Class BOpen
Feb 25, 2026Apt 6D
REPAIR · MAINTENANCE
§ 27-2005 HMC: PROPERLY REPAIR OR REPLACE THE BROKEN OR DEFECTIVE INTERCOMMUNICATION SYSTEM FROM BUILDING FRONT TO EAST WALL IN THE FOYER LOCATED AT APT 6D, 6th STORY, 1st APARTMENT FROM WEST AT NORTH
Class BOpen
Feb 25, 2026Apt 6C
REPAIR · MAINTENANCE
§ 27-2005 HMC: PROPERLY REPAIR OR REPLACE THE BROKEN OR DEFECTIVE INTERCOMMUNUCATION SYSTEM FROM BUILDING FRONT TO SOUTH WALL IN THE FOYER LOCATED AT APT 6C, 6th STORY, 2nd APARTMENT FROM SOUTH AT WEST
Class BOpen
Feb 25, 2026Apt 7G
REPAIR · MAINTENANCE
§ 27-2005 HMC: PROPERLY REPAIR OR REPLACE THE BROKEN OR DEFECTIVE INTERCOMMUNUCATION SYSTEM FROM BUILDING FRONT TO WEST WALL IN THE FOYER LOCATED AT APT 7G, 7th STORY, 4th APARTMENT FROM WEST AT NORTH
Class BOpen
Feb 25, 2026Apt 7G
REPAIR PLASTER · MAINTENANCE
§ 27-2005 ADM CODE REPAIR THE BROKEN OR DEFECTIVE PLASTERED SURFACES AND PAINT IN A UNIFORM COLOR AT EAST AND SOUTH WALL IN THE 1st ROOM FROM EAST LOCATED AT APT 7G, 7th STORY, 4th APARTMENT FROM WEST AT NORTH
Class COpen
Feb 25, 2026Apt 8D
ABATE THE NUISANCE OF ROACHES · EXTERMINATION & RODENT ERADICATION
HMC ADM CODE: § 27-2017.4 ABATE THE INFESTATION CONSISTING OF ROACHES IN THE ENTIRE APARTMENT LOCATED AT APT 8D, 8th STORY, 1st APARTMENT FROM WEST AT NORTH
Class BOpen
Feb 25, 2026Apt 7G
REPAIR THE SOURCE AND ABATE THE WATER LEAK · WATER SUPPLY
§ 27-2026, 2027 HMC: PROPERLY REPAIR THE SOURCE AND ABATE THE EVIDENCE OF A WATER LEAK AT EAST AND SOUTH WALL IN THE 1st ROOM FROM EAST LOCATED AT APT 7G, 7th STORY, 4th APARTMENT FROM WEST AT NORTH
Class BOpen
Feb 25, 2026Apt 6E
REPAIR WITH SIMILAR MATERIAL · MAINTENANCE
§ 27-2005 ADM CODE PROPERLY REPAIR WITH SIMILAR MATERIAL THE BROKEN OR DEFECTIVE WOOD BASE CABINET FLOOR AT EAST IN THE KITCHEN LOCATED AT APT 6E, 6th STORY, 2nd APARTMENT FROM WEST AT NORTH
Class BOpen
Feb 25, 2026Apt 7G
CORRECT FAILURE TO INSTALL TEMPERATURE REPORTING DEVICE · HEAT SENSOR PROGRAM
§27-2033.3(B) CORRECT FAILURE TO INSTALL AN INTERNET CAPABLE TEMPERATURE REPORTING DEVICE IN ONE LIVING ROOM IN APARTMENT MISSING IN THE ENTIRE APARTMENT LOCATED AT APT 7G, 7th STORY, 4th APARTMENT FROM WEST AT NORTH
Class AClosed
Feb 25, 2026Apt 5A
TRACE & REPAIR THE SOURCE & ABATE THE…MOLD · CLEANING
§ 27-2017.3 HMC: TRACE AND REPAIR THE SOURCE AND ABATE THE VISIBLE MOLD CONDITION... LESS THEN 10 SQ FEET AT CEILING IN THE PRIVATE HALLWAY LOCATED AT APT 5A, 5th STORY, 3rd APARTMENT FROM EAST AT SOUTH
Class BClosed
Feb 25, 2026Apt 5A
TRACE & REPAIR THE SOURCE & ABATE THE…MOLD · CLEANING
§ 27-2017.3 HMC: TRACE AND REPAIR THE SOURCE AND ABATE THE VISIBLE MOLD CONDITION... GREATER THEN 10 SQ FEET AT CEILING AND SOUTH AND NORTH WALL IN THE BATHROOM LOCATED AT APT 5A, 5th STORY, 3rd APARTMENT FROM EAST AT SOUTH
Class BOpen
Feb 25, 2026Apt 7D
REPAIR · MAINTENANCE
§ 27-2005 HMC: PROPERLY REPAIR OR REPLACE THE BROKEN OR DEFECTIVE INTERCOMMUNUCATION SYSTEM FROM BUILDING FRONT TO WEST WALL IN THE FOYER LOCATED AT APT 7D, 7th STORY, 1st APARTMENT FROM WEST AT NORTH
Class BOpen
Feb 25, 2026Apt 8D
CORRECT FAILURE TO INSTALL TEMPERATURE REPORTING DEVICE · HEAT SENSOR PROGRAM
§27-2033.3(B) CORRECT FAILURE TO INSTALL AN INTERNET CAPABLE TEMPERATURE REPORTING DEVICE IN ONE LIVING ROOM IN APARTMENT MISSING IN THE ENTIRE APARTMENT LOCATED AT APT 8D, 8th STORY, 1st APARTMENT FROM WEST AT NORTH
Class COpen
Feb 25, 2026Apt 6E
MAKE DOORS SELF-CLOSING · EGRESS
§ 27-2005, 27-2007, 27-2041.1 HMC, §238, § 309; § 107 (2) ( C) MDL AND 28 RCNY §25-171: REPLACE OR REPAIR THE SELF-CLOSING DOORS THAT IS MISSING OR DEFECTIVE LATCH SET IN THE ENTRANCE LOCATED AT APT 6E, 6th STORY, 2nd APARTMENT FROM WEST AT NORTH
Class AClosed
Feb 25, 2026Apt 6C
TRACE & REPAIR THE SOURCE & ABATE THE…MOLD · CLEANING
§ 27-2017.3 HMC: TRACE AND REPAIR THE SOURCE AND ABATE THE VISIBLE MOLD CONDITION... LESS THEN 10 SQ FEET AT WEST WALL IN THE BATHROOM LOCATED AT APT 6C, 6th STORY, 2nd APARTMENT FROM SOUTH AT WEST
Class BOpen
Feb 25, 2026Apt 5A
CORRECT FAILURE TO INSTALL TEMPERATURE REPORTING DEVICE · HEAT SENSOR PROGRAM
§27-2033.3(B) CORRECT FAILURE TO INSTALL AN INTERNET CAPABLE TEMPERATURE REPORTING DEVICE IN ONE LIVING ROOM IN APARTMENT MISSING IN THE ENTIRE APARTMENT LOCATED AT APT 5A, 5th STORY, 3rd APARTMENT FROM EAST AT SOUTH
Class BOpen
Feb 25, 2026Apt 6C
CORRECT FAILURE TO INSTALL TEMPERATURE REPORTING DEVICE · HEAT SENSOR PROGRAM
§27-2033.3(B) CORRECT FAILURE TO INSTALL AN INTERNET CAPABLE TEMPERATURE REPORTING DEVICE IN ONE LIVING ROOM IN APARTMENT MISSING IN THE ENTIRE APARTMENT LOCATED AT APT 6C, 6th STORY, 2nd APARTMENT FROM SOUTH AT WEST
Class BClosed
Feb 25, 2026Apt 8D
REPAIR · MAINTENANCE
§ 27-2005 HMC: PROPERLY REPAIR OR REPLACE THE BROKEN OR DEFECTIVE NTERCOMMUNUCATION SYSTEM FROM BUILDING FRONT TO EAST WALL IN THE FOYER LOCATED AT APT 8D, 8th STORY, 1st APARTMENT FROM WEST AT NORTH
Class BOpen
Feb 25, 2026Apt 7D
CORRECT FAILURE TO INSTALL TEMPERATURE REPORTING DEVICE · HEAT SENSOR PROGRAM
§27-2033.3(B) CORRECT FAILURE TO INSTALL AN INTERNET CAPABLE TEMPERATURE REPORTING DEVICE IN ONE LIVING ROOM IN APARTMENT MISSING IN THE ENTIRE APARTMENT LOCATED AT APT 7D, 7th STORY, 1st APARTMENT FROM WEST AT NORTH
Class BOpen
Feb 23, 2026Apt 8E
CORRECT FAILURE TO INSTALL TEMPERATURE REPORTING DEVICE · HEAT SENSOR PROGRAM
§27-2033.3(B) CORRECT FAILURE TO INSTALL AN INTERNET CAPABLE TEMPERATURE REPORTING DEVICE IN ONE LIVING ROOM IN APARTMENT MISSING IN THE ENTIRE APARTMENT LOCATED AT APT 8E, 8th STORY, 2nd APARTMENT FROM WEST AT NORTH
Class CClosed
Feb 23, 2026
MAKE DOORS SELF-CLOSING · EGRESS
§ 27-2005, 27-2007, 27-2041.1 HMC, §238, § 309; § 107 (2) ( C) MDL AND 28 RCNY §25-171: REPLACE OR REPAIR THE SELF-CLOSING DOORS THAT IS MISSING OR DEFECTIVE LATCH SET AT FIRE STAIR DOOR A AT PUBLIC HALL, 5th STORY
Class COpen
Feb 23, 2026Apt 8E
MAKE DOORS SELF-CLOSING · EGRESS
§ 27-2005, 27-2007, 27-2041.1 HMC, §238, § 309; § 107 (2) ( C) MDL AND 28 RCNY §25-171: REPLACE OR REPAIR THE SELF-CLOSING DOORS THAT IS MISSING OR DEFECTIVE HINGES IN THE ENTRANCE LOCATED AT APT 8E, 8th STORY, 2nd APARTMENT FROM WEST AT NORTH
Class CClosed
Feb 20, 2026Apt 15F
ABATE THE NUISANCE · MAINTENANCE
§ 27-2005 ADM CODE & 309 M/D LAW ABATE THE NUISANCE CONSISTING OF UNCAPPED GASLINE AT EAST WALL IN THE KITCHEN LOCATED AT APT 15F, 14th STORY, SECTION ''530''
Class BClosed
Feb 20, 2026Apt 15F
TRACE & REPAIR THE SOURCE & ABATE THE…MOLD · CLEANING
§ 27-2017.3 HMC: TRACE AND REPAIR THE SOURCE AND ABATE THE VISIBLE MOLD CONDITION... MORE THAN 10 SQFT AND LESS THAN 30 SQFT AT CEILIING IN THE BATHROOM LOCATED AT APT 15F, 14th STORY, SECTION ''530''
Class CClosedRENT IMPAIRING
Feb 20, 2026Apt 16C
INADEQUATE HOT WATER · HEAT AND HOT WATER
§ 27-2031 ADM CODE PROVIDE HOT WATER AT ALL HOT WATER FIXTURES IN THE ENTIRE APARTMENT LOCATED AT APT 16C, 15th STORY, 2nd APARTMENT FROM EAST AT SOUTH , SECTION ''530''
Class CClosed
Feb 10, 2026Apt 9F
PROVIDE ADEQUATE HEAT · HEAT AND HOT WATER
§ 27-2028, 2032 ADM CODE PROVIDE AN ADEQUATE SUPPLY OF HEAT FROM AN APPROVED CENTRAL HEATING SYSTEM, OR AN APPROVED SYSTEM OF GAS OR ELECTRICAL HEATING IN GOOD OPERATING CONDITION FOR THE DWELLING UNIT IN THE ENTIRE APARTMENT LOCATED AT APT 9F, 9th STORY, 2nd APARTMENT FROM SOUTH AT WEST , SECTION ''540''
Class CClosedRENT IMPAIRING
Feb 10, 2026Apt 8J
INADEQUATE HOT WATER · HEAT AND HOT WATER
§ 27-2031 ADM CODE PROVIDE HOT WATER AT ALL HOT WATER FIXTURES IN THE ENTIRE APARTMENT LOCATED AT APT 8J, 8th STORY, 3rd APARTMENT FROM NORTH AT EAST , SECTION ''540''
Class BOpen
Feb 10, 2026Apt 8K
CORRECT FAILURE TO INSTALL TEMPERATURE REPORTING DEVICE · HEAT SENSOR PROGRAM
§27-2033.3(B) CORRECT FAILURE TO INSTALL AN INTERNET CAPABLE TEMPERATURE REPORTING DEVICE IN ONE LIVING ROOM IN APARTMENT ... LOCATED AT APT 8K, 8th STORY, 2nd APARTMENT FROM NORTH AT EAST , SECTION ''540''
Class COpen
Feb 10, 2026Apt 8B
ABATE THE NUISANCE OF ROACHES · EXTERMINATION & RODENT ERADICATION
HMC ADM CODE: § 27-2017.4 ABATE THE INFESTATION CONSISTING OF ROACHES IN THE ENTIRE APARTMENT LOCATED AT APT 8B, 8th STORY, 2nd APARTMENT FROM WEST AT NORTH , SECTION ''540''
Class BOpen
Feb 10, 2026Apt 8B
CORRECT FAILURE TO INSTALL TEMPERATURE REPORTING DEVICE · HEAT SENSOR PROGRAM
§27-2033.3(B) CORRECT FAILURE TO INSTALL AN INTERNET CAPABLE TEMPERATURE REPORTING DEVICE IN ONE LIVING ROOM IN APARTMENT ... LOCATED AT APT 8B, 8th STORY, 2nd APARTMENT FROM WEST AT NORTH , SECTION ''540''
Class CClosed
Feb 10, 2026Apt 8K
PROVIDE ADEQUATE HEAT · HEAT AND HOT WATER
§ 27-2028, 2032 ADM CODE PROVIDE AN ADEQUATE SUPPLY OF HEAT FROM AN APPROVED CENTRAL HEATING SYSTEM, OR AN APPROVED SYSTEM OF GAS OR ELECTRICAL HEATING IN GOOD OPERATING CONDITION FOR THE DWELLING UNIT IN THE ENTIRE APARTMENT LOCATED AT APT 8K, 8th STORY, 2nd APARTMENT FROM NORTH AT EAST , SECTION ''540''
Class BOpen
Feb 10, 2026Apt 9K
CORRECT FAILURE TO INSTALL TEMPERATURE REPORTING DEVICE · HEAT SENSOR PROGRAM
§27-2033.3(B) CORRECT FAILURE TO INSTALL AN INTERNET CAPABLE TEMPERATURE REPORTING DEVICE IN ONE LIVING ROOM IN APARTMENT ... LOCATED AT APT 9K, 9th STORY, 2nd APARTMENT FROM NORTH AT EAST , SECTION ''540''
Class CClosedRENT IMPAIRING
Feb 10, 2026Apt 8K
INADEQUATE HOT WATER · HEAT AND HOT WATER
§ 27-2031 ADM CODE PROVIDE HOT WATER AT ALL HOT WATER FIXTURES IN THE ENTIRE APARTMENT LOCATED AT APT 8K, 8th STORY, 2nd APARTMENT FROM NORTH AT EAST , SECTION ''540''
Class BOpen
Feb 10, 2026Apt 8J
CORRECT FAILURE TO INSTALL TEMPERATURE REPORTING DEVICE · HEAT SENSOR PROGRAM
§27-2033.3(B) CORRECT FAILURE TO INSTALL AN INTERNET CAPABLE TEMPERATURE REPORTING DEVICE IN ONE LIVING ROOM IN APARTMENT ... LOCATED AT APT 8J, 8th STORY, 3rd APARTMENT FROM NORTH AT EAST , SECTION ''540''
Class CClosedRENT IMPAIRING
Feb 10, 2026Apt 8G
INADEQUATE HOT WATER · HEAT AND HOT WATER
§ 27-2031 ADM CODE PROVIDE HOT WATER AT ALL HOT WATER FIXTURES IN THE ENTIRE APARTMENT LOCATED AT APT 8G, 8th STORY, 1st APARTMENT FROM SOUTH AT WEST , SECTION ''540''
Class CClosed
Feb 10, 2026Apt 8G
MAKE DOORS SELF-CLOSING · EGRESS
§ 27-2005, 27-2007, 27-2041.1 HMC, §238, § 309; § 107 (2) ( C) MDL AND 28 RCNY §25-171: REPLACE OR REPAIR THE SELF-CLOSING DOORS THAT IS MISSING OR DEFECTIVE HINGES IN THE ENTRANCE LOCATED AT APT 8G, 8th STORY, 1st APARTMENT FROM SOUTH AT WEST , SECTION ''540''
Class COpen
Feb 10, 2026Apt 9K
ABATE THE NUISANCE OF ROACHES · EXTERMINATION & RODENT ERADICATION
HMC ADM CODE: § 27-2017.4 ABATE THE INFESTATION CONSISTING OF ROACHES IN THE ENTIRE APARTMENT LOCATED AT APT 9K, 9th STORY, 2nd APARTMENT FROM NORTH AT EAST , SECTION ''540''
Class CClosedRENT IMPAIRING
Feb 10, 2026Apt 9F
INADEQUATE HOT WATER · HEAT AND HOT WATER
§ 27-2031 ADM CODE PROVIDE HOT WATER AT ALL HOT WATER FIXTURES IN THE ENTIRE APARTMENT LOCATED AT APT 9F, 9th STORY, 2nd APARTMENT FROM SOUTH AT WEST , SECTION ''540''
Class CClosedRENT IMPAIRING
Feb 10, 2026Apt 9K
INADEQUATE HOT WATER · HEAT AND HOT WATER
§ 27-2031 ADM CODE PROVIDE HOT WATER AT ALL HOT WATER FIXTURES IN THE ENTIRE APARTMENT LOCATED AT APT 9K, 9th STORY, 2nd APARTMENT FROM NORTH AT EAST , SECTION ''540''
Class CClosedRENT IMPAIRING
Feb 10, 2026Apt 9E
INADEQUATE HOT WATER · HEAT AND HOT WATER
§ 27-2031 ADM CODE PROVIDE HOT WATER AT ALL HOT WATER FIXTURES IN THE ENTIRE APARTMENT LOCATED AT APT 9E, 9th STORY, 3rd APARTMENT FROM SOUTH AT WEST , SECTION ''540''
Class CClosedRENT IMPAIRING
Feb 10, 2026Apt 9J
INADEQUATE HOT WATER · HEAT AND HOT WATER
§ 27-2031 ADM CODE PROVIDE HOT WATER AT ALL HOT WATER FIXTURES IN THE ENTIRE APARTMENT LOCATED AT APT 9J, 9th STORY, 3rd APARTMENT FROM NORTH AT EAST , SECTION ''540''
Class BOpen
Feb 10, 2026Apt 9E
CORRECT FAILURE TO INSTALL TEMPERATURE REPORTING DEVICE · HEAT SENSOR PROGRAM
§27-2033.3(B) CORRECT FAILURE TO INSTALL AN INTERNET CAPABLE TEMPERATURE REPORTING DEVICE IN ONE LIVING ROOM IN APARTMENT ... LOCATED AT APT 9E, 9th STORY, 3rd APARTMENT FROM SOUTH AT WEST , SECTION ''540''
Class BOpen
Feb 10, 2026Apt 9J
CORRECT FAILURE TO INSTALL TEMPERATURE REPORTING DEVICE · HEAT SENSOR PROGRAM
§27-2033.3(B) CORRECT FAILURE TO INSTALL AN INTERNET CAPABLE TEMPERATURE REPORTING DEVICE IN ONE LIVING ROOM IN APARTMENT ... LOCATED AT APT 9J, 9th STORY, 3rd APARTMENT FROM NORTH AT EAST , SECTION ''540''
Class CClosed
Feb 10, 2026Apt 9K
REPAIR · MAINTENANCE
§ 27-2005 HMC: PROPERLY REPAIR OR REPLACE THE BROKEN OR DEFECTIVE MORTISE LOCK AT DOOR IN THE ENTRANCE LOCATED AT APT 9K, 9th STORY, 2nd APARTMENT FROM NORTH AT EAST , SECTION ''540''
Class CClosed
Feb 10, 2026Apt 8B
PROVIDE ADEQUATE HEAT · HEAT AND HOT WATER
§ 27-2028, 2032 ADM CODE PROVIDE AN ADEQUATE SUPPLY OF HEAT FROM AN APPROVED CENTRAL HEATING SYSTEM, OR AN APPROVED SYSTEM OF GAS OR ELECTRICAL HEATING IN GOOD OPERATING CONDITION FOR THE DWELLING UNIT IN THE ENTIRE APARTMENT LOCATED AT APT 8B, 8th STORY, 2nd APARTMENT FROM WEST AT NORTH , SECTION ''540''
Class CClosedRENT IMPAIRING
Feb 10, 2026Apt 8B
INADEQUATE HOT WATER · HEAT AND HOT WATER
§ 27-2031 ADM CODE PROVIDE HOT WATER AT ALL HOT WATER FIXTURES IN THE ENTIRE APARTMENT LOCATED AT APT 8B, 8th STORY, 2nd APARTMENT FROM WEST AT NORTH , SECTION ''540''
Class COpen
Feb 10, 2026Apt 9J
ABATE THE NUISANCE OF ROACHES · EXTERMINATION & RODENT ERADICATION
HMC ADM CODE: § 27-2017.4 ABATE THE INFESTATION CONSISTING OF ROACHES IN THE ENTIRE APARTMENT LOCATED AT APT 9J, 9th STORY, 3rd APARTMENT FROM NORTH AT EAST , SECTION ''540''
Class BOpen
Feb 10, 2026Apt 9F
CORRECT FAILURE TO INSTALL TEMPERATURE REPORTING DEVICE · HEAT SENSOR PROGRAM
§27-2033.3(B) CORRECT FAILURE TO INSTALL AN INTERNET CAPABLE TEMPERATURE REPORTING DEVICE IN ONE LIVING ROOM IN APARTMENT ... LOCATED AT APT 9F, 9th STORY, 2nd APARTMENT FROM SOUTH AT WEST , SECTION ''540''
Class BOpen
Feb 10, 2026Apt 8G
CORRECT FAILURE TO INSTALL TEMPERATURE REPORTING DEVICE · HEAT SENSOR PROGRAM
§27-2033.3(B) CORRECT FAILURE TO INSTALL AN INTERNET CAPABLE TEMPERATURE REPORTING DEVICE IN ONE LIVING ROOM IN APARTMENT ... LOCATED AT APT 8G, 8th STORY, 1st APARTMENT FROM SOUTH AT WEST , SECTION ''540''
Class BClosed
Feb 10, 2026Apt 9D
TRACE & REPAIR THE SOURCE & ABATE THE…MOLD · CLEANING
§ 27-2017.3 HMC: TRACE AND REPAIR THE SOURCE AND ABATE THE VISIBLE MOLD CONDITION... GREATER THAN 10 SQ.FT. AT CEILING AND NORTH WALL IN THE BATHROOM LOCATED AT APT 9D, 9th STORY, 4th APARTMENT FROM SOUTH AT WEST , SECTION ''540''
Class COpen
Feb 10, 2026
MAKE DOORS SELF-CLOSING · EGRESS
§ 27-2005, 27-2007, 27-2041.1 HMC, §238, § 309; § 107 (2) ( C) MDL AND 28 RCNY §25-171: REPLACE OR REPAIR THE SELF-CLOSING DOORS THAT IS MISSING OR DEFECTIVE ARM CLOSER DEVICE AT BUILDING ENTRANCE DOOR (FROM ENTRANCE TO VESTIBULE) , 1st STORY, SECTION ''540''