not activeFeb 17, 2017
fire section · other fire violations
inspect and make repairs to all trash rooms including the following: 1) 6th floor trash room door closer is broken. 2) 5th floor trash room door will not close. trash room doors must be self closing.
not activeFeb 17, 2017
sanitation section · inspectors comment
the complainant reported rodent and cockroach problems throughout the building. at the time of inspection hotel occupants also reported problems and pest control was observed setting rodent traps in the community room kitchen. at the time of inspection provide the inspector copies of the current pest control reports along with the treatment protocols for the areas being treated.
not activeFeb 17, 2017
sanitation section · other sanitation violations
at the time of inspection the front area of the basement was flooded from the rains. remove the storm water, dry the area, locate and repair the source of the water entry.
not activeFeb 17, 2017
other section · inspector comments
it is the property owner's responsibility to be present or direct his/her representative to attend the re-inspection as scheduled on this notice of violation for the purpose of providing entry to the inspector of those areas not accessed during the initial inspection as specified, and/or to provide access to all areas cited within this notice. if the property owner cannot attend the scheduled re-inspection (as specified on this notice) it is his/her responsibility to secure a different inspection date and time with the inspector, and provide all tenants with notification as required by california civil code section 1954 (san francisco housing code section 303(b), if any dwellings, apartment units or guest rooms are to be accessed during the re-inspection. important note: due to the violations noted, this property is defined as a nuisance per sec. 1001-d of the sfhc. please review the attached "notice of violation warnings" for information regarding failure to comply with this notice.
not activeMay 6, 2016
sanitation section · sanitize (1306 hc)
at the time of inspection the common area carpeting was in need of cleaning. clean all affected areas including the following: 1) at the elevator landings. 2) the gold carpeting at the rear of the second floor. 3) dried animal waste outside #605, near #611, and at the hall window near the rear of the 6th floor corridor.
not activeMay 6, 2016
sanitation section · clean (1306 hc)
clean the trash left in the middle of the corridor leading to #'s 606 & 609 as well as stored personal items outside #600.
not activeMay 6, 2016
other section · inspector comments
it is the property owner's responsibility to be present or direct his/her representative to attend the re-inspection as scheduled on this notice of violation for the purpose of providing entry to the inspector of those areas not accessed during the initial inspection as specified, and/or to provide access to all areas cited within this notice. if the property owner cannot attend the scheduled re-inspection (as specified on this notice) it is his/her responsibility to secure a different inspection date and time with the inspector, and provide all tenants with notification as required by california civil code section 1954 (san francisco housing code section 303(b), if any dwellings, apartment units or guest rooms are to be accessed during the re-inspection. important note: due to the violations noted, this property is defined as a nuisance per sec. 1001-d of the sfhc. please review the attached "notice of violation warnings" for information regarding failure to comply with this notice.
not activeJul 30, 2015
sanitation section · clean & sanitize (1306 hc)
most of the carpeting throughout the hotel is stained, sticky, smells and is in need of washing or replacing; near the elevators in particular. clean/wash/shampoo the carpeting or replace.
not activeJul 30, 2015
interior surfaces section · repair floor covering (1001b,j hc)
repair or replace the curling vinyl flooring in the elevator.
not activeJul 30, 2015
sanitation section · eliminate rodent infestation (1001b, 1306 hc)
at the time of inspection rodent droppings were noted near the window area of #515. have a licensed pest control contractor eliminate the rodent infestation and seal all entry points. provide a copy of the pest control invoice and remediation plan to the housing inspector at the time of re-inspection.
not activeJul 30, 2015
sanitation section · other sanitation violations
install a door sweep on the bottom of the entry door to #515 to eliminate rodent access.
not activeJul 30, 2015
sanitation section · clean (1306 hc)
clean the soot off the walls, stairway, ceiling near unit #'s 518 & 618.
not activeJul 30, 2015
fire section · repair garbage room door closers (807,707 hc)
repair or replace all defective door closers including those garbage room closers near unit #'s 202, 402, 502, & 602.
not activeJul 30, 2015
plumbing and electrical section · miscellaneous violations
the exterior of the window to unit #615 is very dirty, limiting the amount of required natural light. clean all dirty windows at the rear of the building that are reducing the amount of required natural light.
not activeJul 30, 2015
plumbing and electrical section · repair electrical outlet (1001e hc)
the electrical outlet outside the bathroom of unit #515 is damaged with exposed wiring. repair/replace the electrical outlet.
not activeJul 30, 2015
other section · inspector comments
it is the property owner's responsibility to be present or direct his/her representative to attend the re-inspection as scheduled on this notice of violation for the purpose of providing entry to the inspector of those areas not accessed during the initial inspection as specified, and/or to provide access to all areas cited within this notice. if the property owner cannot attend the scheduled re-inspection (as specified on this notice) it is his/her responsibility to secure a different inspection date and time with the inspector, and provide all tenants with notification as required by california civil code section 1954 (san francisco housing code section 303(b), if any dwellings, apartment units or guest rooms are to be accessed during the re-inspection. important note: due to the violations noted, this property is defined as a nuisance per sec. 1001-d of the sfhc. please review the attached "notice of violation warnings" for information regarding failure to comply with this notice.
not activeJun 9, 2015
building section · this notice includes violations for the areas noted.
144 eddy street-common areas
not activeJun 9, 2015
fire section · remove egress obstruction at (801,1001(l) hc)
fire escape access windows, remove bicycles from the 6th and 4th floor and wheel chair from the second floor, these areas must be clear of all items at all times, no exceptions.
not activeJun 9, 2015
other section · inspector comments
inspector comments regarding "follow up" reinspection: i have scheduled a reinspection of your building on friday, 12-june-2015 at 9:00 am. reinspection of premise to include all areas referenced above. please contact inspector galvis to confirm appointment at 415-558-6513 or email at james.galvis@sfgov.org it is the property owners responsibility to be present or direct his/her representative to attend, the reinspection as scheduled on this notice of violation for the purpose of providing entry to the inspector of those areas cited within this notice. if the property owner cannot attend the scheduled reinspection (as specified on this notice) it is his/her responsibility to secure a different inspection date and time with the inspector, and provide all tenants with notification as required by california civil code section 1954 (san francisco housing code section 303(b)), if any dwellings, apartment units or guest rooms are to be accessed during the reinspection. on scheduled reinspection day, provide the inspector with a full access to all common and public areas per attached checklist. your cooperation is appreciated. important note: please be sure to review the attached "notice of violation warnings!" for information & costs associated with failure to comply with this notice of violation.
not activeJun 10, 2014
building section · this notice includes violations for the areas noted.
144 eddy street-all common areas
not activeJun 10, 2014
other section · repair defective or non-working elevator (1001(l), 713 hc)
elevator must be repaired in order to provide consistent service for all residing tenants and guests.
not activeJun 10, 2014
other section · inspector comments
inspector comments regarding "follow up" reinspection: i have scheduled a reinspection of your building on friday, 18-july-2014 at 9:00 am. reinspection of premise to include all areas referenced above. please contact inspector galvis to confirm appointment at 415-558-6513 or email at james.galvis@sfgov.org it is the property owners responsibility to be present or direct his/her representative to attend, the reinspection as scheduled on this notice of violation for the purpose of providing entry to the inspector of those areas cited within this notice. if the property owner cannot attend the scheduled reinspection (as specified on this notice) it is his/her responsibility to secure a different inspection date and time with the inspector, and provide all tenants with notification as required by california civil code section 1954 (san francisco housing code section 303(b)), if any dwellings, apartment units or guest rooms are to be accessed during the reinspection. on scheduled reinspection day, provide the inspector with a full access to all common and public areas per attached checklist. your cooperation is appreciated. important note: please be sure to review the attached "notice of violation warnings!" for information & costs associated with failure to comply with this notice of violation.
not activeNov 7, 2011
smoke detection section · repair smoke detector (908 911 hc)
repair smoke detector in #402. when done, call the housing inspector noted below.
not activeFeb 8, 2011
building section · this notice includes violations for the areas noted.
144 eddy street - room #403
not activeFeb 8, 2011
interior surfaces section · clean or sanitize (1001(d), 1306 hc)
clean the soiled carpet in room #403.
not activeFeb 8, 2011
other section · inspector comments
it is the property owner's responsibility to be present or direct his/her representative to attend, the reinspection as scheduled on this notice of violation for the purpose of providing entry to the inspector of those areas not accessed during the initial inspection as specified, and/or to provide access to all areas cited within this notice. if the property owner cannot attend the scheduled reinspection (as specified on this notice) it is he/her responsibility to secure a different inspection date and time with the inspector, and provide all tenants with notification as required by california civil code section 1954 (san francisco housing code section 303(b), if any dwellings, apartment units or guest rooms are to be accessed during the reinspection.
not activeApr 6, 2010
Heating equipment
No permit to operate the boiler. CMC 1023
not activeJun 4, 2008
other section · inspections
it is the property owner's responsibility to be present or direct his/her representative to attend the re-inspection as scheduled on this notice of violation for the purpose of providing entry to those areas not accessed during the initial inspection and/or to provide access to all areas cited within this notice. if the property owner cannot attend the scheduled re-inspection (as specified on this notice) it is his/her responsibility to reschedule with the inspector, and provide all tenants with notification as required by california civil code section 1954 (san francisco housing code section 303 (b) if any dwellings, apartment units or guest rooms are to be accessed during the re-inspection.
not activeJun 4, 2008
building section · provide for the fire escape(s) a written report from a qualified service contractor/company stating that all components have been tested and are functional as required or demonstrate proper function of fire escape ladder. sfhc 908.
not activeJun 4, 2008
building section · maintain premises (building rear exterior court) clean and sanitary. sfhc 1306.
maintain premises clean, sanitary, and free from accumulation of debris, filth, rubbish, garbage, vermin, mold and mildew and offensive matter. areas that can no longer be cleaned or made sanitary shall be replaced in an appropriate manner.
not activeJun 4, 2008
building section · provide door closers at smoke/fire door at building rear exit corridor ground floor. sfhc 706, 807.
not activeJun 4, 2008
building section · provide self closing, tight fitting garbage compartment doors. sfhc 707.
not activeJun 4, 2008
building section · provide water heater temperature/pressure relief discharge in accordance with sfpc 608.5
not activeJan 12, 2006
security requirements section · provide self-closing devices at exterior doors (707(5) hc)
provide and install self-closing devices to each garbage room door.
not activeJan 12, 2006
fire section · install directional signs at (801, 1001(m) hc)
the illuminated emergency egress sign near unit #612 is pointing in the wrong direction. adjust the sign to point in the proper direction.
not activeJan 12, 2006
other section · it is the property owner's responsibility to be present or direct his/her representative to attend, the reinspection as scheduled on this notice of violation for the purpose of providing entry to the inspector of those areas not accessed during the initial inspection as specified, and/or to provide access to all areas cited within this notice. if the property owner cannot attend the scheduled reinspection (as specified on this notice) it is his/her responsibility to secure a different inspection date and time with the inspector, and provide all tenants with notification as required by california civil code section 1954 (san francisco housing code section 303(b), if any dwellings, apartment units or guest rooms are to be accessed during the reinspection.
not activeJan 3, 2005
building section · repair inoperative elevator.1001hc./808hc.
inoperative elevator,reoccuring violation.
not activeNov 9, 2004
building section · repair/restore inoperative heating system. provide each habitable room 68 degrees f. for 13 hours. 5:00 am-11:00 am 3:00 pm-10:00 pm. 68 degrees f.701hc./1001hc.
heating system failure.
not activeSep 3, 2004
building section · properly connect radiator unit in gr#304.1001hc./701hc.
disconnected radiator unit.
not activeSep 3, 2004
building section · note: it appeared that the flooring,window and door frames were tilted and unaligned. obtain the services of a licensed structural engineer in order to assess building integrity.1001hc.
building seems to settle,in need to be assesed by a licensed structural engineer.
not activeAug 11, 2004
building section · install a radiator unit to gr.#515. provide 68 degrees f. from : 5:00 am-11:00 am 3:00 pm-10:00 pm to each habitable room.sec. 701hc.
lack of a requiered radiator unit in gr#515.
not activeAug 11, 2004
building section · properly mount and secure detached electrical wall sockets in #515.1001hc.
detached electrical wall sockets.
not activeAug 11, 2004
building section · repair/remount detached bathroom sink in gr#515.1001hc.
detached bathroom sink in gr#515.
not activeAug 11, 2004
building section · 1)keep and maintain all corridors,hallways,lightwells in a clean and sanitary condition during cosmetic remodeling of the building. 2)remove bags of construction debries from 5th floor hallway/1st floor lightwell.1306hc.
public areas in need to be cleaned on routine basis.
not activeFeb 27, 2004
building section · lack of requiered handrails along front interior stairs.
replace all missing handrail along 3rd through 7th floor interior stairs.1001hc. comply with sec 1003.3.6 of the calif. building code requierements attached.
not activeFeb 5, 2004
building section · insanitary premises constituting a health hazard and a nuisance.
1)remove piles of debries,rubbish from thepremises.1306hc. 2)clean and sanitize carpeting throughout the premises.1306hc. 3)clean and sanitize premises throughout.1306hc.
not activeJan 21, 2004
building section · time clock serving the boiler unit is in need of one set of on and off pegs.
set time clock to: 5:00 am-11:00 am 3:00 pm-10:00 pm. provide 68 degrees f. to each habitable room.701hc.
not activeJan 6, 2004
building section · stress cracks along guestroom wall,side of kitchen counter.
asses cause and repair hairline crack side of kitchen counter in gr#618.1001hc.
not activeJan 6, 2004
building section · cracked door frame,entry door to gr#618 is in need of alignment.
replace cracked portion of door frame ,repair and align entry door to gr#618.1001hc.
not activeJan 6, 2004
building section · lack of a radiator unit in gr#617.
install a radiator unit in gr#617.706hc.