919 SUTTER ST

Nob Hill · San Francisco, CA · Parcel 0300020 · Last violation Jan 27, 2025 · Last complaint Aug 16, 2026

NeighborhoodNob Hill
More violations than 90% of nearby buildings
More violations than 90% of buildings and more complaints than 95% of buildings in Nob Hill. Size-normalized against residential buildings in the neighborhood.
ViolationsComplaints
Activity TrendsLast 5 years
More activity recently than in past years
Last 2 yrs: 15 violations · 17 complaints
'21'26ViolationsComplaints
Severityⓘopen violations
All DBI violations have been resolved
Notices of Violation issued by the Department of Building Inspection, by current status.
Severe0
Serious0
Minor0

What to watch forⓘ

  1. Fire safety problems have been reported here.
    Worth checkingⓘ
    Walk the exit route from the unit to the street and check the stairs and hallways are clear of stored items, and that fire doors close properly.
    details ▸

    California law requires safe fire or emergency exits leading to a street or hallway, and requires stairs, hallways and exits to be kept litter free. Storage areas, garages and basements must be kept free of combustible materials. San Francisco's Housing Code separately treats inadequate exits and inadequate fire protection equipment as conditions that make a building substandard, which is the finding behind a notice of violation.

    • California Tenant Guide
    • San Francisco Housing Code §1001(m), (n)
  2. Tenants here have reported pests.
    Worth checkingⓘ
    Look along baseboards and inside low cabinets for droppings, greasy rub marks or tracks, and check whether the bins outside overflow and whether gaps around exterior doors are sealed.
311 Housing Complaints
Total complaints since 2012
21
1 per year avg.↑ Up 750% in the last 2 years (17 vs 2 prior 2 yrs)
Complaint severity
Last 5 years
18
Severeⓘ3
Seriousⓘ9
Minorⓘ6
Dept. of Building Inspection Violations
Total violations since 1997
38
1 per year avg.↑ Rising — no prior history
Open violations
0
No open DBI violations on record.

Top violation categories

5 yrsAll time
Walls, ceilings & cabinetsⓘ6 violations
Plumbingⓘ4 violations
Peeling paintⓘ3 violations
Fire safetyⓘ2 violations
Heating equipmentⓘ2 violations
Moldⓘ2 violations
Cleanliness & refuseⓘ2 violations
Ventilation & lightⓘ2 violations
Smoke detectorsⓘ1 violations
Floors & stairsⓘ1 violations
Heat / hot waterⓘ1 violations
Exterior & windowsⓘ1 violations
No specific condition stated11 violations
See violation log below.

Top complaint types

5 yrsAll time
Infestation Rodent Insect8 complaints
Clutter Hoarder Unit Interior Storage3 complaints
Electrical Non Hazard2 complaints
Electrical Hazardous Condition2 complaints
Mold And Mildew1 complaints
Paint Peeling1 complaints
Plumbing Broken Leaking1 complaints
Fire Hazard1 complaints
Hot Water Lack Of Hot Water1 complaints
Illegal Construction No Permit Exceeds Permit Scope1 complaints
Hide violations (38) ↑See complaints (21) →

Violation log

38 DBI violations

AllOpenClosed
StatusFiledCategoryItemNOV Item Description
not activeJan 27, 2025building sectionthis notice includes violations for the areas noted.919 sutter street unit#20 and all common area
See something wrong? File a complaint with SF 311
details ▸

California law requires buildings and grounds to be kept clean and sanitary and free from debris, filth, rubbish, garbage, rodents and vermin. San Francisco requires property owners to keep their property free of vermin, and requires an owner or manager to respond to a tenant's bed bug complaint by hiring a licensed pest control operator.

  • California Tenant Guide
  • SF.gov, Keeping your building free of vermin
  • Tenants here have reported mold.
    Worth checkingⓘ
    Look for dark spots on walls, floors and ceilings, and for dry or wet spots, flaking or bubbling, or a damp or moldy smell, especially in bathrooms and closets.
    details ▸

    San Francisco's Health Code treats visible or otherwise demonstrable mold or mildew in a residential building as a public health nuisance in its own right. Under state law, mold that the landlord has notice of and that affects livability or health can also breach the implied warranty of habitability.

    • California Tenant Guide
    • San Francisco Health Code §581(b)(6)
  • not activeJan 27, 2025interior surfaces sectionrepair damaged ceilings (1001b,h,o hc)at time of inspection, leak damage was observed in unit#20. repair and repaint damaged area in an approved manner. at time of inspection, no active leak was observed. however, there were signs of possible leak in the past. locate and repair source of leak if necessary.
    not activeJan 27, 2025fire sectionservice central alarm system (908, 909 hc)at time of inspection, fire alarm system certificate is expired. have licensed fire alarm company service / certify fire alarm system - required each year.
    not activeJan 27, 2025plumbing and electrical sectionrepair sink (1001f hc)at time of inspection, damage was observed around kitchen sink in unit#20. repair or replace damaged area around kitchen sink.
    not activeJan 27, 2025interior surfaces sectioneliminate mold/mildew on walls (1301,1001b(13),1306 hc)at time of inspection, mold/mildew was observed around windows in unit#20. eliminate mold/mildew.
    not activeJan 27, 2025other sectioninspector commentsit is the property owner's responsibility to be present or direct his/her representative to attend the re-inspection as scheduled on this notice of violation for the purpose of providing entry to the inspector of those areas not accessed during the initial inspection as specified, and/or to provide access to all areas cited within this notice. if the property owner cannot attend the scheduled reinspection (as specified on this notice) it is his/her responsibility to secure a different inspection date and time with the inspector. provide all tenants with notification as required by california civil code section 1954 (san francisco housing code section 303(b), if any dwellings, apartment units or guest rooms are to be accessed during the re-inspection. you can reach inspector lee @ 415-793-7947 or by email at joy.lee@sfgov.org.
    not activeJan 16, 2025building sectionthis notice includes violations for the areas noted.919 sutter street unit#20 and all common area
    not activeJan 16, 2025other sectionprovide heat to each occupied habitable room capable of maintaining a min. room temp. of 70 degrees f. (21 degrees c.). (701(a) hc)at the time of inspection heating wall unit did not work. repair or replace heating unit to provide adequate heat to habitable rooms in unit. work for this must begin within 3 working days of receiving this notice. if new heating source is installed, please attain all necessary permits, including plumbing, mechanical, electric and building permits. all permits must be finalized prior to housing inspector reinspection, in order to abate this item.
    not activeJan 16, 2025other sectioninspector commentsit is the property owner's responsibility to be present or direct his/her representative to attend the re-inspection as scheduled on this notice of violation for the purpose of providing entry to the inspector of those areas not accessed during the initial inspection as specified, and/or to provide access to all areas cited within this notice. if the property owner cannot attend the scheduled reinspection (as specified on this notice) it is his/her responsibility to secure a different inspection date and time with the inspector. provide all tenants with notification as required by california civil code section 1954 (san francisco housing code section 303(b), if any dwellings, apartment units or guest rooms are to be accessed during the re-inspection. you can reach inspector lee @ 415-793-7947 or by email at joy.lee@sfgov.org.
    not activeJan 16, 2025interior surfaces section——
    not activeJan 13, 2025building sectionthis notice includes violations for the areas noted.919 sutter street unit#24 and all common area
    not activeJan 13, 2025interior surfaces sectionrepair damaged ceilings (1001b,h,o hc)at time of inspection, damage was observed in the following areas in unit#24: living room and bedroom ceiling, kitchen. repair and repaint in an approved manner. at time of inspection, no active leak was observed. however, there were signs of possible leak in the past. locate and repair source of leak if necessary.
    not activeJan 13, 2025interior surfaces sectionrepair floor covering (1001b,j,o hc)at time of inspection, damage on floor covering was observed in unit#24 kitchen area. repair or replace in an approved manner.
    not activeJan 13, 2025interior surfaces sectioneliminate mold/mildew on walls (1301,1001b(13),1306 hc)at time of inspection, mold/mildew was observed in unit#24 kitchen cabinet. eliminate mold/mildew in an approved manner.
    not activeJan 13, 2025other sectioninspector commentsit is the property owner's responsibility to be present or direct his/her representative to attend the re-inspection as scheduled on this notice of violation for the purpose of providing entry to the inspector of those areas not accessed during the initial inspection as specified, and/or to provide access to all areas cited within this notice. if the property owner cannot attend the scheduled reinspection (as specified on this notice) it is his/her responsibility to secure a different inspection date and time with the inspector. provide all tenants with notification as required by california civil code section 1954 (san francisco housing code section 303(b), if any dwellings, apartment units or guest rooms are to be accessed during the re-inspection. you can reach inspector lee @ 415-793-7947 or by email at joy.lee@sfgov.org.
    not activeFeb 3, 2021Heating equipment—No permit to operate the boiler. serial no E 04CC0171, CMC 1022. Monthly monitoring fee applies. Code Sec: SFBC 110A, Table 1A-K
    not activeAug 8, 2016Heating equipment—No permit to operate the boiler. serial no E 04CC0171, CMC 1022
    not activeOct 4, 2012building sectionthis notice includes violations for the areas noted.919 sutter street apartment #5
    not activeOct 4, 2012plumbing and electrical sectionreplace toilet (1001f hc)replace cracked toilet.
    not activeOct 4, 2012interior surfaces sectionrepair damaged walls and ceiling (1001b,h,o hc)repair all cracks in back room, replace all damaged area in order to prevent any plaster from falling.
    not activeOct 4, 2012interior surfaces sectionpaint walls and ceiling (1001b,1301 hc)paint walls and ceiling in back room comments regarding possible lead based paint "disturbing lead based paint can be extremely dangerous to dwelling occupants and visitors, particularly to young children, pregnant women, pets, and to people performing work on the premises. for interior or exterior paint removal : always wet the surface, contain and properly dispose of leaded paint. if you are unsure whether the paint is leaded, you should test it prior to performing any work. if the paint is found to contain lead, you should consult with an expert about appropriate procedures. proper containment and 3-day notification is required for exterior jobs of more than 10 square feet. (sec.3604, sfbc) informational packets are available at (415) 558-6088. you can contact the san francisco childhood lead poisoning prevention program at: (415) 554-8930 for free advice. if you cause lead dust to be created, you could be liable for any illness caused by the dust. ordinance #446-97."
    not activeOct 4, 2012interior surfaces sectionpaint walls and ceiling (1001b,1301 hc)bathroom was not properly prepared for painting and therefore the ceiling must be sanded down and all areas of peeling paint must be scraped and then paint can be applied with the proper semi gloss and not a flat based paint.
    not activeOct 4, 2012other sectioninspector commentsinspector comments regarding "follow up" reinspection: i have scheduled a reinspection of your building on thursday, 15-november-2012 at 2:00 pm. reinspection of premise to include all areas referenced above. please contact inspector galvis to confirm appointment at 415-558-6513. it is the property owners responsibility to be present or direct his/her representative to attend, the reinspection as scheduled on this notice of violation for the purpose of providing entry to the inspector of those areas cited within this notice. if the property owner cannot attend the scheduled reinspection (as specified on this notice) it is his/her responsibility to secure a different inspection date and time with the inspector. on scheduled reinspection day, provide the inspector with a full access to all common and public areas per attached checklist. your cooperation is appreciated.
    not activeJul 24, 2012building sectionthis notice includes violations for the areas noted.919 sutter street apartment #5 and common areas.
    not activeJul 24, 2012fire sectionpermanently remove combustible storage. (904, 1001(i) hc)remove all items from lower corridor leading to exit at front of building.
    not activeJul 24, 2012interior surfaces sectionlocate source of water damage (703, 1001f hc)in bathroom, bathroom closet, hallway closet and hallway in apartment #5
    not activeJul 24, 2012interior surfaces sectionrepair source of water damage (703,1001f hc)in bathroom, bathroom closet, hallway closet and hallway in apartment #5
    not activeJul 24, 2012interior surfaces sectionrepair damaged ceilings and walls (1001b,h,o hc)remove damaged ceiling around light fixture in bathroom and hallway closet and remove damaged walls in closet in bathroom and hallway in apartment #5
    not activeJul 24, 2012interior surfaces sectionpaint ceilings and walls (1001b,1301 hc)in bathroom, bathroom closet, hallway closet and hallway in apartment #5
    not activeJul 24, 2012plumbing and electrical sectionprovide adequate lighting (504g hc)in lower corridor at exit door leading to sutter street
    not activeJul 24, 2012security requirements sectionprovide self-closing device at exterior door (706 hc)at lower corridor door leading to sutter street, also repair door in order to keep it from sticking, door has accumulated paint that does not allow it to open easily.
    not activeJul 24, 2012other sectioninspector commentsinspector comments regarding "follow up" reinspection: i have scheduled a reinspection of your building on wednesday, 15-august-2012 at 9:30 am. reinspection of premise to include all areas referenced above. please contact inspector galvis to confirm appointment at 415-558-6513. it is the property owners responsibility to be present or direct his/her representative to attend, the reinspection as scheduled on this notice of violation for the purpose of providing entry to the inspector of those areas cited within this notice. if the property owner cannot attend the scheduled reinspection (as specified on this notice) it is his/her responsibility to secure a different inspection date and time with the inspector. on scheduled reinspection day, provide the inspector with a full access to all common and public areas per attached checklist. your cooperation is appreciated.
    not activeDec 2, 1999building sectionhallway light fixturereplace 2nd floor hallway light fixture.
    not activeDec 2, 1999building sectionrubbishremove rubbish and debries from basement,boiler room, passageway.1306hc.
    not activeDec 2, 1999building sectiongarbage chute coverinstall a cover over top of garbage chute.1001hc.
    not activeJan 27, 1997interior surfaces sectionrepair damaged walls (1001b,h,o hc)apt. unit #5: rear den room - defective/cracks in interior and exterior walls. 1001 hc.
    not activeJan 27, 1997interior surfaces sectionrepair damaged ceilings (1001b,h,o hc)apt. unit #5 - bubbling ceiling paint in rear den room. 1001 hc.
    not activeJan 27, 1997other sectionmiscellaneous violationsapt. unit #5: rear den room - locate source and repair any associated water leakage in the roof. 1001 hc.
    not activeJan 27, 2025
    building section · this notice includes violations for the areas noted.
    919 sutter street unit#20 and all common area
    not activeJan 27, 2025
    interior surfaces section · repair damaged ceilings (1001b,h,o hc)
    at time of inspection, leak damage was observed in unit#20. repair and repaint damaged area in an approved manner. at time of inspection, no active leak was observed. however, there were signs of possible leak in the past. locate and repair source of leak if necessary.
    not activeJan 27, 2025
    fire section · service central alarm system (908, 909 hc)
    at time of inspection, fire alarm system certificate is expired. have licensed fire alarm company service / certify fire alarm system - required each year.
    not activeJan 27, 2025
    plumbing and electrical section · repair sink (1001f hc)
    at time of inspection, damage was observed around kitchen sink in unit#20. repair or replace damaged area around kitchen sink.
    not activeJan 27, 2025
    interior surfaces section · eliminate mold/mildew on walls (1301,1001b(13),1306 hc)
    at time of inspection, mold/mildew was observed around windows in unit#20. eliminate mold/mildew.
    not activeJan 27, 2025
    other section · inspector comments
    it is the property owner's responsibility to be present or direct his/her representative to attend the re-inspection as scheduled on this notice of violation for the purpose of providing entry to the inspector of those areas not accessed during the initial inspection as specified, and/or to provide access to all areas cited within this notice. if the property owner cannot attend the scheduled reinspection (as specified on this notice) it is his/her responsibility to secure a different inspection date and time with the inspector. provide all tenants with notification as required by california civil code section 1954 (san francisco housing code section 303(b), if any dwellings, apartment units or guest rooms are to be accessed during the re-inspection. you can reach inspector lee @ 415-793-7947 or by email at joy.lee@sfgov.org.
    not activeJan 16, 2025
    building section · this notice includes violations for the areas noted.
    919 sutter street unit#20 and all common area
    not activeJan 16, 2025
    other section · provide heat to each occupied habitable room capable of maintaining a min. room temp. of 70 degrees f. (21 degrees c.). (701(a) hc)
    at the time of inspection heating wall unit did not work. repair or replace heating unit to provide adequate heat to habitable rooms in unit. work for this must begin within 3 working days of receiving this notice. if new heating source is installed, please attain all necessary permits, including plumbing, mechanical, electric and building permits. all permits must be finalized prior to housing inspector reinspection, in order to abate this item.
    not activeJan 16, 2025
    other section · inspector comments
    it is the property owner's responsibility to be present or direct his/her representative to attend the re-inspection as scheduled on this notice of violation for the purpose of providing entry to the inspector of those areas not accessed during the initial inspection as specified, and/or to provide access to all areas cited within this notice. if the property owner cannot attend the scheduled reinspection (as specified on this notice) it is his/her responsibility to secure a different inspection date and time with the inspector. provide all tenants with notification as required by california civil code section 1954 (san francisco housing code section 303(b), if any dwellings, apartment units or guest rooms are to be accessed during the re-inspection. you can reach inspector lee @ 415-793-7947 or by email at joy.lee@sfgov.org.
    not activeJan 16, 2025
    interior surfaces section
    not activeJan 13, 2025
    building section · this notice includes violations for the areas noted.
    919 sutter street unit#24 and all common area
    not activeJan 13, 2025
    interior surfaces section · repair damaged ceilings (1001b,h,o hc)
    at time of inspection, damage was observed in the following areas in unit#24: living room and bedroom ceiling, kitchen. repair and repaint in an approved manner. at time of inspection, no active leak was observed. however, there were signs of possible leak in the past. locate and repair source of leak if necessary.
    not activeJan 13, 2025
    interior surfaces section · repair floor covering (1001b,j,o hc)
    at time of inspection, damage on floor covering was observed in unit#24 kitchen area. repair or replace in an approved manner.
    not activeJan 13, 2025
    interior surfaces section · eliminate mold/mildew on walls (1301,1001b(13),1306 hc)
    at time of inspection, mold/mildew was observed in unit#24 kitchen cabinet. eliminate mold/mildew in an approved manner.
    not activeJan 13, 2025
    other section · inspector comments
    it is the property owner's responsibility to be present or direct his/her representative to attend the re-inspection as scheduled on this notice of violation for the purpose of providing entry to the inspector of those areas not accessed during the initial inspection as specified, and/or to provide access to all areas cited within this notice. if the property owner cannot attend the scheduled reinspection (as specified on this notice) it is his/her responsibility to secure a different inspection date and time with the inspector. provide all tenants with notification as required by california civil code section 1954 (san francisco housing code section 303(b), if any dwellings, apartment units or guest rooms are to be accessed during the re-inspection. you can reach inspector lee @ 415-793-7947 or by email at joy.lee@sfgov.org.
    not activeFeb 3, 2021
    Heating equipment
    No permit to operate the boiler. serial no E 04CC0171, CMC 1022. Monthly monitoring fee applies. Code Sec: SFBC 110A, Table 1A-K
    not activeAug 8, 2016
    Heating equipment
    No permit to operate the boiler. serial no E 04CC0171, CMC 1022
    not activeOct 4, 2012
    building section · this notice includes violations for the areas noted.
    919 sutter street apartment #5
    not activeOct 4, 2012
    plumbing and electrical section · replace toilet (1001f hc)
    replace cracked toilet.
    not activeOct 4, 2012
    interior surfaces section · repair damaged walls and ceiling (1001b,h,o hc)
    repair all cracks in back room, replace all damaged area in order to prevent any plaster from falling.
    not activeOct 4, 2012
    interior surfaces section · paint walls and ceiling (1001b,1301 hc)
    paint walls and ceiling in back room comments regarding possible lead based paint "disturbing lead based paint can be extremely dangerous to dwelling occupants and visitors, particularly to young children, pregnant women, pets, and to people performing work on the premises. for interior or exterior paint removal : always wet the surface, contain and properly dispose of leaded paint. if you are unsure whether the paint is leaded, you should test it prior to performing any work. if the paint is found to contain lead, you should consult with an expert about appropriate procedures. proper containment and 3-day notification is required for exterior jobs of more than 10 square feet. (sec.3604, sfbc) informational packets are available at (415) 558-6088. you can contact the san francisco childhood lead poisoning prevention program at: (415) 554-8930 for free advice. if you cause lead dust to be created, you could be liable for any illness caused by the dust. ordinance #446-97."
    not activeOct 4, 2012
    interior surfaces section · paint walls and ceiling (1001b,1301 hc)
    bathroom was not properly prepared for painting and therefore the ceiling must be sanded down and all areas of peeling paint must be scraped and then paint can be applied with the proper semi gloss and not a flat based paint.
    not activeOct 4, 2012
    other section · inspector comments
    inspector comments regarding "follow up" reinspection: i have scheduled a reinspection of your building on thursday, 15-november-2012 at 2:00 pm. reinspection of premise to include all areas referenced above. please contact inspector galvis to confirm appointment at 415-558-6513. it is the property owners responsibility to be present or direct his/her representative to attend, the reinspection as scheduled on this notice of violation for the purpose of providing entry to the inspector of those areas cited within this notice. if the property owner cannot attend the scheduled reinspection (as specified on this notice) it is his/her responsibility to secure a different inspection date and time with the inspector. on scheduled reinspection day, provide the inspector with a full access to all common and public areas per attached checklist. your cooperation is appreciated.
    not activeJul 24, 2012
    building section · this notice includes violations for the areas noted.
    919 sutter street apartment #5 and common areas.
    not activeJul 24, 2012
    fire section · permanently remove combustible storage. (904, 1001(i) hc)
    remove all items from lower corridor leading to exit at front of building.
    not activeJul 24, 2012
    interior surfaces section · locate source of water damage (703, 1001f hc)
    in bathroom, bathroom closet, hallway closet and hallway in apartment #5
    not activeJul 24, 2012
    interior surfaces section · repair source of water damage (703,1001f hc)
    in bathroom, bathroom closet, hallway closet and hallway in apartment #5
    not activeJul 24, 2012
    interior surfaces section · repair damaged ceilings and walls (1001b,h,o hc)
    remove damaged ceiling around light fixture in bathroom and hallway closet and remove damaged walls in closet in bathroom and hallway in apartment #5
    not activeJul 24, 2012
    interior surfaces section · paint ceilings and walls (1001b,1301 hc)
    in bathroom, bathroom closet, hallway closet and hallway in apartment #5
    not activeJul 24, 2012
    plumbing and electrical section · provide adequate lighting (504g hc)
    in lower corridor at exit door leading to sutter street
    not activeJul 24, 2012
    security requirements section · provide self-closing device at exterior door (706 hc)
    at lower corridor door leading to sutter street, also repair door in order to keep it from sticking, door has accumulated paint that does not allow it to open easily.
    not activeJul 24, 2012
    other section · inspector comments
    inspector comments regarding "follow up" reinspection: i have scheduled a reinspection of your building on wednesday, 15-august-2012 at 9:30 am. reinspection of premise to include all areas referenced above. please contact inspector galvis to confirm appointment at 415-558-6513. it is the property owners responsibility to be present or direct his/her representative to attend, the reinspection as scheduled on this notice of violation for the purpose of providing entry to the inspector of those areas cited within this notice. if the property owner cannot attend the scheduled reinspection (as specified on this notice) it is his/her responsibility to secure a different inspection date and time with the inspector. on scheduled reinspection day, provide the inspector with a full access to all common and public areas per attached checklist. your cooperation is appreciated.
    not activeDec 2, 1999
    building section · hallway light fixture
    replace 2nd floor hallway light fixture.
    not activeDec 2, 1999
    building section · rubbish
    remove rubbish and debries from basement,boiler room, passageway.1306hc.
    not activeDec 2, 1999
    building section · garbage chute cover
    install a cover over top of garbage chute.1001hc.
    not activeJan 27, 1997
    interior surfaces section · repair damaged walls (1001b,h,o hc)
    apt. unit #5: rear den room - defective/cracks in interior and exterior walls. 1001 hc.
    not activeJan 27, 1997
    interior surfaces section · repair damaged ceilings (1001b,h,o hc)
    apt. unit #5 - bubbling ceiling paint in rear den room. 1001 hc.
    not activeJan 27, 1997
    other section · miscellaneous violations
    apt. unit #5: rear den room - locate source and repair any associated water leakage in the roof. 1001 hc.