guest rooms are to be accessed during the re-inspection. important note: due to the violations noted, this property is defined as a nuisance per sec. 1001-d of the sfhc. please review the attached "notice of violation warnings" for information regarding failure to comply with this notice. all open notices of violation will be re-inspected at this time.
not activeOct 13, 2015
smoke detection section · provide smoke detector (908,911 hc)
replace the missing hardwired smoke alarm to rm. 208.
not activeOct 5, 2015
smoke detection section · provide smoke detector (908,911 hc)
replace the missing hardwired smoke alarm to room #210.
not activeOct 5, 2015
other section · inspector comments
it is the property owner's responsibility to be present or direct his/her representative to attend the re-inspection as scheduled on this notice of violation for the purpose of providing entry to the inspector of those areas not accessed during the initial inspection as specified, and/or to provide access to all areas cited within this notice. if the property owner cannot attend the scheduled re-inspection (as specified on this notice) it is his/her responsibility to secure a different inspection date and time with the inspector, and provide all tenants with notification as required by california civil code section 1954 (san francisco housing code section 303(b), if any dwellings, apartment units or guest rooms are to be accessed during the re-inspection. important note: due to the violations noted, this property is defined as a nuisance per sec. 1001-d of the sfhc. please review the attached "notice of violation warnings" for information regarding failure to comply with this notice. all open notices of violation will be re-inspected at
not activeOct 5, 2015
smoke detection section · other fire violations
replace the painted over sprinkler head located in the toilet room on the second floor near the stairs.
not activeSep 10, 2015
other section · inspector comments
a bedbug referral has been made to the dept. of environmental health for room 210; follow all procedures given by that department.
not activeSep 10, 2015
sanitation section · clean (1306 hc)
at the time of inspection the ceiling fan and the exterior glass to the window in room 210 were in need of cleaning; clean these surfaces.
not activeSep 10, 2015
other section · inspector comments
it is the property owner's responsibility to be present or direct his/her representative to attend the re-inspection as scheduled on this notice of violation for the purpose of providing entry to the inspector of those areas not accessed during the initial inspection as specified, and/or to provide access to all areas cited within this notice. if the property owner cannot attend the scheduled re-inspection (as specified on this notice) it is his/her responsibility to secure a different inspection date and time with the inspector, and provide all tenants with notification as required by california civil code section 1954 (san francisco housing code section 303(b), if any dwellings, apartment units or guest rooms are to be accessed during the re-inspection. important note: due to the violations noted, this property is defined as a nuisance per sec. 1001-d of the sfhc. please review the attached "notice of violation warnings" for information regarding failure to comply with this notice. all open notices of violation will be re-inspected at this time.
not activeMar 25, 2015
plumbing and electrical section · make necessary repairs to tub/shower (1001 hc)
re-finish or replace bathtub on 5th floor between rooms 507 & 508, if bathtub is re-finished follow the pursuant guidelines: comments regarding possible lead based paint "disturbing lead based paint can be extremely dangerous to dwelling occupants and visitors, particularly to young children, pregnant women, pets, and to people performing work on the premises. for interior or exterior paint removal : always wet the surface, contain and properly dispose of leaded paint. if you are unsure whether the paint is leaded, you should test it prior to performing any work. if the paint is found to contain lead, you should consult with an expert about appropriate procedures. proper containment and 3-day notification is required for exterior jobs of more than 10 square feet. (sec.3604, sfbc) informational packets are available at (415) 558-6088. you can contact the san francisco childhood lead poisoning prevention program at: (415) 554-8930 for free advice. if you cause lead dust to be created, you could be liable for any illness caused by the dust. ordinance #446-97."
not activeMar 25, 2015
building section · this notice includes violations for the areas noted.
373 ellis street-common areas
not activeMar 25, 2015
other section · inspector comments
inspector comments regarding "follow up" reinspection: i have scheduled a reinspection of your building on monday, 27-april-at 1:00 pm. reinspection of premise to include all areas referenced above. please contact inspector galvis to confirm appointment at 415-558-6513 or email at james.galvis@sfgov.org it is the property owners responsibility to be present or direct his/her representative to attend, the reinspection as scheduled on this notice of violation for the purpose of providing entry to the inspector of those areas cited within this notice. if the property owner cannot attend the scheduled reinspection (as specified on this notice) it is his/her responsibility to secure a different inspection date and time with the inspector, and provide all tenants with notification as required by california civil code section 1954 (san francisco housing code section 303(b)), if any dwellings, apartment units or guest rooms are to be accessed during the reinspection. on scheduled reinspection day, provide the inspector with a full access to all common and public areas per attached checklist. your cooperation is appreciated. important note: please be sure to review the attached "notice of violation warnings!" for information & costs associated with failure to comply with this notice of violation.
not activeJan 12, 2015
building section · this notice includes violations for the areas noted.
373 ellis street room 411
not activeJan 12, 2015
interior surfaces section · other interior violations
provide mattress, box spring and frame in room 411
not activeJan 12, 2015
other section · inspector comments
inspector comments regarding "follow up" reinspection: i have scheduled a reinspection of your building on thursday, 26-february-2015-at 12:30 pm. reinspection of premise to include all areas referenced above. please contact inspector galvis to confirm appointment at 415-558-6513 or email at james.galvis@sfgov.org it is the property owners responsibility to be present or direct his/her representative to attend, the reinspection as scheduled on this notice of violation for the purpose of providing entry to the inspector of those areas cited within this notice. if the property owner cannot attend the scheduled reinspection (as specified on this notice) it is his/her responsibility to secure a different inspection date and time with the inspector, and provide all tenants with notification as required by california civil code section 1954 (san francisco housing code section 303(b)), if any dwellings, apartment units or guest rooms are to be accessed during the reinspection. on scheduled reinspection day, provide the inspector with a full access to all common and public areas per attached checklist. your cooperation is appreciated. important note: please be sure to review the attached "notice of violation warnings!" for information & costs associated with failure to comply with this notice of violation.
not activeJan 12, 2015
plumbing and electrical section · repair sink (1001f hc)
replace missing hot water valve knob
not activeJan 12, 2015
sanitation section · eliminate rodent infestation (1001b, 1306 hc)
in room 411
not activeFeb 12, 2014
other section · inspector comments
inspector comments regarding "follow up" reinspection: i have scheduled a reinspection of your building on thursday, 13-march-2014 at 1:00 pm. reinspection of premise to include all areas referenced above. please contact inspector galvis to confirm appointment at 415-558-6513 or email at james.galvis@sfgov.org it is the property owners responsibility to be present or direct his/her representative to attend, the reinspection as scheduled on this notice of violation for the purpose of providing entry to the inspector of those areas cited within this notice. if the property owner cannot attend the scheduled reinspection (as specified on this notice) it is his/her responsibility to secure a different inspection date and time with the inspector. on scheduled reinspection day, provide the inspector with a full access to all common and public areas per attached checklist. your cooperation is appreciated.
not activeFeb 12, 2014
fire section · remove egress obstruction at (801,1001(l) hc)
it was observed at the time of inspection, on the second floor there was a mattress, box spring and frame, this is deemed an egress obstruction and at no time should there be any items in the hallway or any area that is an egress for the emergency evacuation of residents, no exceptions
not activeFeb 12, 2014
sanitation section · eliminate bedbug infestation (1001b, 1306 hc)
it was noted a the time of inspection that the mattress that was blocking the egress on the second floor was infested with bedbugs, therefore you are required to follow the guidlines pursuant article 11, section 581 of the san francisco health code. pco report must be presented at time of re-inspection, no exceptions.
not activeFeb 12, 2014
building section · this notice includes violations for the areas noted.
373 ellis street-common areas
not activeFeb 12, 2014
other section · repair defective or non-working elevator (1001(l), 713 hc)
at the time of inspection the elevator would not stop at all floors, provide documentation from a certified technician that states that the elevator will provide consistent operation for all residents and guests
not activeDec 30, 2013
fire section · provide directional exit signage (801,1001(l) hc)
provide directional exit signage for each required fire corridors. install directional exit signs in a strategic locations to evacuees can identify the nearest location in the event of an emergency evacuation.
not activeDec 30, 2013
building section · this property is defined as a nuisance per section "1001-d" of the san francisco housing code.
373 ellis st. public fire corridor and stairs
not activeDec 30, 2013
other section · it is the property owner¿s responsibility to be present or direct his/her representative to attend, the reinspection as scheduled on this notice of violation for the purpose of providing entry to the inspector of those areas cited within this notice. if the property owner cannot attend the scheduled reinspection (as specified on this notice) it is his/her responsibility to secure a different inspection date and time with the inspector. your cooperation is appreciated.
not activeOct 5, 2012
sanitation section · remove rubbish or trash (1306,1307 hc)
remove refuse from the roof area.
not activeOct 5, 2012
building section · repair window latches or hardware (1001(b)hc)
repair in 5th floor bathroom.
not activeOct 5, 2012
other section · inspector comments
due to the violations noted, this property is considered a nuisance, as defined by sec. 1001 (d) hc. it is the owner's responsibility to attend the reinspection scheduled below (or send a representative) and provide access to the areas cited. if this is not possible, the owner must obtain other inspections until compliance is confirmed.
not activeOct 5, 2012
sanitation section · clean or sanitize (1306 hc)
thoroughly clean all showers and bathtubs. the showers at the ends of the halls were particularly dirty as the grout was black with mold. remove the mold with cleansers or replace the discolored grout. suggest use of cleansers with bleach.
not activeOct 5, 2012
building section · repair window sash frame (1001(h),708 hc)
in the 5th floor bathroom, repair the upper sash to close completely.
not activeOct 5, 2012
plumbing and electrical section · make necessary repairs to tub/shower (1001 hc)
in the 4th and 5th floor bathrooms, repair the deteriorated tub surfaces.
not activeApr 26, 2012
other section · due to the violations noted, this property is considered a nuisance, as defined by sec. 1001 (d) hc. it is the owner's responsibility to attend the reinspection scheduled below (or send a representative) and provide access to the areas cited. if this is not possible, the owner must obtain other inspections until compliance is confirmed.
not activeApr 26, 2012
building section · repair window latches or hardware (1001(b)hc)
repair in 5th floor bathroom.
not activeApr 26, 2012
plumbing and electrical section · make necessary repairs to tub/shower (1001 hc)
resurface the 4th floor bathroom tub.
not activeApr 26, 2012
sanitation section · clean or sanitize (1306 hc)
clean walls of 5th floor bathroom.
not activeApr 26, 2012
interior surfaces section · paint ceilings (1001b,1301 hc)
paint peeling ceiling of 5th floor toilet room.
not activeApr 26, 2012
interior surfaces section · paint walls (1001b,1301 hc)
paint door and walls of 4th floor toilet room.
not activeApr 26, 2012
interior surfaces section · repair damaged walls (1001b,h,o hc)
a) repair and paint damaged hallway wall outside 4th floor toilet room door. b) repair and paint damaged wall (along the door frame) inside the 2nd floor toilet room.
not activeApr 26, 2012
interior surfaces section · repair damaged ceilings (1001b,h,o hc)
repair and paint damaged ceiling of 3rd floor toilet room.
not activeApr 26, 2012
building section · repair window sash cords (1001(h) hc)
repair in 5th floor bathroom.
not activeSep 21, 2010
interior surfaces section · replace broken glass window pane (1001(d)(h) hc)
in unit #416.
not activeSep 21, 2010
building section · this notice includes violations for the areas noted.
373 ellis street - unit #416
not activeSep 21, 2010
plumbing and electrical section · repair ceiling light fixture (1001(b)(d) hc)
repair defective ceiling light fixture in unit #416.