Class CClosedRENT IMPAIRING
Aug 18, 2025
LEAKY ROOF · MAINTENANCE
§ 27-2005 ADM CODE REPAIR THE ROOF SO THAT IT WILL NOT LEAK AT CEILING AT PUBLIC HALL, 4th STORY
Class COpen
Aug 18, 2025Apt 3A
REPAIR THE SOURCE AND ABATE THE WATER LEAK · WATER SUPPLY
§ 27-2026, 2027 HMC: PROPERLY REPAIR THE SOURCE AND ABATE THE EVIDENCE OF A WATER LEAK AT CEILING IN THE KITCHEN LOCATED AT APT 3A, 3rd STORY, 1st APARTMENT FROM SOUTH AT WEST
Class CClosed
Aug 6, 2025Apt 4B
INSTALL/REPLACE/REPAIR WINDOW GUARDS (APT) · WINDOW GUARDS
§ 27-2043.1 HMC INSTALL THE MISSING OR REPAIR/REPLACE THE DEFECTIVE WINDOW GUARD(S) IN ACCORDANCE WITH THE SPECIFICATIONS OF THE NEW YORK CITY HEALTH CODE SECTION 24 RCNY CHAPTER 12. WG TO INSTALL = 3; WG TO REPLACE = 0; WG TO REPAIR = 0; IN THE ENTIRE APARTMENT LOCATED AT APT 4B, 4th STORY, 1st APARTMENT FROM WEST AT NORTH
Class CClosed
Aug 6, 2025Apt 4N
MAKE DOORS SELF-CLOSING · EGRESS
§ 27-2005, 27-2007, 27-2041.1 HMC, §238, § 309; § 107 (2) ( C) MDL AND 28 RCNY §25-171: REPLACE OR REPAIR THE SELF-CLOSING DOORS THAT IS MISSING OR DEFECTIVE HINGES IN THE ENTRANCE LOCATED AT APT 4N, 4th STORY, 1st APARTMENT FROM EAST AT SOUTH
Class COpen
Jul 24, 2025Apt 3L
REPAIR PLASTER · MAINTENANCE
§ 27-2005 ADM CODE REPAIR THE BROKEN OR DEFECTIVE PLASTERED SURFACES AND PAINT IN A UNIFORM COLOR AT CEILING AND SOUTH WALL IN THE 1st ROOM FROM NORTH LOCATED AT APT 3L, 3rd STORY, 1st APARTMENT FROM WEST AT NORTH
Class CClosed
Jul 7, 2025Apt 3E
LEAD-BASED PAINT HAZARD- POSITIVE · LEAD-BASED PAINT
§ 27-2056.6 ADM CODE - CORRECT THE LEAD-BASED PAINT HAZARD - PAINT THAT TESTED POSITIVE FOR LEAD CONTENT AND THAT IS PEELING OR ON A DETERIORATED SUBSURFACE - USING WORK PRACTICES SET FORTH IN 28 RCNY §11-06(B)(2) 1st DOOR FRAME FROM SOUTH AT WEST WALL IN THE 1st KITCHEN LOCATED AT APT 3E, 3rd STORY, 1st APARTMENT FROM EAST AT SOUTH
Class CClosed
Jul 7, 2025Apt 3E
LEAD-BASED PAINT HAZARD- POSITIVE · LEAD-BASED PAINT
§ 27-2056.6 ADM CODE - CORRECT THE LEAD-BASED PAINT HAZARD - PAINT THAT TESTED POSITIVE FOR LEAD CONTENT AND THAT IS PEELING OR ON A DETERIORATED SUBSURFACE - USING WORK PRACTICES SET FORTH IN 28 RCNY §11-06(B)(2) 1st DOOR FROM WEST AT NORTH WALL, 1st DOOR FRAME FROM WEST AT NORTH WALL IN THE 4th ROOM FROM NORTH LOCATED AT APT 3E, 3rd STORY, 1st APARTMENT FROM EAST AT SOUTH
Class CClosed
Jul 7, 2025Apt 3E
LEAD-BASED PAINT HAZARD- POSITIVE · LEAD-BASED PAINT
§ 27-2056.6 ADM CODE - CORRECT THE LEAD-BASED PAINT HAZARD - PAINT THAT TESTED POSITIVE FOR LEAD CONTENT AND THAT IS PEELING OR ON A DETERIORATED SUBSURFACE - USING WORK PRACTICES SET FORTH IN 28 RCNY §11-06(B)(2) 1st DOOR FRAME FROM SOUTH AT WEST WALL IN THE 1st BATHROOM LOCATED AT APT 3E, 3rd STORY, 1st APARTMENT FROM EAST AT SOUTH
Class CClosed
Jul 7, 2025Apt 3E
LEAD-BASED PAINT HAZARD- POSITIVE · LEAD-BASED PAINT
§ 27-2056.6 ADM CODE - CORRECT THE LEAD-BASED PAINT HAZARD - PAINT THAT TESTED POSITIVE FOR LEAD CONTENT AND THAT IS PEELING OR ON A DETERIORATED SUBSURFACE - USING WORK PRACTICES SET FORTH IN 28 RCNY §11-06(B)(2) 1st DOOR FROM WEST AT NORTH WALL, 1st DOOR FRAME FROM WEST AT NORTH WALL IN THE FOYER LOCATED AT APT 3E, 3rd STORY, 1st APARTMENT FROM EAST AT SOUTH
Class CClosed
Jul 7, 2025Apt 3E
LEAD-BASED PAINT HAZARD- POSITIVE · LEAD-BASED PAINT
§ 27-2056.6 ADM CODE - CORRECT THE LEAD-BASED PAINT HAZARD - PAINT THAT TESTED POSITIVE FOR LEAD CONTENT AND THAT IS PEELING OR ON A DETERIORATED SUBSURFACE - USING WORK PRACTICES SET FORTH IN 28 RCNY §11-06(B)(2) 1st WINDOW FRAME FROM NORTH AT EAST WALL IN THE 2nd ROOM FROM NORTH LOCATED AT APT 3E, 3rd STORY, 1st APARTMENT FROM EAST AT SOUTH
Class COpen
Jul 7, 2025Apt 3E
LEAD-BASED PAINT HAZARD - DURING UNIT VACANCY · LEAD-BASED PAINT
§ 27-2056.7, 27-2056.8, 27-2056.9 ADM CODE -CERTIFY COMPLIANCE WITH LEAD-BASED PAINT HAZARD CONTROL REQUIREMENTS DURING PERIOD OF UNIT VACANCY BY PERFORMING ACTIVITIES NECESSARY TO ABATE TESTED LEAD-BASED PAINT FROM REQUIRED WINDOW AND/OR DOOR FRICTION SURFACES FOR APARTMENT AND MAKE FLOORS SMOOTH AND CLEANABLE, POSITIVE LEAD-BASED PAINT IN AN APARTMENT WITH A CHILD UNDER SIX LOCATED AT APT 3E, 3rd STORY, 1st APARTMENT FROM EAST AT SOUTH
Class CClosed
Jul 2, 2025Apt 3E
INSTALL/REPLACE/REPAIR WINDOW GUARDS (APT) · WINDOW GUARDS
§ 27-2043.1 HMC INSTALL THE MISSING OR REPAIR/REPLACE THE DEFECTIVE WINDOW GUARD(S) IN ACCORDANCE WITH THE SPECIFICATIONS OF THE NEW YORK CITY HEALTH CODE SECTION 24 RCNY CHAPTER 12. WG TO INSTALL = 4; WG TO REPLACE = 0; WG TO REPAIR = 0; IN THE ENTIRE APARTMENT LOCATED AT APT 3E, 3rd STORY, 1st APARTMENT FROM SOUTH AT WEST
Class CClosed
Jul 2, 2025Apt 2F
INSTALL/REPLACE/REPAIR WINDOW GUARDS (APT) · WINDOW GUARDS
§ 27-2043.1 HMC INSTALL THE MISSING OR REPAIR/REPLACE THE DEFECTIVE WINDOW GUARD(S) IN ACCORDANCE WITH THE SPECIFICATIONS OF THE NEW YORK CITY HEALTH CODE SECTION 24 RCNY CHAPTER 12. WG TO INSTALL = 1; WG TO REPLACE = 0; WG TO REPAIR = 0; IN THE ENTIRE APARTMENT LOCATED AT APT 2F, 2nd STORY, 1st APARTMENT FROM EAST AT SOUTH
Class COpen
Jul 2, 2025Apt 2F
ABATE THE NUISANCE · MAINTENANCE
§ 27-2005 ADM CODE & 309 M/D LAW ABATE THE NUISANCE CONSISTING OF WINDOW GUARD NSTALLED AT FIRE ESCAPE WINDOW IN THE 1st ROOM FROM EAST AT SOUTH LOCATED AT APT 2F, 2nd STORY, 1st APARTMENT FROM EAST AT SOUTH
Class CClosed
Jul 2, 2025Apt 3E
ABATE THE NUISANCE · MAINTENANCE
§ 27-2005 ADM CODE & 309 M/D LAW ABATE THE NUISANCE CONSISTING OF AIR CONDITION AT FIRE ESCAPE WINDOW IN THE 1st ROOM FROM NORTH LOCATED AT APT 3E, 3rd STORY, 1st APARTMENT FROM SOUTH AT WEST
Class COpen
Jul 1, 2025Apt 3A
MAKE DOORS SELF-CLOSING · EGRESS
§ 27-2005, 27-2007, 27-2041.1 HMC, §238, § 309; § 107 (2) ( C) MDL AND 28 RCNY §25-171: REPLACE OR REPAIR THE SELF-CLOSING DOORS THAT IS MISSING OR DEFECTIVE HINGES IN THE ENTRANCE LOCATED AT APT 3A, 3rd STORY, 2nd APARTMENT FROM WEST AT NORTH
Class COpen
Jul 1, 2025Apt 2C
REPAIR THE SOURCE AND ABATE THE WATER LEAK · WATER SUPPLY
§ 27-2026, 2027 HMC: PROPERLY REPAIR THE SOURCE AND ABATE THE EVIDENCE OF A WATER LEAK ACTIVE WATER LEAK AT CEILING IN THE BATHROOM LOCATED AT APT 2C, 2nd STORY, 1st APARTMENT FROM SOUTH AT WEST
Class COpen
Jun 30, 2025
MAKE DOORS SELF-CLOSING · EGRESS
§ 27-2005, 27-2007, 27-2041.1 HMC, §238, § 309; § 107 (2) ( C) MDL AND 28 RCNY §25-171: REPLACE OR REPAIR THE SELF-CLOSING DOORS THAT IS MISSING OR DEFECTIVE LATCH AT VESTIBULE DOOR
Class CClosed
Jun 30, 2025Apt 1H
REPAIR · MAINTENANCE
§ 27-2005 HMC: PROPERLY REPAIR OR REPLACE THE BROKEN OR DEFECTIVE WINDOW COUNTER BALANCE AT LOWER SASH AT EAST IN THE BATHROOM LOCATED AT APT 1H, 1st STORY, 2nd APARTMENT FROM NORTH AT EAST , SECTION AT EAST
Class CClosed
Jun 30, 2025Apt 3E
MAKE DOORS SELF-CLOSING · EGRESS
§ 27-2005, 27-2007, 27-2041.1 HMC, §238, § 309; § 107 (2) ( C) MDL AND 28 RCNY §25-171: REPLACE OR REPAIR THE SELF-CLOSING DOORS THAT IS MISSING OR DEFECTIVE HINGES IN THE ENTRANCE LOCATED AT APT 3E, 3rd STORY, 1st APARTMENT FROM SOUTH AT WEST , SECTION AT WEST
Class CClosed
Jun 30, 2025Apt 3E
INSTALL/REPLACE/REPAIR WINDOW GUARDS (APT) · WINDOW GUARDS
§ 27-2043.1 HMC INSTALL THE MISSING OR REPAIR/REPLACE THE DEFECTIVE WINDOW GUARD(S) IN ACCORDANCE WITH THE SPECIFICATIONS OF THE NEW YORK CITY HEALTH CODE SECTION 24 RCNY CHAPTER 12. WG TO INSTALL = 4; WG TO REPLACE = 0; WG TO REPAIR = 0; IN THE ENTIRE APARTMENT LOCATED AT APT 3E, 3rd STORY, 1st APARTMENT FROM SOUTH AT WEST , SECTION AT WEST
Class COpen
Jun 27, 2025Apt 3A
TRACE & REPAIR THE SOURCE & ABATE THE…MOLD · CLEANING
§ 27-2017.3 HMC: TRACE AND REPAIR THE SOURCE AND ABATE THE VISIBLE MOLD CONDITION... AT CEILING , WEST AND NORTH WALLS EQUAL TO 30 SQ. FEET IN THE BATHROOM LOCATED AT APT 3A, 3rd STORY, 2nd APARTMENT FROM WEST AT NORTH
Class CClosed
Jun 27, 2025Apt 3A
REPAIR · MAINTENANCE
§ 27-2005 HMC: PROPERLY REPAIR OR REPLACE THE BROKEN OR DEFECTIVE SPRING BALANCE AT LOWER SASH AT WINDOW IN THE 1st ROOM FROM NORTH LOCATED AT APT 3A, 3rd STORY, 2nd APARTMENT FROM WEST AT NORTH
Class CClosed
Jun 27, 2025Apt 3A
REPAIR · MAINTENANCE
§ 27-2005 HMC: PROPERLY REPAIR OR REPLACE THE BROKEN OR DEFECTIVE SPRING BALANCE AT LOWER SASH AT WINDOW IN THE BATHROOM LOCATED AT APT 3A, 3rd STORY, 2nd APARTMENT FROM WEST AT NORTH
Class COpen
Jun 27, 2025Apt 3A
REPAIR WITH SIMILAR MATERIAL · MAINTENANCE
§ 27-2005 ADM CODE PROPERLY REPAIR WITH SIMILAR MATERIAL THE BROKEN OR DEFECTIVE CERAMIC FLOOR TILES IN THE BATHROOM LOCATED AT APT 3A, 3rd STORY, 2nd APARTMENT FROM WEST AT NORTH
Class COpen
Jun 9, 2025Apt 2A
ABATE THE NUISANCE · MAINTENANCE
§ 27-2005 ADM CODE & 309 M/D LAW ABATE THE NUISANCE CONSISTING OF HOT WATER IN EXCESS OF 30 DEGREES FAHREINHEIT IN THE ENTIRE APARTMENT LOCATED AT APT 2A, 2nd STORY, 1st APARTMENT FROM WEST AT NORTH
Class COpen
May 16, 2025Apt 4L
PROVIDE SUPPLY OF ELECTRICTY TO FIXTURES · ARTIFICIAL LIGHTING
§ 27-2037, 2038 HMC: PROVIDE A SAFE AND ADEQUATE SUPPLY OF ELECTRIC SERVICE TO THE FIXTURES AT THE CEILING IN THE CLOSET IN THE FOYER LOCATED AT APT 4L, 4th STORY, 1st APARTMENT FROM WEST AT NORTH
Class COpen
May 16, 2025Apt 4L
REPAIR · MAINTENANCE
§ 27-2005 HMC: PROPERLY REPAIR OR REPLACE THE BROKEN OR DEFECTIVE LOCK AT THE WINDOW IN THE 3rd ROOM FROM EAST AT NORTH LOCATED AT APT 4L, 4th STORY, 1st APARTMENT FROM WEST AT NORTH
Class CClosed
May 14, 2025Apt 1F
REPAIR PLASTER · MAINTENANCE
§ 27-2005 ADM CODE REPAIR THE BROKEN OR DEFECTIVE PLASTERED SURFACES AND PAINT IN A UNIFORM COLOR AT CEILING IN THE BATHROOM LOCATED AT APT 1F, 1st STORY, 1st APARTMENT FROM EAST AT SOUTH , SECTION AT EAST
Class CClosed
May 12, 2025Apt 4F
LEAD-BASED PAINT HAZARD- POSITIVE · LEAD-BASED PAINT
§ 27-2056.6 ADM CODE - CORRECT THE LEAD-BASED PAINT HAZARD - PAINT THAT TESTED POSITIVE FOR LEAD CONTENT AND THAT IS PEELING OR ON A DETERIORATED SUBSURFACE - USING WORK PRACTICES SET FORTH IN 28 RCNY §11-06(B)(2) 1st WINDOW FRAME FROM SOUTH AT WEST WALL IN THE 4th ROOM FROM NORTH LOCATED AT APT 4F, 4th STORY, 1st APARTMENT FROM EAST AT SOUTH
Class CClosed
May 12, 2025Apt 4F
LEAD-BASED PAINT HAZARD- POSITIVE · LEAD-BASED PAINT
§ 27-2056.6 ADM CODE - CORRECT THE LEAD-BASED PAINT HAZARD - PAINT THAT TESTED POSITIVE FOR LEAD CONTENT AND THAT IS PEELING OR ON A DETERIORATED SUBSURFACE - USING WORK PRACTICES SET FORTH IN 28 RCNY §11-06(B)(2) NORTH WALL, SOUTH WALL, EAST WALL, WEST WALL, 1st WINDOW FRAME FROM SOUTH AT WEST WALL IN THE 2nd ROOM FROM NORTH LOCATED AT APT 4F, 4th STORY, 1st APARTMENT FROM EAST AT SOUTH
Class CClosed
May 12, 2025Apt 4F
INSTALL/REPLACE/REPAIR WINDOW GUARDS (APT) · WINDOW GUARDS
§ 27-2043.1 HMC INSTALL THE MISSING OR REPAIR/REPLACE THE DEFECTIVE WINDOW GUARD(S) IN ACCORDANCE WITH THE SPECIFICATIONS OF THE NEW YORK CITY HEALTH CODE SECTION 24 RCNY CHAPTER 12. WG TO INSTALL = 1, WG TO REPLACE = 0, WG TO REPAIR = 0 IN THE ENTIRE APARTMENT LOCATED AT APT 4F, 4th STORY, 1st APARTMENT FROM EAST AT SOUTH
Class CClosed
May 12, 2025Apt 4F
MAKE DOORS SELF-CLOSING · EGRESS
§ 27-2005, 27-2007, 27-2041.1 HMC, §238, § 309; § 107 (2) ( C) MDL AND 28 RCNY §25-171: REPLACE OR REPAIR THE SELF-CLOSING DOORS THAT IS MISSING OR DEFECTIVE DOOR HINGES IN THE ENTRANCE LOCATED AT APT 4F, 4th STORY, 1st APARTMENT FROM EAST AT SOUTH
Class CClosed
May 12, 2025Apt 4F
TRACE & REPAIR THE SOURCE & ABATE THE…MOLD · CLEANING
§ 27-2017.3 HMC: TRACE AND REPAIR THE SOURCE AND ABATE THE VISIBLE MOLD CONDITION... GREATER THAN 30 SQ.FT AT CEILING IN THE BATHROOM LOCATED AT APT 4F, 4th STORY, 1st APARTMENT FROM EAST AT SOUTH
Class COpen
Apr 16, 2025
REPAIR THE SOURCE AND ABATE THE WATER LEAK · WATER SUPPLY
§ 27-2026, 2027 HMC: PROPERLY REPAIR THE SOURCE AND ABATE THE EVIDENCE OF A WATER LEAK OVER CEILING AT VESTIBULE AT PUBLIC HALL, 1st STORY
Class CClosed
Apr 14, 2025
MAKE DOORS SELF-CLOSING · EGRESS
§ 27-2005, 27-2007, 27-2041.1 HMC, §238, § 309; § 107 (2) ( C) MDL AND 28 RCNY §25-171: REPLACE OR REPAIR THE SELF-CLOSING DOORS THAT IS MISSING OR DEFECTIVE LATCH SET AT BUILDING ENTRANCE DOOR AT PUBLIC HALL, 1st STORY
Class COpen
Mar 24, 2025
PROVIDE SUPPLY OF ELECTRICTY TO FIXTURES · ARTIFICIAL LIGHTING
§ 27-2037, 2038 HMC: PROVIDE A SAFE AND ADEQUATE SUPPLY OF ELECTRIC SERVICE TO THE FIXTURES AT CEILING LIGHT FIXTURES AT BASEMENT
Class COpen
Mar 24, 2025Apt 4L
REPAIR · MAINTENANCE
§ 27-2005 HMC: PROPERLY REPAIR OR REPLACE THE BROKEN OR DEFECTIVE COUNTER BALANCE AT LOWER SASH IN THE 1st ROOM FROM EAST AT NORTH LOCATED AT APT 4L, 4th STORY, 1st APARTMENT FROM NORTH AT EAST , SECTION AT EAST
Class CClosedRENT IMPAIRING
Mar 24, 2025
LEAKY ROOF · MAINTENANCE
§ 27-2005 ADM CODE REPAIR THE ROOF SO THAT IT WILL NOT LEAK OVER CEILING AT PUBLIC HALL
Class COpen
Mar 24, 2025
REPAIR/ABATE UNSAFE WIRES · ARTIFICIAL LIGHTING
§ 27-2005, 2006, 2037 HMC: PROPERLY REPAIR AND ABATE UNSAFE ELECTRIC WIRING CONDITION CONSISTING OF EXPOSED ELECTRICAL WIRE AT CEILING AND WALLS AT BASEMENT
Class COpen
Mar 24, 2025
POST BOILER ROOM ACCESS NOTICE · HEAT AND HOT WATER
§ 27-2033 ADM CODE POST NOTICE, IN FORM APPROVED BY THE DEPARTMENT, STATING THE NAME AND LOCATION OF THE PERSON DESIGNATED BY THE OWNER TO HAVE KEY TO BUILDINGS HEATING SYSTEM SIGN MISSING
Class CClosed
Mar 24, 2025
ABATE THE NUISANCE · MAINTENANCE
§ 27-2005 ADM CODE & 309 M/D LAW ABATE THE NUISANCE CONSISTING OF REFRIGERATOR WITH DOOR INTACT AT PUBLIC HALL, 4th STORY
Class CClosed
Mar 24, 2025
REPAIR WITH SIMILAR MATERIAL · MAINTENANCE
§ 27-2005 ADM CODE PROPERLY REPAIR WITH SIMILAR MATERIAL THE BROKEN OR DEFECTIVE FIRE RETARDANT MATERIAL AT CEILING AT BASEMENT
Class CClosed
Mar 24, 2025Apt 1G
REPAIR THE SOURCE AND ABATE THE WATER LEAK · WATER SUPPLY
§ 27-2026, 2027 HMC: PROPERLY REPAIR THE SOURCE AND ABATE THE EVIDENCE OF A WATER LEAK AT CEILING IN THE 3rd ROOM FROM EAST LOCATED AT APT 1G, 1st STORY, 1st APARTMENT FROM EAST AT SOUTH
Class CClosed
Mar 24, 2025Apt 1G
REPAIR PLASTER · MAINTENANCE
§ 27-2005 ADM CODE REPAIR THE BROKEN OR DEFECTIVE PLASTERED SURFACES AND PAINT IN A UNIFORM COLOR AT CEILING IN THE 3rd ROOM FROM EAST LOCATED AT APT 1G, 1st STORY, 1st APARTMENT FROM EAST AT SOUTH
Class COpen
Mar 24, 2025Apt 3K
REPAIR WITH SIMILAR MATERIAL · MAINTENANCE
§ 27-2005 ADM CODE PROPERLY REPAIR WITH SIMILAR MATERIAL THE BROKEN OR DEFECTIVE CERAMIC TILES AT EAST WALL IN THE BATHROOM LOCATED AT APT 3K, 3rd STORY, 1st APARTMENT FROM SOUTH AT WEST , SECTION AT WEST
Class COpen
Mar 24, 2025Apt 3K
MAKE DOORS SELF-CLOSING · EGRESS
§ 27-2005, 27-2007, 27-2041.1 HMC, §238, § 309; § 107 (2) ( C) MDL AND 28 RCNY §25-171: REPLACE OR REPAIR THE SELF-CLOSING DOORS THAT IS MISSING OR DEFECTIVE DOOR HINGES IN THE ENTRANCE LOCATED AT APT 3K, 3rd STORY, 1st APARTMENT FROM SOUTH AT WEST , SECTION AT WEST
Class CClosed
Mar 24, 2025
REPAIR WITH SIMILAR MATERIAL · MAINTENANCE
§ 27-2005 ADM CODE PROPERLY REPAIR WITH SIMILAR MATERIAL THE BROKEN OR DEFECTIVE UNKEYED FIRE RETARNT MATERIAL AT BULKHEAD TO ROOF AT PUBLIC HALL
Class CClosed
Mar 18, 2025Apt 4B
REPAIR · MAINTENANCE
§ 27-2005 HMC: PROPERLY REPAIR OR REPLACE THE BROKEN OR DEFECTIVE GLASS PANE AT LOWER WINDOW SASH IN THE 1st ROOM FROM NORTH AT WEST LOCATED AT APT 4B, 4th STORY, 1st APARTMENT FROM WEST AT NORTH
Class CClosed
Mar 18, 2025Apt 4B
REPAIR · MAINTENANCE
§ 27-2005 HMC: PROPERLY REPAIR OR REPLACE THE BROKEN OR DEFECTIVE FIRE RATED DOOR IN THE ENTRANCE LOCATED AT APT 4B, 4th STORY, 1st APARTMENT FROM WEST AT NORTH