not activeJun 23, 2014
building section · this notice includes violations for the areas noted.
room to room and common area inspection of the subject property.
not activeJun 23, 2014
building section · paint walls, ceilings and/or trim (1001-b, 1301, 1306 hc)
repaint all areas where paint is removed or damaged or where surfaces are repaired including specific guestroom locations indicated below.
not activeJun 23, 2014
fire section · in guestroom #402, correct all violations in the column to the right.
(a) repair/replace/adjust damaged guestroom door with approved smoke enclosure door that operates correctly, fully self closes and latches (706, 807, 1001-b hc). (b) install latch, repair, replace or adjust damaged window sashes, frames, balancers so they operate correctly and provide weather protection (703, 1001-b,h hc). (c) provide minimum 135 degree viewer on guestroom door (maximum height 58") (706 hc).
not activeJun 23, 2014
fire section · in guestroom #411, correct all violations cited in the column to the right.
(a) repair/replace/adjust damaged guestroom door with approved smoke enclosure door that operates correctly, fully self closes and latches (706, 807, 1001-b hc). (b) provide minimum 135 degree viewer on guestroom door (maximum height 58") (706 hc).
not activeJun 23, 2014
smoke detection section · in guestroom #309, correct all violations cited in the column to the right.
(a) repair/replace/adjust damaged guestroom door with approved smoke enclosure door that operates correctly, fully self closes and latches (706, 807, 1001-b hc). (b) in the bathroom, repair, replace or adjust damaged window sashes, frames, balancers so they operate correctly and provide weather protection (703, 1001-b,h hc). (c) repair/replace damaged/rusted/chipped guestroom sink (505, 1001b,f hc). (d) repair running toilet (505, 1001b, hc). (e) provide minimum 135 degree viewer on guestroom door (maximum height 58") (706 hc).
not activeJun 23, 2014
smoke detection section · in guestroom #301, correct all violations cited in the column to the right.
(a) repair/replace/adjust damaged guestroom door with approved smoke enclosure door that operates correctly, fully self closes and latches (706, 807, 1001-b hc). (b) repair, replace or adjust damaged window sashes, frames, balancers so they operate correctly and provide weather protection (703, 1001-b,h hc). (c) remove hasps or i-bolts on guestroom door (801, 1001-b hc).
not activeJun 23, 2014
smoke detection section · in guestroom #322, correct all violations cited in the column to the right.
(a) repair/replace/adjust damaged guestroom door with approved smoke enclosure door that operates correctly, fully self closes and latches (706, 807, 1001-b hc). (b) repair, replace or adjust damaged window sashes, frames, balancers so they operate correctly and provide weather protection (703, 1001-b,h hc). (c) repair/replace damaged/rusted/chipped guestroom sink (505, 1001b,f hc).
not activeJun 23, 2014
plumbing and electrical section · in guestroom #226, correct all violations cited in the column to the right.
(a) repair/replace/adjust damaged guestroom door with approved smoke enclosure door that operates correctly, fully self closes and latches (706, 807, 1001-b hc). (b) repair damaged wall and ceiling above tub and repaint (1001-b, 1306 hc). (c) provide latch, repair, replace or adjust damaged window sashes, frames, balancers so they operate correctly and provide weather protection (703, 1001-b,h hc).
not activeJun 23, 2014
plumbing and electrical section · in guestroom #201, correct all violations cited in the column to the right.
(a) repair/replace/adjust damaged guestroom door with approved smoke enclosure door that operates correctly, fully self closes and latches (706, 807, 1001-b hc). (b) provide latch, repair, replace or adjust damaged window sashes, frames, balancers so they operate correctly and provide weather protection (703, 1001-b,h hc). (c) repair light (1001e hc). (d) provide minimum 135 degree viewer on guestroom door (maximum height 58") (706 hc).
not activeJun 23, 2014
sanitation section · in guestroom #109, correct all violations cited in the column to the right.
(a) provide minimum 135 degree viewer on guestroom door (maximum height 58") (706 hc).
not activeJun 23, 2014
sanitation section · in guestroom #100, correct all violations cited in the column to the right.
(a) repair/replace/adjust damaged guestroom door with approved smoke enclosure door that operates correctly, fully self closes and latches (706, 807, 1001-b hc). (b) repair damaged wall at closet door and repaint (1001-b, 1306 hc).
not activeJun 23, 2014
building section · repair windows (708, 1001-b,h hc)
in several guestrooms, window sash frames do not operate correctly, have broken or missing sash cords, do not latch and/or provide adequate seal. repair or replace and adjust as needed so all guestroom windows, including those at specific locations indicated below, operate correctly, can be latched and provide an adequate seal.
not activeJun 23, 2014
fire section · in guestroom #424, correct all violations cited in the column to the right.
(a) repair/replace/adjust damaged guestroom door with approved smoke enclosure door that operates correctly, fully self closes and latches (706, 807, 1001-b hc). (b) repair, replace or adjust damaged window sashes, frames, balancers so they operate correctly and provide weather protection (703, 1001-b,h hc). (c) provide minimum 135 degree viewer on guestroom door (maximum height 58") (706 hc).
not activeJun 23, 2014
fire section · in guestroom #418, correct all violations cited in the column to the right.
(a) repair/replace/adjust damaged guestroom door with approved smoke enclosure door that operates correctly, fully self closes and latches (706, 807, 1001-b hc). (b) provide latch, repair, replace or adjust damaged window sashes, frames, balancers so they operate correctly and provide weather protection (703, 1001-b,h hc).
not activeJun 23, 2014
fire section · in guestroom #412, correct all violations cited in the column to the right.
(a) repair/replace/adjust damaged guestroom door with approved smoke enclosure door that operates correctly, fully self closes and latches (706, 807, 1001-b hc). (b) provide latch, repair, replace or adjust damaged window sashes, frames, balancers so they operate correctly and provide weather protection (703, 1001-b,h hc). (c) provide switch plate cover (1001e hc). (d) repair/replace damaged/rusted/chipped guestroom sink (505, 1001b,f hc).
not activeJun 23, 2014
fire section · in guestroom #409, correct all violations cited in the column to the right.
(a) repair/replace/adjust damaged guestroom door with approved smoke enclosure door that operates correctly, fully self closes and latches (706, 807, 1001-b hc).
not activeJun 23, 2014
smoke detection section · in guestroom #303, correct all violations cited in the column to the right.
(a) repair damaged wall and ceiling and repaint (1001-b, 1306 hc).
not activeJun 23, 2014
smoke detection section · in guestroom #328, correct all violations cited in the column to the right.
(a) repair/replace/adjust damaged guestroom door with approved smoke enclosure door that operates correctly, fully self closes and latches (706, 807, 1001-b hc). (b) repair, replace or adjust damaged window sashes, frames, balancers so they operate correctly and provide weather protection (703, 1001-b,h hc). (c) repair/replace damaged/rusted/chipped guestroom sink and leaking faucet (505, 1001b,f hc).
not activeJun 23, 2014
plumbing and electrical section · in guestroom #221, correct all violations cited in the column to the right.
(a) repair damaged/loose sub-floor boards (1001b, 1306 hc).
not activeJun 23, 2014
plumbing and electrical section · in guestroom #219, correct all violations cited in the column to the right.
(a) repair/replace/adjust damaged guestroom door with approved smoke enclosure door that operates correctly, fully self closes and latches (706, 807, 1001-b hc). (b) repair, replace or adjust damaged window sashes, frames, balancers so they operate correctly and provide weather protection (703, 1001-b,h hc).
not activeJun 23, 2014
plumbing and electrical section · in guestroom #204, correct all violations cited in the column to the right.
(a) provide door sweep, repair/replace/adjust damaged guestroom door with approved smoke enclosure door that operates correctly, fully self closes and latches (706, 807, 1001-b hc). (b) repair damaged wall next to bed and repaint (1001-b, 1306 hc). (c) repair, replace or adjust damaged window sashes, frames, balancers so they operate correctly and provide weather protection (703, 1001-b,h hc). (d) repair/replace damaged/rusted/chipped guestroom sink (505, 1001b,f hc).
not activeJun 23, 2014
sanitation section · in guestroom #104, correct all violations cited in the column to the right.
(a) repair/replace/adjust damaged guestroom door with approved smoke enclosure door that operates correctly, fully self closes and latches (706, 807, 1001-b hc). (b) repair, replace or adjust damaged window sashes, frames, balancers so they operate correctly and provide weather protection (703, 1001-b,h hc). (c) repair/replace loose faucets at guestroom sink (505, 1001b,f hc).
not activeJun 23, 2014
building section · provide carbon monoxide detector / alarms (420 sfbc)
carbon monoxide detector-alarms are required in all sleeping rooms on floors with fossil fuel-burning heater or appliances, fireplaces or attached garages and on all floors above and below a fossil fuel-burning heater or appliance, fireplace or attached garage. since there is a gas burning appliance in the basement of the hotel, carbon monoxide detector-alarms are required in all sleeping rooms on the first floor above the basement and in the common areas on the same floor. note: combination carbon monoxide detector-alarms and smoke detector-alarms can be used in areas that require both type of detector-alarms.
not activeJun 23, 2014
building section · repair or replace guestroom sink (1001-b,f hc)
porcelain on many guestroom sinks is chipped and underlying metl exposed and rusty making sinks difficult to keep clean. repair or replace all guestroom sinks where chips have exposed underlying metal, including those in specific guestroom locations indicated below. cracked or broken sinks must be replaced.
not activeJun 23, 2014
fire section · in guestroom #429, correct all violations cited in the column to the right.
(a) repair/replace/adjust damaged guestroom door with approved smoke enclosure door that operates correctly, fully self closes and latches (706, 807, 1001-b hc). (b) repair damaged wall around sink and repaint (1001-b, 1306 hc). (c) repair, replace or adjust damaged window sashes, frames, balancers so they operate correctly and provide weather protection (703, 1001-b,h hc). (d) repair/replace damaged/rusted/chipped guestroom sink (505, 1001b,f hc). (e) repair damaged floor covering, loose carpeting (1001b, 1306 hc). (f) remove hasps or i-bolts on guestroom door (801, 1001-b hc).
not activeJun 23, 2014
fire section · in guestroom #404, correct all violations cited in the column to the right.
(a) repair/replace/adjust damaged guestroom door with approved smoke enclosure door that operates correctly, fully self closes and latches (706, 807, 1001-b hc). (b) provide minimum 135 degree viewer on guestroom door (maximum height 58") (706 hc).
not activeJun 23, 2014
smoke detection section · in guestroom #310, correct all violations cited in the column to the right.
(a) repair/replace/adjust damaged guestroom door with approved smoke enclosure door that operates correctly, fully self closes and latches (706, 807, 1001-b hc). (b) install latche, repair, replace or adjust damaged window sashes, frames, balancers so they operate correctly and provide weather protection (703, 1001-b,h hc). (c) provide minimum 135 degree viewer on guestroom door (maximum height 58") (706 hc).
not activeJun 23, 2014
smoke detection section · in guestroom #302, correct all violations cited in the column to the right.
(a) repair/replace/adjust damaged guestroom door with approved smoke enclosure door that operates correctly, fully self closes and latches (706, 807, 1001-b hc). (b) repair, replace or adjust damaged window sashes, frames, balancers so they operate correctly and provide weather protection (703, 1001-b,h hc). (c) repair closet door handle (1001-b hc).
not activeJun 23, 2014
smoke detection section · in guestroom #323, correct all violations cited in the column to the right.
(a) repair/replace/adjust damaged guestroom door with approved smoke enclosure door that operates correctly, fully self closes and latches (706, 807, 1001-b hc). (b) repair damaged wall and ceiling and repaint (1001-b, 1306 hc). (c) repair, replace or adjust damaged window sashes, frames, balancers so they operate correctly and provide weather protection (703, 1001-b,h hc). (d) provide missing smoke detector (908, 911 hc). (e) repair/replace damaged/rusted/chipped guestroom sink (505, 1001b,f hc). (f) repair damaged floor covering (1001b, 1306 hc). (g) clean and sanitize entire room, floors walls and ceiling (1306 hc).
not activeJun 23, 2014
plumbing and electrical section · in guestroom #227, correct all violations cited in the column to the right.
(a) repair/replace/adjust damaged guestroom door with approved smoke enclosure door that operates correctly, fully self closes and latches (706, 807, 1001-b hc). (b) repair damaged wall and ceiling and repaint (1001-b, 1306 hc). (c) provide latch, repair, replace or adjust damaged window sashes, frames, balancers so they operate correctly and provide weather protection (703, 1001-b,h hc). (d) repair/replace damaged/rusted/chipped guestroom sink (505, 1001b,f hc). (e) provide minimum 135 degree viewer on guestroom door (maximum height 58") (706 hc).
not activeJun 23, 2014
plumbing and electrical section · in guestroom #200, correct all violations cited in the column to the right.
(a) repair/replace/adjust damaged guestroom door with approved smoke enclosure door that operates correctly, fully self closes and latches (706, 807, 1001-b hc). (b) provide latch, repair, replace or adjust damaged window sashes, frames, balancers so they operate correctly and provide weather protection (703, 1001-b,h hc). (c) provide missing smoke detector (908, 911 hc). (d) provide minimum 135 degree viewer on guestroom door (maximum height 58") (706 hc).
not activeJun 23, 2014
sanitation section · in guestroom #110, correct all violations cited in the column to the right.
(a) repair/replace/adjust damaged guestroom door with approved smoke enclosure door that operates correctly, fully self closes and latches (706, 807, 1001-b hc). (b) repair damaged walls and ceilings and repaint (1001-b, 1306 hc). (c) repair, replace or adjust damaged window sashes, frames, balancers so they operate correctly and provide weather protection (703, 1001-b,h hc). (d) provide minimum 135 degree viewer on guestroom door (maximum height 58") (706 hc).
not activeJun 23, 2014
sanitation section · in guestroom #102, correct all violations cited in the column to the right.
(a) repair, replace or adjust damaged window sashes, frames, balancers so they operate correctly and provide weather protection (703, 1001-b,h hc).
not activeJun 23, 2014
building section · replace substandard guestroom smoke enclosure doors (706, 807 hc)
several guestroom doors are deteriorated, are not tight fitting or have been replaced with unapproved doors. at all guestrooms including specific locations indicated below, replace all damaged doors and all unapproved replacement doors with approved one-and-three-eighths inch solid core wood door or rated metal doors. the replacement doors are required to be tight-fitting, self closing and self latching (with handles that control the latch) and have a deadbolt with thumb turn on he inside and in good condition for security and smoke enclosure purposes.
not activeJun 23, 2014
building section · provide minimum 135 degree viewer for guestroom entry doors (706 hc)
wherever viewers are missing or painted over and in specific guestroom locations indicated below, provide approved guestroom door viewers.
not activeJun 23, 2014
fire section · in guestroom #421, correct all violations cited in the column to the right.
(a) repair/replace/adjust damaged guestroom door with approved smoke enclosure door that operates correctly, fully self closes and latches (706, 807, 1001-b hc). (b) provide latch, repair, replace or adjust damaged window sashes, frames, balancers so they operate correctly and provide weather protection (703, 1001-b,h hc).
not activeJun 18, 2014
smoke detection section · in guestroom #420, correct all violations cited in the column to the right.
(a) repair/replace/adjust damaged guestroom door with approved smoke enclosure door that operates correctly, fully self closes and latches and provide door sweep (706, 807, 1001-b hc). (b) repair pipe penetration at ceiling and repaint (1001-b, 1306 hc). (c) repair light fixture (1001e hc).
not activeJun 18, 2014
other section · inspector comments
it is the property owner's responsibility to be present or direct his/her representative to attend the re-inspection as scheduled on this notice of violation for the purpose of providing entry to the inspector of those areas not accessed during the initial inspection as specified, and/or to provide access to all areas cited within this notice. if the property owner cannot attend the scheduled re-inspection (as specified on this notice) it is his/her responsibility to secure a different inspection date and time with the inspector, and provide all tenants with notification as required by california civil code section 1954 (san francisco housing code section 303(b), if any dwellings, apartment units or guest rooms are to be accessed during the re-inspection.
not activeJun 18, 2014
smoke detection section · in guestroom #331, correct all violations cited in the column to the right.
(a) provide designated guestroom number at entry door, should be a contrasting color (706 hc). (b) provide minimum 135 degree viewer on guestroom door (maximum height 58") (706 hc).
not activeJun 18, 2014
smoke detection section · in guestroom #107, correct all violations cited in the column to the right.
(a) repair/replace/adjust damaged guestroom door with approved smoke enclosure door that operates correctly, fully self closes and latches (706, 807, 1001-b hc). (b) provide minimum 135 degree viewer on guestroom door (maximum height 58") (706 hc).
not activeJun 18, 2014
smoke detection section · in guestroom #228, correct all violations cited in the column to the right.
(a) repair/replace damaged/rusted/chipped guestroom sink and faucets (505, 1001b,f hc).
not activeJun 18, 2014
smoke detection section · in guestroom #205, correct all violations cited in the column to the right.
(a) repair/replace/adjust damaged guestroom door with approved smoke enclosure door that operates correctly, fully self closes and latches (706, 807, 1001-b hc). (b) provide designated guestroom number at entry door, should be a contrasting color (706 hc).
not activeJun 18, 2014
smoke detection section · in guestroom #324, correct all violations cited in the column to the right.
(a) repair/replace/adjust damaged guestroom door with approved smoke enclosure door that operates correctly, fully self closes and latches (706, 807, 1001-b hc).
not activeJun 18, 2014
other section · inspector comments
repairs cited in this notice require a building permit, and may require plumbing and / or electrical permits. it is the responsibility of the owner to obtain (or have others obtain) any required permits before beginning work that requires (a) permit(s). this case can not be abated until the housing inspector makes a final inspection to verify that all violations have been corrected and all required permits have been obtained and finalized. on reinspection day, present to the housing inspector the job card, permit application and permits indicating that all required work under permit is complete. prior to reinspection by the housing inspector, call building, electrical and/or plumbing inspector(s) for required inspection(s).
not activeJun 18, 2014
smoke detection section · in guestroom #215, correct all violations cited in the column to the right.
(a) repair damaged wall above tv and repaint (1001-b, 1306 hc). (b) provide missing window latch (703, 1001-b,h hc). (c) provide designated guestroom number at entry door, should be a contrasting color (706 hc).
not activeJun 18, 2014
smoke detection section · in guestroom #317, correct all violations cited in the column to the right.
(a) remove clog and repair/replace damaged/rusted/chipped guestroom sink (505, 1001b,f hc).
not activeJun 18, 2014
smoke detection section · in guestroom #423, correct all violations cited in the column to the right.
(a) repair/replace/adjust damaged guestroom door with approved smoke enclosure door that operates correctly, fully self closes and latches (706, 807, 1001-b hc). (b) provide latch, repair, replace or adjust damaged window sashes, frames, balancers so they operate correctly and provide weather protection (703, 1001-b,h hc). (c) repair/replace damaged/rusted/chipped guestroom sink (505, 1001b,f hc). (d) provide minimum 135 degree viewer on guestroom door (maximum height 58") (706 hc).
not activeJun 18, 2014
building section · this notice includes violations for the areas noted.
hot rooms at various locations in hotel.
not activeJun 18, 2014
smoke detection section · in guestroom #416, correct all
(a) repair/replace/adjust damaged guestroom door with approved smoke enclosure door that operates correctly, fully self closes and latches (706, 807, 1001-b hc). (b) repair/replace damaged/rusted/chipped guestroom sink and faucets (505, 1001b,f hc). (c) provide minimum 135 degree viewer on guestroom door (maximum height 58") (706 hc).
not activeJun 18, 2014
smoke detection section · in guestroom #231, correct all violations cited in the column to the right.
(a) repair/replace/adjust damaged guestroom door with approved smoke enclosure door that operates correctly, fully self closes and latches (706, 807, 1001-b hc). (b) repair/replace damaged/rusted/chipped guestroom sink (505, 1001b,f hc).