not activeFeb 6, 2020
interior surfaces section · remove or cover damaged paint in an approved manner to prevent a lead hazard. see attached lead hazard warning. (1301 hc)
investigation revealed peeling paint throughout unit 504 at walls and ceilings of unit. remove and properly dispose severely peeling and flaking paint. note: it is the owner's responsibility to investigate for possible presence of lead based paint and remove, following procedures set forth by the san francisco health and building departments. consult with a qualified lead abatement contractor as required.
not activeFeb 6, 2020
interior surfaces section · disturbing lead based paint can be extremely dangerous to dwelling occupants and visitors, particularly to young children, pregnant women, pets, and to people performing work on the premises. for interior or exterior paint removal : always wet the surface, contain and properly dispose of leaded paint. if you are unsure whether the paint is leaded, you should test it prior to performing any work. if the paint is found to contain lead, you should consult with an expert about appropriate procedures. proper containment and 3-day notification is required for exterior jobs of more than 10 sq.ft. (sec.3423, sfbc) informational packets are available at (415) 558-6088. you can contact the san francisco childhood lead poisoning prevention program at: (415) 252-3800 for free advice. if you cause lead dust to be created, you could be liable for any illness caused by the dust. ordinance #446-97.
not activeFeb 6, 2020
interior surfaces section · paint ceilings/walls (1001b,1301 hc)
once flaking/peeling paint is removed throughout unit, re-paint unit.
not activeFeb 6, 2020
interior surfaces section · eliminate mold/mildew (1301,1001b(13),1306 hc)
eliminate mold/mildew at bathroom ceiling and bathtub.
not activeFeb 6, 2020
plumbing and electrical section · make necessary repairs to tub/shower (1001 hc)
replace deteriorated sealant/grout around bathtub. have bath tub wall properly repaired where duct tape has been placed.
not activeFeb 6, 2020
building section · general dilapidation or improper maintenance (1001 (b)(13))
replace missing door at bathroom.
not activeFeb 6, 2020
plumbing and electrical section · provide adequate lighting (504g hc)
repair flickering light bulb at kitchen ceiling light fixture.
not activeFeb 6, 2020
other section · general dilapidation or improper maintenance (1001 (b)(13))
provide replacement for broken mail key.
not activeFeb 6, 2020
other section · inspector comments
it is the property owner's responsibility to be present or direct his/her representative to attend, the re-inspection as scheduled on this notice of violation for the purpose of providing entry to the inspector of those areas not accessed during the initial inspection as specified, and/or to a access to all areas cited within this notice. if the property owner cannot attend the scheduled re-inspection (as specified on this notice) it is his/her responsibility to secure a different inspection date and time with the inspector, and provide all tenants with notification as required by california civil code section 1954 (san francisco housing code section 303(b), if any dwellings, apartment units or guest rooms are to be accessed during the re-inspection. correction of violations cited in this notice may require building, plumbing and/or electrical permits. it is the responsibility of the owner to obtain (or have others obtain) any required permits before beginning work that requires permit(s). when applying for a permit, reference the complaint number from this notice of violation. you must have the proper permit signed-off and finalized before housing inspector returns in order for this violation to be abated. important note: due to the nature of this violation, this property has been defined as a nuisance per section 1001(d) of the san francisco housing code.
not activeSep 20, 2018
building section · this notice includes violations for the areas noted.
common area
not activeSep 20, 2018
building section · repair defective or non-working elevator (1001(l), 713 hc)
at the time of inspection, two elevators were noted, with the elevator closest to the front entry disabled and service to the other elevator restored while inspector present (elevator door had been left ajar at basement level). restore service to disabled elevator and provide documentation re: repairs to inspector at the time of reinspection.
not activeSep 20, 2018
other section · inspector comments
due to the violations noted, this property constitutes a nuisance per the san francisco housing code section 1001(d). it is the property owner's responsibility to be present or direct his/her representative to attend, the reinspection as scheduled on this notice of violation for the purpose of providing entry to the inspector of those areas not accessed during the initial inspection as specified, and/or to provide access to all areas cited within this notice. if the property owner cannot attend the scheduled reinspection (as specified on this notice) it is his/her responsibility to secure a different inspection date and time with the inspector, and provide all tenants with notification as required by california civil code section 1954 (san francisco housing code section 303(b), if any dwellings, apartment units or guest rooms are to be accessed during the reinspection.
not activeFeb 23, 2009
building section · repair window latches or hardware (1001(b)hc)
at the time of inspection there was water on the bathroom floor under the window in #703. the bathroom window in #703 doesn't seal properly. repair/replace the missing weatherstrip along with any worn latches etc.
not activeFeb 23, 2009
building section · repair weather proofing on stucco (1001(h),703 hc)
seal the gaps/breaks in the stucco outside of and surrounding the bathroom window of #703.
not activeFeb 23, 2009
smoke detection section · repair central alarm system (908, 909 hc)
provide a new annual certification for the alarm system panel last inspected on 1/2008.
not activeFeb 23, 2009
fire section · remove egress obstruction at (801,1001(l) hc)
remove the chains obstructing the roof access stairway; this is an emergency path of egress.
not activeFeb 23, 2009
other section · inspector comments
note: on reinspection day, property manager, owner or the owner's agent needs to demonstrate the workability of the fire escape ladders. the fire escapes are to be checked on all buildings during the course of a routine inspection. non-working fire escape ladder is a life safety hazard and must be corrected immediately. provide a written and signed report from a qualified service company or contractor stating that all parts and cables have been tested and are functional or you are required to lower the ladder on re-inspection day to verify its proper full release. reminder: test and verify that all windows or doors leading to emergency fire escape are operational and unobstructed. advise occupants not to block the path of emergency exits on the inside. **reminder**all manufacturers recommend that the fire escape drop ladder be maintained and serviced annually, particularly the cable and all moving parts. lubricate and drop the ladder at least once a year.
not activeFeb 23, 2009
other section · inspector comments
it is the property owner's responsibility to be present or direct his/her representative to attend the reinspection as scheduled on this notice of violation for the purpose of providing entry to the inspector of those areas not accessed during the initial inspection as specified, and/or to provide access to all areas cited within this notice. if the property owner cannot attend the scheduled reinspection (as specified on this notice) it is his/her responsibility to secure a different inspection date and time with the inspector, and provide all tenants with notification as required by california civil code section 1954 (san francisco housing code section 303(b), if any dwellings, apartment units or guest rooms are to be accessed during the reinspection.
not activeFeb 20, 2007
fire section · remove flammable storage (904,1001(i) hc)
remove the flammable storage in the basement or store under a sprinkler head in a closed metal cabinet.
not activeFeb 20, 2007
other section · inspector comments
it is the property owner's responsibility to be present or direct his/her representative to attend the reinspection as scheduled on this notice of violation for the purpose of providing entry to the inspector of those areas not accessed during the initial inspection as specified, and/or to provide access to all areas cited within this notice. if the property owner cannot attend the scheduled reinspection (as specified on this notice) it is his/her responsibility to secure a different inspection date and time with the inspector, and provide all tenants with notification as required by california civil code section 1954 (san francisco housing code section 303(b), if any dwellings, apartment units or guest rooms are to be accessed during the reinspection.
not activeFeb 14, 2007
other section · provide heat to each occupied habitable room for 13 hrs between 5:00 a.m. and 11:00 a.m. and between 3:00 p.m. and 10:00 p.m. capable to maintaining a min. room temp. of 68 degrees f. (20 degrees c.). (701c hc)
complete the repairs in progress at the time of inspection and provide the required heat.
not activeFeb 14, 2007
other section · inspector comments
it is the property owner's responsibility to be present or direct his/her representative to attend the reinspection as scheduled on this notice of violation for the purpose of providing entry to the inspector of those areas not accessed during the initial inspection as specified, and/or to provide access to all areas cited within this notice. if the property owner cannot attend the scheduled reinspection (as specified on this notice) it is his/her responsibility to secure a different inspection date and time with the inspector, and provide all tenants with notification as required by california civil code section 1954 (san francisco housing code section 303(b), if any dwellings, apartment units or guest rooms are to be accessed during the reinspection.
not activeJan 29, 2007
sanitation section · provide adequate number of garbage receptacles (1304 hc)
there was garbage stored in bags in the basement at the time of inspection. provide an adequate number of garbage receptacles.
not activeJan 29, 2007
other section · provide resident manager info(1311 hc)
list the resident manager on the call box at the buildings entrance. provide manager contact info in the lobby of the building.
not activeJan 29, 2007
security requirements section · provide self-closing devices at exterior doors (706 hc)
provide a self closing device for the rear security gate at the tradesmans alley.
not activeJan 29, 2007
security requirements section · provide deadlatch locks with min 1/2" throw at exit doors (706 hc)
provide a self locking deadlatch to the security gate at the street side of the tradesmans alley.
not activeJan 29, 2007
other section · inspector comments
note: on reinspection day, property manager, owner or the owner's agent needs to demonstrate the workability of the fire escape ladders. the fire escapes are to be checked on all buildings during the course of a routine inspection. non-working fire escape ladder is a life safety hazard and must be corrected immediately. provide a written and signed report from a qualified service company or contractor stating that all parts and cables have been tested and are functional or you are required to lower the ladder on re-inspection day to verify its proper full release. reminder: test and verify that all windows or doors leading to emergency fire escape are operational and unobstructed. advise occupants not to block the path of emergency exits on the inside. **reminder**all manufacturers recommend that the fire escape drop ladder be maintained and serviced annually, particularly the cable and all moving parts. lubricate and drop the ladder at least once a year.
not activeJan 29, 2007
fire section · remove egress obstruction at (801,1001(l) hc)
remove the egress obstructions, drywall etc., in the tradesmans alley.
not activeJan 29, 2007
building section · adjust elevator doors (1001 b hc)
adjust the elevator doors so they close and permit the elevator cab to move to other floors.
not activeJan 29, 2007
other section · provide shutoff tool for gas utility shutoff (712 hc)
the existing gas wrench is tethered with a wire cable that's to short to allow it to reach the gas shutoffs. correct the problem.
not activeJan 29, 2007
other section · post enclosed gas meter instructional diagram in a public area. (712 hc)
not activeJan 29, 2007
other section · inspector comments
it is the property owner's responsibility to be present or direct his/her representative to attend the reinspection as scheduled on this notice of violation for the purpose of providing entry to the inspector of those areas not accessed during the initial inspection as specified, and/or to provide access to all areas cited within this notice. at the time of inspection provide access to all common areas including the roof, basement, boiler room, time clock, and all storage areas. if the property owner cannot attend the scheduled reinspection (as specified on this notice) it is his/her responsibility to secure a different inspection date and time with the inspector, and provide all tenants with notification as required by california civil code section 1954 (san francisco housing code section 303(b), if any dwellings, apartment units or guest rooms are to be accessed during the reinspection.
not activeJan 29, 2007
other section · inspector comments
at the time of inspection the boiler time clock was not properly set. the inspector reset the clock to the correct afternoon setting for turning on the boiler.
not activeJan 16, 2007
other section · set timeclock to provide the required amount and hours of heat. (701c hc)
boiler time clock is improperly set; not providing the minimum required hours of heat.
not activeJan 16, 2007
other section · provide non-tamperable temp.-sensing device with a + to -1 1/2 degree f. (.8 degrees c.) tol., centrally located in bldg in habitable rm (not mgr or owner's) to which heat is provided, occupied or not (701c hc)
provide access to the thermostat. the thermostat must be centrally located, 3rd or 4th floor, on the cool side of the building.
not activeJan 16, 2007
other section · post the current boiler certification in the boiler room.
the boiler certification now posted is out of date. post the current certification in the boiler room in a conspicous place.
not activeJan 16, 2007
smoke detection section · repair central alarm system (908, 909 hc)
provide a new annual certification for the alarm panel. the current sticker with years of dates inked in does not meet housing code standards.
not activeJan 16, 2007
other section · provide heat to each occupied habitable room for 13 hrs between 5:00 a.m. and 11:00 a.m. and between 3:00 p.m. and 10:00 p.m. capable to maintaining a min. room temp. of 68 degrees f. (20 degrees c.). (701c hc)
provide a source of heat to #101.
not activeJan 16, 2007
other section · inspector comments
it is the property owner's responsibility to be present or direct his/her representative to attend the reinspection as scheduled on this notice of violation for the purpose of providing entry to the inspector of those areas not accessed during the initial inspection as specified, and/or to provide access to all areas cited within this notice. if the property owner cannot attend the scheduled reinspection (as specified on this notice) it is his/her responsibility to secure a different inspection date and time with the inspector, and provide all tenants with notification as required by california civil code section 1954 (san francisco housing code section 303(b), if any dwellings, apartment units or guest rooms are to be accessed during the reinspection.
not activeJan 24, 2005
building section · 1)repair leaking ,malfunctioning toilet unit in apt#1103,causing damaged ceiling surfaces in bathroom apt#1003.1001hc. 2)remove,contain and properly dispose of peeling,water damaged paint and plaster along the walls and ceiling surfaces in bathroom #1003.1001hc. 3)replaster and paint batrhoom in apt #1003,throughout.1301hc.
damaged walls and ceiling surfaces in bathroom apt#1003,in need to be repaired and painted.
not activeJan 20, 2005
building section · repair drefective toilet unit in apt. 604,causing soiled water to discharge through the bathroom ceiling in apt#504.1001hc.
defective toilet unit in apt #604
not activeJan 20, 2005
building section · 1)remove,contain and properly dispose of water damaged ,peeling paint and plaster from bathroom ceiling surfaces in apt #505. 2)resheetrock damaged ceiling surfaces,replaster and paint bathroom in apt #504,throughout.1001hc./13001hc.
damaged bathroom ceiling surfaces.
not activeJan 10, 2005
building section · 1)assess cause and eliminate overhead leaks causing water seepage along dining room wall surfaces facing leavenworth st.1001hc. 2)have exterior siding,gutters and drainage inspected by a qualified contractor. 3)remove and abate mold from base of diningroom wall surfaces.1306hc.
1)water seepage from the exterior of the structure,causing wet dining room wall surfaces 2)moldy dining room wall surfaces due to traped in moisture,constituting a potential health hazard to the occupant of apt#702.
not activeJan 10, 2005
building section · 1)repair overhead leaks in bathroom apt#802,causing ceiling damage to bathroom apt#702.1001hc. 2)remove mold from bathroom walls and ceiling surfaces,as well as areas under,side of bathroom window in apt#702.1001hc./1306hc.
overhead leaks from apt#802 in need of repairs.
not activeOct 26, 2004
building section · 1)service,restore inoperative boiler unit. 2)provide 68 degrees f. to each habitable room from:5:00 am-11:00 am 3:00 pm-10:00 pm. 701hc./1001hc.
inoperative boiler.
not activeJul 19, 2004
building section · recharge hallway fire extinguishers.905hc.
expired hallway fire extinguishers.
not activeJul 19, 2004
building section · service front and rear fire escape ladder and cables.1001hc.
fire escape ladder and cable in need to be serviced,to assure proper operation.
not activeJul 19, 2004
building section · install an approoved handrail along: 1)side passageway stairs leading to street. 2)rear exterior stairs leading to the garden area.1001hc.
side and rear stairs are lacking requiered handrails.
not activeJul 13, 2004
building section · replace double cylinder half an inch dead latch locking device with a single cylinder type,openable from the inside without any effort,key or special knowledge.706hc./801hc./1001hc.
double cylinder half an inch dead latch is constituting an egress obstruction as well as a life and safety hazard.
not activeJan 14, 2002
other section · lack of hot water to the premises.
1)reinstate hot water to premises. 2)provide 105-120 degrees f. to each habitable dwelling.505hc.