Class BOpen
Oct 1, 2026Apt 4C
REPAIR THE SOURCE AND ABATE THE WATER LEAK · WATER SUPPLY
§ 27-2026, 2027 HMC: PROPERLY REPAIR THE SOURCE AND ABATE THE EVIDENCE OF A WATER LEAK AT NORTH WALL BELOW TERRACE DOORS IN THE 1st ROOM FROM NORTH AT EAST LOCATED AT APT 4C, 4th STORY, 1st APARTMENT FROM WEST AT NORTH
Class COpen
Oct 1, 2026
REPAIR · MAINTENANCE
§ 27-2005 HMC: PROPERLY REPAIR OR REPLACE THE BROKEN OR DEFECTIVE GLASS PANE AT DOOR TO PUBLIC STAIRS, STAIRWAY ''A'', 1ST STAIRWAY FROM NORTH. AT PUBLIC HALL, 4th STORY
Class BOpen
Sep 29, 2026Apt 3D
REPAIR THE SOURCE AND ABATE THE WATER LEAK · WATER SUPPLY
§ 27-2026, 2027 HMC: PROPERLY REPAIR THE SOURCE AND ABATE THE EVIDENCE OF A WATER LEAK AT CEILING IN THE BATHROOM LOCATED AT APT 3D, 3rd STORY, 1st APARTMENT FROM SOUTH AT WEST , SECTION AT NORTH
Class AOpen
Sep 29, 2026Apt 1A
TRACE & REPAIR THE SOURCE & ABATE THE…MOLD · CLEANING
§ 27-2017.3 HMC: TRACE AND REPAIR THE SOURCE AND ABATE THE VISIBLE MOLD CONDITION... LESS THAN 10SQ.FT AT NORTH AND EAST WALLS IN THE 3rd ROOM FROM NORTH LOCATED AT APT 1A, 1st STORY, 1st APARTMENT FROM WEST AT NORTH
Class COpen
Sep 29, 2026Apt 1A
REPAIR WITH SIMILAR MATERIAL · MAINTENANCE
§ 27-2005 ADM CODE PROPERLY REPAIR WITH SIMILAR MATERIAL THE BROKEN OR DEFECTIVE UNEVEN WOOD FLOOR IN THE 3rd ROOM FROM NORTH LOCATED AT APT 1A, 1st STORY, 1st APARTMENT FROM WEST AT NORTH
Class BOpen
Sep 29, 2026Apt 3D
REPAIR OR REPLACE SMOKE DETECTOR · SMOKE DETECTING DEVICES
§ 27-2045(B)(1)(A) HMC, § 12-01, § 12-03 RCNY REPAIR, REPLACE OR PROVIDE AN APPROVED AND OPERATIONAL SMOKE DETECTING DEVICE, INSTALLED IN ACCORDANCE WITH DEPARTMENT OF BUILDINGS RULES AND REGULATIONS DEFECTIVE IN THE ENTIRE APARTMENT LOCATED AT APT 3D, 3rd STORY, 1st APARTMENT FROM SOUTH AT WEST , SECTION AT NORTH
Class BOpen
Sep 29, 2026Apt 4E
REPAIR OR REPLACE CO DETECTOR · CARBON MONOXIDE DETECTING DEVICES
§ 27-2045(B)(1)(B) HMC, § 12-06, § 12-07, § 12-09 RCNY REPAIR, REPLACE OR PROVIDE AN APPROVED AND OPERATIONAL CARBON MONOXIDE DETECTING DEVICE, INSTALLED IN ACCORDANCE WITH APPLICABLE LAW AND RULES DEFECTIVE IN THE ENTIRE APARTMENT LOCATED AT APT 4E, 4th STORY, 5th APARTMENT FROM SOUTH AT WEST
Class BOpen
Sep 29, 2026Apt 4E
REPAIR · MAINTENANCE
§ 27-2005 HMC: PROPERLY REPAIR OR REPLACE THE BROKEN OR DEFECTIVE LIGHT FIXTURE AT CEILING IN THE 3rd ROOM FROM NORTH LOCATED AT APT 4E, 4th STORY, 5th APARTMENT FROM SOUTH AT WEST
Class BOpen
Sep 29, 2026Apt 4E
REPAIR · MAINTENANCE
§ 27-2005 HMC: PROPERLY REPAIR OR REPLACE THE BROKEN OR DEFECTIVE LIGHT FIXTURE AT CEILING IN THE KITCHEN LOCATED AT APT 4E, 4th STORY, 5th APARTMENT FROM SOUTH AT WEST
Class COpenRENT IMPAIRING
Sep 29, 2026Apt 308
REMOVE OBSTUCTION FROM WATER CLOSET · SEWERS AND DRAINAGE
§ 27-2026 ADM CODE REMOVE ALL OBSTRUCTIONS FROM WATER CLOSET .. IN THE BATHROOM LOCATED AT APT 308, 3rd STORY, 5th APARTMENT FROM WEST AT NORTH
Class BOpen
Sep 29, 2026Apt 4E
REPAIR PLASTER · MAINTENANCE
§ 27-2005 ADM CODE REPAIR THE BROKEN OR DEFECTIVE PLASTERED SURFACES AND PAINT IN A UNIFORM COLOR AT WEST AND SOUTH WALL IN THE BATHROOM LOCATED AT APT 4E, 4th STORY, 5th APARTMENT FROM SOUTH AT WEST
Class BOpen
Sep 29, 2026Apt 4E
PROVIDE SUPPLY OF ELECTRICTY TO FIXTURES · ARTIFICIAL LIGHTING
§ 27-2037, 2038 HMC: PROVIDE A SAFE AND ADEQUATE SUPPLY OF ELECTRIC SERVICE TO THE FIXTURES ELECTRICAL OUTLET AT WEST WALL IN THE 2nd ROOM FROM NORTH LOCATED AT APT 4E, 4th STORY, 5th APARTMENT FROM SOUTH AT WEST
Class BOpen
Sep 29, 2026Apt 3D
REPAIR PLASTER · MAINTENANCE
§ 27-2005 ADM CODE REPAIR THE BROKEN OR DEFECTIVE PLASTERED SURFACES AND PAINT IN A UNIFORM COLOR THE CEILING IN THE BATHROOM LOCATED AT APT 3D, 3rd STORY, 1st APARTMENT FROM SOUTH AT WEST , SECTION AT NORTH
Class BOpen
Sep 29, 2026Apt 3D
REPAIR OR REPLACE CO DETECTOR · CARBON MONOXIDE DETECTING DEVICES
§ 27-2045(B)(1)(B) HMC, § 12-06, § 12-07, § 12-09 RCNY REPAIR, REPLACE OR PROVIDE AN APPROVED AND OPERATIONAL CARBON MONOXIDE DETECTING DEVICE, INSTALLED IN ACCORDANCE WITH APPLICABLE LAW AND RULES DEFECTIVE IN THE ENTIRE APARTMENT LOCATED AT APT 3D, 3rd STORY, 1st APARTMENT FROM SOUTH AT WEST , SECTION AT NORTH
Class BOpen
Sep 29, 2026Apt 4E
REPAIR OR REPLACE SMOKE DETECTOR · SMOKE DETECTING DEVICES
§ 27-2045(B)(1)(A) HMC, § 12-01, § 12-03 RCNY REPAIR, REPLACE OR PROVIDE AN APPROVED AND OPERATIONAL SMOKE DETECTING DEVICE, INSTALLED IN ACCORDANCE WITH DEPARTMENT OF BUILDINGS RULES AND REGULATIONS DEFECTIVE IN THE ENTIRE APARTMENT LOCATED AT APT 4E, 4th STORY, 5th APARTMENT FROM SOUTH AT WEST
Class BOpen
Sep 29, 2026Apt 701C
REPAIR · MAINTENANCE
§ 27-2005 HMC: PROPERLY REPAIR OR REPLACE THE BROKEN OR DEFECTIVE ELECTRIC FUSE BOX AT NORTH WALL IN THE PRIVATE HALLWAY LOCATED AT APT 701C, 7th STORY, 11th APARTMENT FROM SOUTH AT WEST
Class BOpen
Sep 29, 2026Apt 4E
REPAIR · MAINTENANCE
§ 27-2005 HMC: PROPERLY REPAIR OR REPLACE THE BROKEN OR DEFECTIVE MECHANICAL VENTILATION SYSTEM AT CEILING IN THE KITCHEN LOCATED AT APT 4E, 4th STORY, 5th APARTMENT FROM SOUTH AT WEST
Class BOpen
Sep 29, 2026Apt 701C
REPAIR OR REPLACE CO DETECTOR · CARBON MONOXIDE DETECTING DEVICES
§ 27-2045(B)(1)(B) HMC, § 12-06, § 12-07, § 12-09 RCNY REPAIR, REPLACE OR PROVIDE AN APPROVED AND OPERATIONAL CARBON MONOXIDE DETECTING DEVICE, INSTALLED IN ACCORDANCE WITH APPLICABLE LAW AND RULES DEFECTIVE IN THE ENTIRE APARTMENT LOCATED AT APT 701C, 7th STORY, 11th APARTMENT FROM SOUTH AT WEST
Class BOpen
Sep 29, 2026Apt 4E
REPAIR · MAINTENANCE
§ 27-2005 HMC: PROPERLY REPAIR OR REPLACE THE BROKEN OR DEFECTIVE LIGHT FIXTURE AT CEILING IN THE 2nd ROOM FROM NORTH LOCATED AT APT 4E, 4th STORY, 5th APARTMENT FROM SOUTH AT WEST
Class BOpen
Sep 29, 2026Apt 3D
REPAIR WITH SIMILAR MATERIAL · MAINTENANCE
§ 27-2005 ADM CODE PROPERLY REPAIR WITH SIMILAR MATERIAL THE BROKEN OR DEFECTIVE CAULKING AROUND BATHTUB IN THE BATHROOM LOCATED AT APT 3D, 3rd STORY, 1st APARTMENT FROM SOUTH AT WEST , SECTION AT NORTH
Class COpen
Sep 29, 2026Apt 1A
REPAIR WITH SIMILAR MATERIAL · MAINTENANCE
§ 27-2005 ADM CODE PROPERLY REPAIR WITH SIMILAR MATERIAL THE BROKEN OR DEFECTIVE UNEVEN WOOD FLOOR IN THE ENTRANCE LOCATED AT APT 1A, 1st STORY, 1st APARTMENT FROM WEST AT NORTH
Class BOpen
Sep 29, 2026Apt 818
REPAIR OR REPLACE SMOKE DETECTOR · SMOKE DETECTING DEVICES
§ 27-2045(B)(1)(A) HMC, § 12-01, § 12-03 RCNY REPAIR, REPLACE OR PROVIDE AN APPROVED AND OPERATIONAL SMOKE DETECTING DEVICE, INSTALLED IN ACCORDANCE WITH DEPARTMENT OF BUILDINGS RULES AND REGULATIONS DEFECTIVE IN THE ENTIRE APARTMENT LOCATED AT APT 818, 8th STORY, 2nd APARTMENT FROM NORTH AT EAST
Class COpen
Sep 29, 2026Apt 3D
ABATE THE NUISANCE OF ROACHES · EXTERMINATION & RODENT ERADICATION
HMC ADM CODE: § 27-2017.4 ABATE THE INFESTATION CONSISTING OF ROACHES IN THE ENTIRE APARTMENT LOCATED AT APT 3D, 3rd STORY, 1st APARTMENT FROM SOUTH AT WEST , SECTION AT NORTH
Class BOpen
Sep 29, 2026Apt 1A
TRACE & REPAIR THE SOURCE & ABATE THE…MOLD · CLEANING
§ 27-2017.3 HMC: TRACE AND REPAIR THE SOURCE AND ABATE THE VISIBLE MOLD CONDITION... MORE THAN 10 SQ.FT BUT LESS THAN 30 SQ.FT OBSERVED AT ALL WALLS IN THE 1st ROOM FROM NORTH LOCATED AT APT 1A, 1st STORY, 1st APARTMENT FROM WEST AT NORTH
Class BOpen
Sep 29, 2026Apt 3D
REPAIR WITH SIMILAR MATERIAL · MAINTENANCE
§ 27-2005 ADM CODE PROPERLY REPAIR WITH SIMILAR MATERIAL THE BROKEN OR DEFECTIVE WOOD FLOOR TILE IN THE KITCHEN LOCATED AT APT 3D, 3rd STORY, 1st APARTMENT FROM SOUTH AT WEST , SECTION AT NORTH
Class COpen
Sep 29, 2026Apt 1A
REPAIR WITH SIMILAR MATERIAL · MAINTENANCE
§ 27-2005 ADM CODE PROPERLY REPAIR WITH SIMILAR MATERIAL THE BROKEN OR DEFECTIVE UNEVEN WOOD FLOOR IN THE 1st ROOM FROM NORTH LOCATED AT APT 1A, 1st STORY, 1st APARTMENT FROM WEST AT NORTH
Class BOpen
Sep 29, 2026Apt 701C
REPAIR OR REPLACE SMOKE DETECTOR · SMOKE DETECTING DEVICES
§ 27-2045(B)(1)(A) HMC, § 12-01, § 12-03 RCNY REPAIR, REPLACE OR PROVIDE AN APPROVED AND OPERATIONAL SMOKE DETECTING DEVICE, INSTALLED IN ACCORDANCE WITH DEPARTMENT OF BUILDINGS RULES AND REGULATIONS DEFECTIVE IN THE ENTIRE APARTMENT LOCATED AT APT 701C, 7th STORY, 11th APARTMENT FROM SOUTH AT WEST
Class AOpen
Sep 28, 2026
POST GAS LEAK NOTICE · POSTING/SIGNAGE
§ 27-2005 HMC: POST, IN A FORM APPROVED BY THE COMMISSIONER, AND MAINTAIN A NOTICE IN A COMMON AREA OF THE BUILDING REGARDING THE PROCEDURES THAT SHOULD BE FOLLOWED WHEN A GAS LEAK IS SUSPECTED
Class AOpen
Sep 28, 2026
IV-1. MAILBOXES PRESENT · POSTING/SIGNAGE
§ 329, M/D LAW AND DEPT. RULES AND REGS. PROVIDE A COMPLETED CERTIFICATE OF INSPECTION VISITS IN A PROPER FRAME AT OR NEAR MAILBOXES, BOTTOM EDGE OF FRAME BETWEEN 48-62 INCHES ABOVE FLOOR MISSING AT PUBLIC HALL
Class COpen
Sep 28, 2026Apt 5A
ABATE THE NUISANCE OF ROACHES · EXTERMINATION & RODENT ERADICATION
HMC ADM CODE: § 27-2017.4 ABATE THE INFESTATION CONSISTING OF ROACHES IN THE ENTIRE APARTMENT LOCATED AT APT 5A, 5th STORY, 1st APARTMENT FROM SOUTH AT WEST
Class AOpen
Sep 28, 2026
POST REGISTRATION SIGN · ANNUAL PROPERTY REGISTRATION
§ 27-2104 ADM CODE POST AND MAINTAIN A PROPER SIGN ON WALL OF ENTRANCE STORY SHOWING THE REGISTRATION NUMBER ASSIGNED BY THE DEPARTMENT AND THE ADDRESS OF THE BUILDING. AT PUBLIC HALL, 1st STORY
Class COpen
Sep 28, 2026
POST BOILER ROOM ACCESS NOTICE · HEAT AND HOT WATER
§ 27-2033 ADM CODE POST NOTICE, IN FORM APPROVED BY THE DEPARTMENT, STATING THE NAME AND LOCATION OF THE PERSON DESIGNATED BY THE OWNER TO HAVE KEY TO BUILDINGS HEATING SYSTEM MISSING AT PUBLIC HALL, 1st STORY
Class AOpen
Sep 28, 2026
POST HOUSING INFORMATION GUIDE NOTICE · POSTING/SIGNAGE
§ 26-1103 ADMIN. CODE: POST AND MAINTAIN A PROPER NOTICE ON WALL OF THE ENTRANCE STORY IN ENGLISH AND SPANISH ON THE AVAILABILITY OF THE AGENCYS HOUSING INFORMATION GUIDE. A SAMPLE NOTICE CAN BE FOUND AT WWW.NYC.GOV/HPD.
Class BOpen
Sep 28, 2026Apt 405
REPAIR · MAINTENANCE
§ 27-2005 HMC: PROPERLY REPAIR OR REPLACE THE BROKEN OR DEFECTIVE ELECTRICAL LIGHT FIXTIRE AT CEILING IN THE 1st ROOM FROM NORTH LOCATED AT APT 405, 4th STORY, 5th APARTMENT FROM WEST AT NORTH
Class AOpen
Sep 28, 2026
IV-1. MAILBOXES PRESENT · POSTING/SIGNAGE
§ 329, M/D LAW AND DEPT. RULES AND REGS. PROVIDE A COMPLETED CERTIFICATE OF INSPECTION VISITS IN A PROPER FRAME AT OR NEAR MAILBOXES, BOTTOM EDGE OF FRAME BETWEEN 48-62 INCHES ABOVE FLOOR MISSING AT PUBLIC HALL, 1st STORY
Class COpen
Sep 28, 2026Apt 405
SECURE LOOSE MATTER · MAINTENANCE
§ 27-2005 ADM CODE PROPERLY SECURE THE LOOSE ELECTRICAL LIGHT FIXTURE AT CEILING IN THE PRIVATE HALLWAY LOCATED AT APT 405, 4th STORY, 5th APARTMENT FROM WEST AT NORTH
Class AOpen
Sep 28, 2026
POST SMOKE DETECTOR NOTICE · POSTING/SIGNAGE
§27-2045(B)(5) HMC, § 12-01 RCNY POST A PROPER NOTICE OF SMOKE DETECTOR REQUIREMENTS, IN A FORM APPROVED BY THE COMMISSIONER, AT OR NEAR THE MAILBOX MISSING AT PUBLIC HALL, 1st STORY
Class AOpen
Sep 28, 2026
POST CO DETECTOR NOTICE · CARBON MONOXIDE DETECTING DEVICES
§27-2045(B)(5) HMC, § 12-06, 12-10 RCNY POST A PROPER NOTICE OF CARBON MONOXIDE DETECTING DEVICE REQUIREMENTS, IN A FORM APPROVED BY COMMISSIONER, IN A COMMON AREA OF A CLASS A MULTIPLE DWELLING NEAR INSPECTION CERTIFICATE OR PROVIDE NOTICE TO TENANTS IN PRIVATE DWELLINGS MISSING
Class AOpen
Sep 28, 2026
POST SIGN INDICATING NAME AND ADDRESS OF JANITOR, ETC. · POSTING/SIGNAGE
§ 27-2053 ADM CODE POST SIGN ON WALL OF ENTRANCE STORY BEARING NAME, ADDRESS INCLUDING APARTMENT NUMBER IF ANY, AND TELEPHONE NUMBER OF SUPERINTENDENT, JANITOR OR HOUSEKEEPER. AT PUBLIC HALL, 1st STORY
Class BOpen
Sep 25, 2026Apt 1A
REPAIR · MAINTENANCE
§ 27-2005 HMC: PROPERLY REPAIR OR REPLACE THE BROKEN OR DEFECTIVE LIGHT FIXTURE AT CEILING IN THE BATHROOM LOCATED AT APT 1A, 1st STORY, 1st APARTMENT FROM NORTH AT EAST
Class AOpen
Sep 25, 2026
POST SIGN INDICATING NAME AND ADDRESS OF JANITOR, ETC. · POSTING/SIGNAGE
§ 27-2053 ADM CODE POST SIGN ON WALL OF ENTRANCE STORY BEARING NAME, ADDRESS INCLUDING APARTMENT NUMBER IF ANY, AND TELEPHONE NUMBER OF SUPERINTENDENT, JANITOR OR HOUSEKEEPER. AT PUBLIC HALL, 1st STORY
Class BOpen
Sep 25, 2026Apt 1A
REPAIR THE SOURCE AND ABATE THE WATER LEAK · WATER SUPPLY
§ 27-2026, 2027 HMC: PROPERLY REPAIR THE SOURCE AND ABATE THE EVIDENCE OF A WATER LEAK AT CEILING IN THE BATHROOM LOCATED AT APT 1A, 1st STORY, 1st APARTMENT FROM NORTH AT EAST
Class BOpen
Sep 25, 2026Apt 1A
REPAIR PLASTER · MAINTENANCE
§ 27-2005 ADM CODE REPAIR THE BROKEN OR DEFECTIVE PLASTERED SURFACES AND PAINT IN A UNIFORM COLOR THE CEILING IN THE BATHROOM LOCATED AT APT 1A, 1st STORY, 1st APARTMENT FROM NORTH AT EAST
Class AOpen
Sep 25, 2026
POST GAS LEAK NOTICE · POSTING/SIGNAGE
§ 27-2005 HMC: POST, IN A FORM APPROVED BY THE COMMISSIONER, AND MAINTAIN A NOTICE IN A COMMON AREA OF THE BUILDING REGARDING THE PROCEDURES THAT SHOULD BE FOLLOWED WHEN A GAS LEAK IS SUSPECTED AT PUBLIC HALL, 1st STORY
Class COpen
Sep 25, 2026
POST BOILER ROOM ACCESS NOTICE · HEAT AND HOT WATER
§ 27-2033 ADM CODE POST NOTICE, IN FORM APPROVED BY THE DEPARTMENT, STATING THE NAME AND LOCATION OF THE PERSON DESIGNATED BY THE OWNER TO HAVE KEY TO BUILDINGS HEATING SYSTEM SIGNAGE DEFECTIVE/INFORMATION BLANK AT PUBLIC HALL, 1st STORY
Class AOpen
Sep 25, 2026
IV-1. MAILBOXES PRESENT · POSTING/SIGNAGE
§ 329, M/D LAW AND DEPT. RULES AND REGS. PROVIDE A COMPLETED CERTIFICATE OF INSPECTION VISITS IN A PROPER FRAME AT OR NEAR MAILBOXES, BOTTOM EDGE OF FRAME BETWEEN 48-62 INCHES ABOVE FLOOR FRAME MISSING AT PUBLIC HALL, 1st STORY
Class AOpen
Sep 25, 2026
POST REGISTRATION SIGN · ANNUAL PROPERTY REGISTRATION
§ 27-2104 ADM CODE POST AND MAINTAIN A PROPER SIGN ON WALL OF ENTRANCE STORY SHOWING THE REGISTRATION NUMBER ASSIGNED BY THE DEPARTMENT AND THE ADDRESS OF THE BUILDING. AT PUBLIC HALL, 1st STORY
Class AOpen
Sep 25, 2026
RENT STABILIZATION LAW INFORMATION SIGN · POSTING/SIGNAGE
§27-2104(B) HMC POST A PROPER NOTICE REGARDING RENT STABILIZATION LAW, IN A FORM APPROVED BY THE COMMISSIONER, IN A CONSPICUOUS LOCATION WITHIN THE COMMON AREA AT THE BUILDINGS ENTRANCE. FOR MORE INFORMATION ABOUT SIGNAGE REQUIREMENTS, PLEASE VISIT: HTTPS://WWW.NYC.GOV/SITE/HPD/SERVICES-AND-INFORMATION/REQUIRED-SIGNAGE.PAGE
Class BOpen
Sep 25, 2026Apt 1A
REPAIR THE SOURCE AND ABATE THE WATER LEAK · WATER SUPPLY
§ 27-2026, 2027 HMC: PROPERLY REPAIR THE SOURCE AND ABATE THE EVIDENCE OF A WATER LEAK AT NORTH WALL IN THE 1st ROOM FROM NORTH LOCATED AT APT 1A, 1st STORY, 1st APARTMENT FROM NORTH AT EAST
Class AOpen
Sep 25, 2026Apt 1A
TRACE & REPAIR THE SOURCE & ABATE THE…MOLD · CLEANING
§ 27-2017.3 HMC: TRACE AND REPAIR THE SOURCE AND ABATE THE VISIBLE MOLD CONDITION... LESS THAN 10 SQUARE FEET OBSERVED AT CEILING IN THE BATHROOM LOCATED AT APT 1A, 1st STORY, 1st APARTMENT FROM NORTH AT EAST