Class COpen
Sep 30, 2026Apt B3
ABATE THE NUISANCE OF MICE · EXTERMINATION & RODENT ERADICATION
HMC ADM CODE: § 27-2017.4 ABATE THE INFESTATION CONSISTING OF MICE IN THE ENTIRE APARTMENT LOCATED AT APT B3, 1st STORY, 2nd APARTMENT FROM WEST AT NORTH
Class COpen
Sep 30, 2026
MAKE DOORS SELF-CLOSING · EGRESS
§ 27-2005, 27-2007, 27-2041.1 HMC, §238, § 309; § 107 (2) ( C) MDL AND 28 RCNY §25-171: REPLACE OR REPAIR THE SELF-CLOSING DOORS THAT IS MISSING OR DEFECTIVE HINGES AT 1ST FIRE DOOR FROM EAST AT SOUTH LEADING TO STAIR A AT PUBLIC HALL AT BASEMENT
Class BOpen
Sep 30, 2026Apt B5
ABATE THE NUISANCE · MAINTENANCE
§ 27-2005 ADM CODE & 309 M/D LAW ABATE THE NUISANCE CONSISTING OF MECHANCIAL VENTILATION SYSTEM SEALED UP AT NORTH WALL IN THE BATHROOM LOCATED AT APT B5, 1st STORY, 3rd APARTMENT FROM EAST AT SOUTH
Class COpen
Sep 30, 2026Apt B3
ABATE THE NUISANCE OF ROACHES · EXTERMINATION & RODENT ERADICATION
HMC ADM CODE: § 27-2017.4 ABATE THE INFESTATION CONSISTING OF ROACHES IN THE ENTIRE APARTMENT LOCATED AT APT B3, 1st STORY, 2nd APARTMENT FROM WEST AT NORTH
Class BOpen
Sep 30, 2026
SECURE LOOSE MATTER · MAINTENANCE
§ 27-2005 ADM CODE PROPERLY SECURE THE LOOSE VINYL COVER 6TH TREAD FROM BOTTOM AT 2nd PUBLIC HALL STAIRS FROM EAST, 2nd STORY
Class BOpen
Sep 30, 2026
REPAIR THE SOURCE AND ABATE THE WATER LEAK · WATER SUPPLY
§ 27-2026, 2027 HMC: PROPERLY REPAIR THE SOURCE AND ABATE THE EVIDENCE OF A WATER LEAK AT CEILING AT PUBLIC HALL, 2nd STORY
Class AOpen
Sep 30, 2026
TRACE & REPAIR THE SOURCE & ABATE THE…MOLD · CLEANING
§ 27-2017.3 HMC: TRACE AND REPAIR THE SOURCE AND ABATE THE VISIBLE MOLD CONDITION... LESS THAN 30 SQUARE FEET OBSERVED AT CEILING AT PUBLIC HALL, 2nd STORY
Class BOpenRENT IMPAIRING
Sep 30, 2026
LEAKY ROOF · MAINTENANCE
§ 27-2005 ADM CODE REPAIR THE ROOF SO THAT IT WILL NOT LEAK OVER CEILING AT PUBLIC HALL, 3rd STORY
Class BOpen
Sep 30, 2026
REPAIR WITH SIMILAR MATERIAL · MAINTENANCE
§ 27-2005 ADM CODE PROPERLY REPAIR WITH SIMILAR MATERIAL THE BROKEN OR DEFECTIVE FIRE RETARDANT MATERIAL AT CEILING AT PUBLIC HALL, 2nd STORY
Class COpenRENT IMPAIRING
Sep 30, 2026Apt D25
REMOVE ILLEGAL FASTENING · EGRESS
§ 27-2005, 2007 ADM CODE REMOVE THE ILLEGAL FASTENING CONSISTING OF SLIDING BOLT WITH EYE CAPABLE OF BEING PAD LOCKED AT DOOR IN THE ENTRANCE LOCATED AT APT D25, 3rd STORY, 13th APARTMENT FROM WEST AT NORTH
Class COpen
Sep 30, 2026
MAKE DOORS SELF-CLOSING · EGRESS
§ 27-2005, 27-2007, 27-2041.1 HMC, §238, § 309; § 107 (2) ( C) MDL AND 28 RCNY §25-171: REPLACE OR REPAIR THE SELF-CLOSING DOORS THAT IS MISSING OR DEFECTIVE HINGES AT LAUNDRY ROOM ENTRANCE DOOR AT BASEMENT
Class AOpen
Sep 30, 2026
PAINT · PAINTING
§ 27-2013 ADM CODE PAINT WITH LIGHT COLORED PAINT TO THE SATISFACTION OF THIS DEPARTMENT AT CEILING AT PUBLIC HALL, 2nd STORY
Class AOpen
Sep 30, 2026
PAINT · PAINTING
§ 27-2013 ADM CODE PAINT WITH LIGHT COLORED PAINT TO THE SATISFACTION OF THIS DEPARTMENT AT CEILING AT PUBLIC HALL, 3rd STORY
Class BOpen
Sep 30, 2026
REPAIR WITH SIMILAR MATERIAL · MAINTENANCE
§ 27-2005 ADM CODE PROPERLY REPAIR WITH SIMILAR MATERIAL THE BROKEN OR DEFECTIVE FIRE RETARDANT MATERIAL AT CEILING AT PUBLIC HALL, 3rd STORY
Class BOpen
Sep 30, 2026Apt B1
REPAIR · MAINTENANCE
§ 27-2005 HMC: PROPERLY REPAIR OR REPLACE THE BROKEN OR DEFECTIVE SLIDING DOOR AT NORTH WALL LEADING TO TERRACE IN THE 1st ROOM FROM NORTH LOCATED AT APT B1, 1st STORY, 1st APARTMENT FROM WEST AT NORTH
Class BOpen
Sep 29, 2026Apt B8
REPAIR PLASTER · MAINTENANCE
§ 27-2005 ADM CODE REPAIR THE BROKEN OR DEFECTIVE PLASTERED SURFACES AND PAINT IN A UNIFORM COLOR AT CEILING IN THE 3rd ROOM FROM NORTH LOCATED AT APT B8, 1st STORY, 7th APARTMENT FROM EAST AT SOUTH
Class BOpen
Sep 29, 2026Apt B8
SECURE LOOSE MATTER · MAINTENANCE
§ 27-2005 ADM CODE PROPERLY SECURE THE LOOSE ELECTRICAL OUTLET AT EAST AND WEST WALL IN THE 3rd ROOM FROM NORTH LOCATED AT APT B8, 1st STORY, 7th APARTMENT FROM EAST AT SOUTH
Class BOpen
Sep 29, 2026Apt B8
REPAIR · MAINTENANCE
§ 27-2005 HMC: PROPERLY REPAIR OR REPLACE THE BROKEN OR DEFECTIVE SLIDING DOOR FRAME AT SOUTH WALL LEADING TO TERRACE IN THE 3rd ROOM FROM NORTH LOCATED AT APT B8, 1st STORY, 7th APARTMENT FROM EAST AT SOUTH
Class BOpen
Sep 29, 2026Apt B8
REPAIR OR REPLACE CO DETECTOR · CARBON MONOXIDE DETECTING DEVICES
§ 27-2045(B)(1)(B) HMC, § 12-06, § 12-07, § 12-09 RCNY REPAIR, REPLACE OR PROVIDE AN APPROVED AND OPERATIONAL CARBON MONOXIDE DETECTING DEVICE, INSTALLED IN ACCORDANCE WITH APPLICABLE LAW AND RULES DEFECTIVE IN THE ENTIRE APARTMENT LOCATED AT APT B8, 1st STORY, 7th APARTMENT FROM EAST AT SOUTH
Class BOpen
Sep 29, 2026Apt B8
REPAIR PLASTER · MAINTENANCE
§ 27-2005 ADM CODE REPAIR THE BROKEN OR DEFECTIVE PLASTERED SURFACES AND PAINT IN A UNIFORM COLOR AT CEILING AND WEST WALL IN THE BATHROOM LOCATED AT APT B8, 1st STORY, 7th APARTMENT FROM EAST AT SOUTH
Class COpen
Sep 29, 2026Apt B8
ABATE THE NUISANCE OF ROACHES · EXTERMINATION & RODENT ERADICATION
HMC ADM CODE: § 27-2017.4 ABATE THE INFESTATION CONSISTING OF ROACHES IN THE ENTIRE APARTMENT LOCATED AT APT B8, 1st STORY, 7th APARTMENT FROM EAST AT SOUTH
Class BOpen
Sep 29, 2026Apt B8
REPAIR THE SOURCE AND ABATE THE WATER LEAK · WATER SUPPLY
§ 27-2026, 2027 HMC: PROPERLY REPAIR THE SOURCE AND ABATE THE EVIDENCE OF A WATER LEAK AT CEILING IN THE KITCHENETTE LOCATED AT APT B8, 1st STORY, 7th APARTMENT FROM EAST AT SOUTH
Class COpenRENT IMPAIRING
Sep 29, 2026Apt B2
INADEQUATE HOT WATER · HEAT AND HOT WATER
§ 27-2031 ADM CODE PROVIDE HOT WATER AT ALL HOT WATER FIXTURES IN THE ENTIRE APARTMENT LOCATED AT APT B2, 1st STORY, 10th APARTMENT FROM EAST AT SOUTH
Class BOpen
Sep 29, 2026Apt B5
REPAIR OR REPLACE SMOKE DETECTOR · SMOKE DETECTING DEVICES
§ 27-2045(B)(1)(A) HMC, § 12-01, § 12-03 RCNY REPAIR, REPLACE OR PROVIDE AN APPROVED AND OPERATIONAL SMOKE DETECTING DEVICE, INSTALLED IN ACCORDANCE WITH DEPARTMENT OF BUILDINGS RULES AND REGULATIONS MISSING IN THE ENTIRE APARTMENT LOCATED AT APT B5, 1st STORY, 3rd APARTMENT FROM EAST AT SOUTH
Class BOpen
Sep 29, 2026Apt B25
REPAIR PLASTER · MAINTENANCE
§ 27-2005 ADM CODE REPAIR THE BROKEN OR DEFECTIVE PLASTERED SURFACES AND PAINT IN A UNIFORM COLOR AT ALL WALLS AND CEILING IN THE BATHROOM LOCATED AT APT B25, 1st STORY, 11th APARTMENT FROM WEST AT NORTH
Class BOpen
Sep 29, 2026Apt B8
REPAIR · MAINTENANCE
§ 27-2005 HMC: PROPERLY REPAIR OR REPLACE THE BROKEN OR DEFECTIVE ELECTRICAL OUTLET AT WEST WALL IN THE BATHROOM LOCATED AT APT B8, 1st STORY, 7th APARTMENT FROM EAST AT SOUTH
Class BOpen
Sep 29, 2026Apt B25
TRACE & REPAIR THE SOURCE & ABATE THE…MOLD · CLEANING
§ 27-2017.3 HMC: TRACE AND REPAIR THE SOURCE AND ABATE THE VISIBLE MOLD CONDITION... MORE THAN 10 SQUARE FEET AND LESS THAN 30 SQUARE FEET AT ALL WALLS AND CEILING OBSERVED IN THE BATHROOM LOCATED AT APT B25, 1st STORY, 11th APARTMENT FROM WEST AT NORTH
Class BOpen
Sep 29, 2026Apt B8
REPAIR THE SOURCE AND ABATE THE WATER LEAK · WATER SUPPLY
§ 27-2026, 2027 HMC: PROPERLY REPAIR THE SOURCE AND ABATE THE EVIDENCE OF A WATER LEAK AT CEILING IN THE BATHROOM LOCATED AT APT B8, 1st STORY, 7th APARTMENT FROM EAST AT SOUTH
Class BOpen
Sep 29, 2026Apt B5
REPAIR WITH SIMILAR MATERIAL · MAINTENANCE
§ 27-2005 ADM CODE PROPERLY REPAIR WITH SIMILAR MATERIAL THE BROKEN OR DEFECTIVE METAL DOOR IN THE ENTRANCE LOCATED AT APT B5, 1st STORY, 3rd APARTMENT FROM EAST AT SOUTH
Class BOpen
Sep 29, 2026Apt B8
REPAIR THE SOURCE AND ABATE THE WATER LEAK · WATER SUPPLY
§ 27-2026, 2027 HMC: PROPERLY REPAIR THE SOURCE AND ABATE THE EVIDENCE OF A WATER LEAK AT CEILING IN THE 3rd ROOM FROM NORTH LOCATED AT APT B8, 1st STORY, 7th APARTMENT FROM EAST AT SOUTH
Class BOpen
Sep 29, 2026Apt B25
TRACE & REPAIR THE SOURCE & ABATE THE…MOLD · CLEANING
§ 27-2017.3 HMC: TRACE AND REPAIR THE SOURCE AND ABATE THE VISIBLE MOLD CONDITION... GREATER THAN 10 SQUARE FEET AND LESS THAN 30 SQUARE FEET OBSERVED AT NORTH WALL IN THE 1st ROOM FROM NORTH LOCATED AT APT B25, 1st STORY, 11th APARTMENT FROM WEST AT NORTH
Class BOpen
Sep 29, 2026Apt B25
REPAIR PLASTER · MAINTENANCE
§ 27-2005 ADM CODE REPAIR THE BROKEN OR DEFECTIVE PLASTERED SURFACES AND PAINT IN A UNIFORM COLOR AT NORTH WALL IN THE 1st ROOM FROM NORTH LOCATED AT APT B25, 1st STORY, 11th APARTMENT FROM WEST AT NORTH
Class BOpen
Sep 29, 2026Apt B5
REPAIR PLASTER · MAINTENANCE
§ 27-2005 ADM CODE REPAIR THE BROKEN OR DEFECTIVE PLASTERED SURFACES AND PAINT IN A UNIFORM COLOR AT CEILING IN THE BATHROOM LOCATED AT APT B5, 1st STORY, 3rd APARTMENT FROM EAST AT SOUTH
Class BOpen
Sep 29, 2026Apt B2
REPAIR · MAINTENANCE
§ 27-2005 HMC: PROPERLY REPAIR OR REPLACE THE BROKEN OR DEFECTIVE ELECTRICAL OUTLET AT EAST WALL IN THE KITCHEN LOCATED AT APT B2, 1st STORY, 10th APARTMENT FROM EAST AT SOUTH
Class BOpen
Sep 29, 2026Apt B25
REPAIR OR REPLACE SMOKE DETECTOR · SMOKE DETECTING DEVICES
§ 27-2045(B)(1)(A) HMC, § 12-01, § 12-03 RCNY REPAIR, REPLACE OR PROVIDE AN APPROVED AND OPERATIONAL SMOKE DETECTING DEVICE, INSTALLED IN ACCORDANCE WITH DEPARTMENT OF BUILDINGS RULES AND REGULATIONS DEFECTIVE IN THE ENTIRE APARTMENT LOCATED AT APT B25, 1st STORY, 11th APARTMENT FROM WEST AT NORTH
Class BOpen
Sep 29, 2026Apt B25
REPAIR THE SOURCE AND ABATE THE WATER LEAK · WATER SUPPLY
§ 27-2026, 2027 HMC: PROPERLY REPAIR THE SOURCE AND ABATE THE EVIDENCE OF A WATER LEAK AT NORTH WALL IN THE 1st ROOM FROM NORTH LOCATED AT APT B25, 1st STORY, 11th APARTMENT FROM WEST AT NORTH
Class BOpen
Sep 29, 2026Apt B5
PROVIDE SUPPLY OF ELECTRICTY TO FIXTURES · ARTIFICIAL LIGHTING
§ 27-2037, 2038 HMC: PROVIDE A SAFE AND ADEQUATE SUPPLY OF ELECTRIC SERVICE TO THE FIXTURES , ELECTRICAL BASEBOARD HEATER AT NORTH WALL IN THE 1st ROOM FROM NORTH LOCATED AT APT B5, 1st STORY, 3rd APARTMENT FROM EAST AT SOUTH
Class AOpen
Sep 29, 2026Apt B1
TRACE & REPAIR THE SOURCE & ABATE THE…MOLD · CLEANING
§ 27-2017.3 HMC: TRACE AND REPAIR THE SOURCE AND ABATE THE VISIBLE MOLD CONDITION... LESS THAN 10 SQUARE FEET OBSERVED AT NORTH, WEST AND EAST WALL IN THE BATHROOM LOCATED AT APT B1, 1st STORY, 1st APARTMENT FROM WEST AT NORTH
Class BOpen
Sep 29, 2026Apt B1
REPAIR THE SOURCE AND ABATE THE WATER LEAK · WATER SUPPLY
§ 27-2026, 2027 HMC: PROPERLY REPAIR THE SOURCE AND ABATE THE EVIDENCE OF A WATER LEAK AT CEILING IN THE KITCHENETTE LOCATED AT APT B1, 1st STORY, 1st APARTMENT FROM WEST AT NORTH
Class BOpen
Sep 29, 2026Apt B1
REPAIR PLASTER · MAINTENANCE
§ 27-2005 ADM CODE REPAIR THE BROKEN OR DEFECTIVE PLASTERED SURFACES AND PAINT IN A UNIFORM COLOR AT CEILING AND EAST WALL IN THE KITCHENETTE LOCATED AT APT B1, 1st STORY, 1st APARTMENT FROM WEST AT NORTH
Class AOpen
Sep 29, 2026Apt B1
REPAIR WITH SIMILAR MATERIAL · MAINTENANCE
§ 27-2005 ADM CODE PROPERLY REPAIR WITH SIMILAR MATERIAL THE BROKEN OR DEFECTIVE WOOD CLOSET DOOR AT WEST ALL IN THE FOYER LOCATED AT APT B1, 1st STORY, 1st APARTMENT FROM WEST AT NORTH
Class BOpen
Sep 29, 2026Apt B1
REPAIR WITH SIMILAR MATERIAL · MAINTENANCE
§ 27-2005 ADM CODE PROPERLY REPAIR WITH SIMILAR MATERIAL THE BROKEN OR DEFECTIVE VINYL FLOOR TILES IN THE 1st ROOM FROM NORTH LOCATED AT APT B1, 1st STORY, 1st APARTMENT FROM WEST AT NORTH
Class BOpen
Sep 29, 2026Apt B2
REPAIR THE SOURCE AND ABATE THE WATER LEAK · WATER SUPPLY
§ 27-2026, 2027 HMC: PROPERLY REPAIR THE SOURCE AND ABATE THE EVIDENCE OF A WATER LEAK AT CEILING IN THE BATHROOM LOCATED AT APT B2, 1st STORY, 10th APARTMENT FROM EAST AT SOUTH
Class BOpen
Sep 29, 2026Apt B2
REPAIR PLASTER · MAINTENANCE
§ 27-2005 ADM CODE REPAIR THE BROKEN OR DEFECTIVE PLASTERED SURFACES AND PAINT IN A UNIFORM COLOR AT CEILING IN THE BATHROOM LOCATED AT APT B2, 1st STORY, 10th APARTMENT FROM EAST AT SOUTH
Class AOpen
Sep 29, 2026Apt B2
RESET WATER CLOSET BOWL · SEWERS AND DRAINAGE
§ 27-2026 ADM CODE RESET, SO AS TO SECURE A PROPER AND TIGHT CONNECTION, THE WATER CLOSET BOWL IN THE BATHROOM LOCATED AT APT B2, 1st STORY, 10th APARTMENT FROM EAST AT SOUTH
Class BOpen
Sep 29, 2026Apt B2
REPAIR OR REPLACE CO DETECTOR · CARBON MONOXIDE DETECTING DEVICES
§ 27-2045(B)(1)(B) HMC, § 12-06, § 12-07, § 12-09 RCNY REPAIR, REPLACE OR PROVIDE AN APPROVED AND OPERATIONAL CARBON MONOXIDE DETECTING DEVICE, INSTALLED IN ACCORDANCE WITH APPLICABLE LAW AND RULES DEFECTIVE IN THE ENTIRE APARTMENT LOCATED AT APT B2, 1st STORY, 10th APARTMENT FROM EAST AT SOUTH
Class BOpen
Sep 29, 2026Apt B2
REPAIR OR REPLACE SMOKE DETECTOR · SMOKE DETECTING DEVICES
§ 27-2045(B)(1)(A) HMC, § 12-01, § 12-03 RCNY REPAIR, REPLACE OR PROVIDE AN APPROVED AND OPERATIONAL SMOKE DETECTING DEVICE, INSTALLED IN ACCORDANCE WITH DEPARTMENT OF BUILDINGS RULES AND REGULATIONS DEFECTIVE IN THE ENTIRE APARTMENT LOCATED AT APT B2, 1st STORY, 10th APARTMENT FROM EAST AT SOUTH
Class COpen
Sep 29, 2026Apt B2
ABATE THE NUISANCE OF ROACHES · EXTERMINATION & RODENT ERADICATION
HMC ADM CODE: § 27-2017.4 ABATE THE INFESTATION CONSISTING OF ROACHES IN THE ENTIRE APARTMENT LOCATED AT APT B2, 1st STORY, 10th APARTMENT FROM EAST AT SOUTH
Class COpen
Sep 29, 2026Apt B2
ABATE THE NUISANCE OF MICE · EXTERMINATION & RODENT ERADICATION
HMC ADM CODE: § 27-2017.4 ABATE THE INFESTATION CONSISTING OF MICE IN THE ENTIRE APARTMENT LOCATED AT APT B2, 1st STORY, 10th APARTMENT FROM EAST AT SOUTH
Class BOpen
Sep 29, 2026Apt B1
REPAIR PLASTER · MAINTENANCE
§ 27-2005 ADM CODE REPAIR THE BROKEN OR DEFECTIVE PLASTERED SURFACES AND PAINT IN A UNIFORM COLOR AT CEILING IN THE BATHROOM LOCATED AT APT B1, 1st STORY, 1st APARTMENT FROM WEST AT NORTH